HELVAR digidim 317 Manuale utente

Helvar | Data is subject to change without notice. 1
Installation Guide
Sensor lens
- PIR Sensor
- Status LED
- IR Receiver
Mounting bezel Retaining spring
Retaining spring
DALI +
DALI
-
PIR Sensor
Detects movement within the detection range, allowing load control in response to changes in room occupancy.
Status LED
The red LED flashes to indicate: Valid setting received (single flash of LED)
Identify active (LED flashes repeatedly)
DALI Connection
The DALI connection is made via DA+ and DA– terminals. The device is not polarity-sensitive.
IR Receiver and Remote Control
You can use the Helvar 303 Infrared Remote Control (available separately) to:
• recall lighting scenes 1–4;
• adjust light levels;
• store current level; and
• install preset levels for scenes 1–4.
Note: A different remote control unit (IR307) is used for 317 sensors of hardware rev. 1, and software version 5.40.
For instructions, see Installation Guide 7860287, issue 1.
High-Bay Presence/Absence Detector (317)
The 317 High-Bay PIR Presence/Absence Detector, in conjunction with a Helvar lighting control system, provides
automatic control of lighting loads in buildings and interior spaces with high ceilings. The 317 is typically installed in
warehouses and factories, and it is used in other applications where mounting heights are too high for standard sensors.
As with all the other Helvar ‘system’ sensors, the 317 is fully compatible with Helvar’s lighting systems and
configuration software, Designer and Toolbox. Once connected to a Helvar DALI network and lighting control system, the
software automatically detects the unit, which can then be programmed with the required functions.
Sensitivity
Adjust the sensitivity using Designer or Toolbox.
The factory default setting is 9 (maximum).
Note: On maximum sensitivity, the detector unit is extremely sensitive to movement and may detect through glass,
thin walls or partitions. If this causes a problem, reduce its sensitivity.
The temperature difference between the detection target and the background must be at least 4°C.
Adjusting On, Exit and Transition Time-Outs
The default time-outs for On, Exit and Transition can be altered using Designer, or Toolbox.
Identify: Check Connection to DALI Network
To make sure that the sensor is correctly connected to the DALI network, use the Identify function in Designer or
Toolbox. The sensor’s status LED flashes repeatedly until Identify is cancelled.
Sensitivity, Time-Outs, Identify
Features and Connections

Helvar 317 High-Bay PIR Presence/Absence Detector: Installation Guide
2
Detection area
A lower mounting height
will decrease the overall
size of the detection zone.
Alignment marks
15 m
40 m
Alignment Marks
The sensor head has 4 alignment marks.
These marks correspond to the four outer passive
infrared sensors under the lens.
Use these marks to align with aisles and corridors to
ensure the best detection characteristics.
Height Range
Diameter
15 m 40 m
10 m 26 m
6 m 16 m
3 m 9 m
Slot
number
Masking shield:
approx. % coverage
1 45 %
2 30 %
3 20 %
4 10 %
Diameter
number
Masking shield:
approx. % coverage
1 90 %
2 65 %
3 45 %
4 35 %
5 20 %
Height Range
Diameter
15 m 30 m
10 m 20 m
6 m 12 m
3 m 8 m
Detection Area Masking
Two adaptable clip-on shielding masks are supplied with the 317. Each can cover half of the sensor lens.
Lateral or radial strips can be cut out of the masks to customise the detection area.
Aisles/Corridors (lateral masks)
Cut the mask to make two lateral masks. This leaves a straight section of the lens uncovered.
The slots you cut out approximate to the levels of sensor coverage given in the following table:
Orientation and Sensitivity
If someone walks ‘across’ the detection area (not directly towards the centre of the sensor), the sensor range is greater
than if someone walks towards the centre of sensor (‘along’ the line between alignment marks).
Therefore, note the orientation of the sensor (as indicated by the alignment marks) when installing the sensors.
Small Areas (Radial Masks)
Cut semicircles out of the mask to make two radial masks. This leaves a circular section of the lens uncovered.
The ‘diameter numbers’ of the semicircles you cut out approximate to the levels of sensor coverage given in the table:
Walk Across Walk Towards
1 2 3 4 5 5 4 3 2 1
Diameter number
Alignment marksAlignment marks
Detection Area and Detection Area Masking
1 2 3 4 4 3 2 1
Slots:
Alignment mark

Helvar | Data is subject to change without notice. 3
1. Connect the DALI connector to the socket located at the rear of the sensor.
2. Flush fixing: Insert the unit into the ceiling or wall (see Connection and Fixing: Flush Fixing); or
Surface mounting: Install the unit using the SBB-A surface back box (see Connection and Fixing: Surface Mounting).
3. Power the unit up.
4. Configure the unit using Designer or Toolbox.
5. If the load triggered by the sensor comes on, by default it will take 20 minutes (of no movement detected) for the
load to switch off.
Installation Notes
• Position the sensor so that the occupants of the room are normally inside the detection zone.
• Do not fix the sensor to an unstable or vibrating surface.
• Do not install the sensor within one metre of any lighting, forced air heating, or ventilation equipment.
• Consider the possible effects on infrared detector of layers of hot and cold air in large buildings.
Layers of cold or hot air can form in the upper part of large buildings, such as warehouses, due