COMPACT-MULTI – INSTALLATION/OPERATION MANUAL
5IM-OF-K4C0-01 Jun/12
9
2.14 OFF CYCLE AIR CIRCULATION
#4 LO SPEED All models have the #4 Lo speed switch for optional constant air circulation
during the furnace off cycle.
“FAN ON” When “FAN ON” is selected on the thermostat, the blower will run constantly
at the #1 Hi speed providing heat, cooling or neither as selected.
3.0 BURNER SPECIFICATIONS
Model Burner Input Nozzle Pump Air
Setting Turbulator Output Heating CFM@ Blower Speed
USGPH L/h Btu/h (psi) Btu/h kW 0.2"wc 0.5"wc 0.2"wc 0.5"wc
K4C-E1-0090-03 Riello 40 F3 0.61 2.31 85,400 0.50 80B 150 2.8 0.5 74,000 22 990 990 4 3
0.73 2.76 102,200 0.60 60W 3.5 1.0 88,000 26 1180 1090 3 2
K4C-G3-K098-03
Beckett AFG-F0 0.61 2.31 85,400 0.50 70W 150 6/0 - 73,000 21 1050 1050 3 2
Beckett AFG-F3 0.73 2.76 102,200 0.60 70W 150 7/0 - 88,000 26 1150 1100 2 1
0.79 2.99 110,600 0.65 70W 9/0 - 93,000 27 1150 1100 2 1
K4C-N1-K098-03 Beckett NX-LH
0.61 2.31 85,400 0.50 60A
150
2.3 - 75,000 22 1050 1050 3 2
0.73 2.76 102,200 0.60 60A 3.5 - 88,000 26 1150 1100 2 1
0.81 3.07 113,400 0.65 60A 4.0 - 98,000 29 1150 1100 2 1
Direct Vent
K4C-V1-0090-03 Riello BF3
0.61 2.31 85,400 0.50 80W 150 5.0 0.5 74,000 22 990 990 4 3
0.73 2.76 102,200 0.60 60W 6.0 1.5 88,000 26 1180 1090 3 2
The turbulator & air settings found in this section should be used as a guide.
With ECM motors, the last 2 digits of the model number are E3 instead of 03.
4.0 BLOCKED VENT SWITCH
Oil-fired appliances installed in Canada require a blocked vent shut-off system when installed
on a chimney. A safety switch is included with the furnace to perform this function. It is the
installer’s responsibility to install the switch in accordance with the instructions provided. Not
applicable for Direct Vent systems.
Field Controls Model: WMO-1 (Manual Reset)
Switch Operation
Blocked vent switches are flue gas safety devices for detecting spillage of flue gases due to a
blocked flue or inadequate draft. After detecting a problem, the switch de-energizes the
system’s burner control.
NEVER reset the switch unless the cause of the blockage has been corrected.