A. General description
HDL KNX / EIB M/DLP04.1-A2-48 wall switch Panel controller have 3 page for lighting and curtain
control, one page for floor heating, one page for HVAC control.This manual contains the programming
information for this module.
Note:
Programming: 1 button + 10 button
Lock or Unlock: 2 button + 9 button
Basic information setting: 9 button +10 button
Programming: Keep pressing 1 and 10 buttons together for 2 seconds, the LED Indicators will
flashing.
Lock or Unlock: keep pressing 2 and 9 buttons together for 2s, will lock the panel or unlock
the panel.
Basic information setting: keep pressing 9 and 10 buttons together for 2s, Will enter the
main menu page.
In this page can set LCD and LED brightness, Conversion from degrees Celsius to Fahrenheit,
or form Fahrenheit to degrees Celsius, etc.

APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Guangzhou Hedong Electric Co., Ltd. (HDL) - www.hdlautomation.com 5/88
B. Function overview flowchart
Start
1.0 General
1.1 General
2.0 Functions
2.1 Rocker
2.2 FCU
2.3 Floor Heating
2.4 Air-condition
2.1.1 Rocker A
2.1.2 Rocker B
2.1.3 Rocker C
2.1.4 Rocker D
2.1.5 Rocker E
2.1.6 Rocker F
2.1.7 Rocker G
2.1.8 Rocker H
2.1.9 Rocker I
2.1.10 Rocker J
2.1.11 Rocker K
2.1.12 Rocker L
2.2.2 Heating output
2.3.1 FH output
2.4.1 AC ouput
Switch controller
Dimming controller
Shutter controller
Flexible controller
Scene controller
Sequence controller
Percentage controller
Threshold controller
String(14bytes) controller
Alternate controller
Combination controller
2.2.3 Cooling output
2.2.1 Fan output
2.2.4 Heating and Cooling

APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Guangzhou Hedong Electric Co., Ltd. (HDL) - www.hdlautomation.com 6/88
C. Function description
1.0_general 1
No.
ETS-Parameter
Range (default)
Description
1
System delay(0...255s)
(0)...255s
Set system delsy time.
2
Hearbeat telegram
-Disable
-Send value“0”cyclically
-Send value“1”cyclically
-Send value“1/0”
inverted cyclically
Disable: No hearbeat telegram.
Send value“0”cyclically: Cycling to
send the hearbeat telegram “0”.
Send value“1”cyclically: Cycling to
send the hearbeat telegram “1”.
Send value“1/0”inverted cyclically:
Cycling to send the hearbeat
telegram “0/1”.
3
->LCD display of the rocker
buttons image
-Buttons image “same
source”
-Buttons image
“independent source”
Buttons image “same source”: All
button’s images are the same
image source.
Buttons image “independent
source”: You can download
different images for every button.
_Brightness of button LED
4
Brightness of button LED ON
Level 00%...(100%)
Set brightness of button LED ON.
5
Brightness of button LED
OFF
Level (00%)...100%
Set brightness of button LED OFF.
6
Change brightness of button
-Disable
Disable: The LED ON brightness of

APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Guangzhou Hedong Electric Co., Ltd. (HDL) - www.hdlautomation.com 7/88
LED ON via EIB
-Enable
the buttons can’t changed by
other KNX/EIB devices.
Enable: Other devices on the bus
can send telegram to change the
LED ON brightness of the buttons.
7
Change brightness of button
LED OFF via EIB
-Disable
-Enable
Disable: The LED OFF brightness of
the buttons can’t changed by
other KNX/EIB devices.
Enable: Other devices on the bus
can send telegram to change the
LED OFF brightness of the buttons.
_Brightness of the LCD
8
Brightness of the LCD
Level 00%...(100%)
Set the LCD level of the backlight.
9
Change brightness of LCD
via EIB
-Disable
-Enable
Disable: The LCD’s brightness can’t
changed by other KNX/EIB
devices.
Enable: Other devices on the bus
can send telegram to change LCD’s
brightness.
_Automatic darker
10
LCD and LED brightness
automatic darker
-Disable
-Enable
It’s energy- saving mode.if enable,
LCD and LED brightness will
automatic darker after a set delay.
11
--LCD and LED brightness
automatic darker after a
delay
3...(5)...255s
Set the delay time of LCD and LED
brightness automatic darker.
12
--LED brightness automatic
darker at ON
Level 00%...(20%)...100%
Set the LED brightness level of
automatic darker at ON.
13
--LCD brightness automatic
darker
Level (00%)...100%
Set the LCD brightness level of
automatic darker.

APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Guangzhou Hedong Electric Co., Ltd. (HDL) - www.hdlautomation.com 8/88
14
--The operation of first time
press the button
-Normal operation
-The brightness of ON
status
Normal operation: Operate
normally according to the setting
of the button.
The brightness of ON status: The
operation of first time press the
button the brightness of ON
status.
15
Active infrared function via
bus
-Disable
-Enable
Enable or disable for Active
infrared function via bus.
16
Infrared default active status
-Inactive
-Active
Inactive: Infrared default status is
inactive.
Active: Infrared default status is
active.
17
Lock the buttons via EIB
-Disable
-Enable
Disable: Can’t lock the buttons via
EIB.
Enable: Can lock the buttons via
EIB.
_ The button trigger
18
Enable buttons is triggered
via EIB
-Disable
-Enable
Enable or disable for buttons is
triggered via EIB.
19
--The button trigger
condition
- ‘0’-trigger
- ‘1’-trigger
‘0’-trigger: Press ‘0’ the button
trigger.
‘1’-trigger:Press ‘1’ the button
trigger.
20
--Enable rocker A...D
-No
The DLP panel there are 5 pages,

APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Guangzhou Hedong Electric Co., Ltd. (HDL) - www.hdlautomation.com 9/88
buttons is triggered via EIB
-Yes
the first include A,B,C,D buttons.
This parameter is set can or can’t
trigger these buttons via EIB.
21
--Enable rocker E...H buttons
is triggered via EIB
-No
-Yes
This is the second page.
This parameter is set can or can’t
trigger E...H buttons via EIB.
22
--Enable rocker I...L buttons
is triggered via EIB
-No
-Yes
This is the third page.
This parameter is set can or can’t
trigger I...L buttons via EIB.
23
Enable Slave Clock
-Disable
-Enable
Inside DLP panel has a slave clock,
if enable and the time can
displayed on DLP.
24
Read the object status of
the rockers
-Disable
-Enable
Set enable or disable read the
object status of the rockers.
25
--Delay for read the object
status(5...255s)
(5)...255s
Set the delay time for read the
object status.
1.1_General 2

APPLICATION PROGRAM INFORMATION–LCDPanelController (V1.1), M/DLP04.1-A2-48- Version 1.1
Guangzhou Hedong Electric Co., Ltd. (HDL) - www.hdlautomation.com 10 /88
No.
ETS-Parameter
Range (default)
Description
=>Temperature show mode
1
Temperature show mode
-Degrees Celsius
-Degrees Fahrenheit
Set temperature show mode:
Celsius(C)
Fahrenheit(F)
=>Local temperature
2
The local temperature
correction(-5C...+5C)
-5C...(0C)...+5C
DLP panel embedded with a
temperature sensor, sometimes
has deviation, you can correction
it by set the parameter.
3
Local temperature report(In
range)
-No
-Yes
Report the local temperaturein
range.
4
->Temperature=>Threshold1
(-30C...+99C)
-30C...(0C)...+99C
Set the temperature show
threshold1.
5
->Temperature=>Threshold2
(-30C...+99C)
-30C...(0C)...+99C
Set the temperature show
threshold2.
6
--Temperature report mode
-Report when changed
-Report cyclic
Report when changed: The
temperature is reported when the
temperature changed.
Report cyclic: Always report
temperature values in a loop.
7
--Temperature report of
check period(1...65535s)
1...(5)...65535s
Set the time for temperature
report of check period.
=>Information zone of rocker page
8
Display date and time
-No
-Yes
Set the rocker page whether dislay
date and time.
9
Display temperatur(Celsius
degrees)
-No
-Yes
Set the rocker page whether dislay
temperatur(Celsius degrees) .
10
Display temperatur(Celsius
degrees)
-Local sensor
-Via EIB
Local sensor:The display
temperature is read through the
local sensor.
Via EIB: The display temperature is
controlled via EIB.
11
--Temperature correction
value(-5C...+5C)
-5C...(0C)...+5C
Set the temperature correction
value.
12
Scrolling information
displayed time
interval(5...255s)
(5)...255s
Set the DLP panel scrolling
information displayed time
interval.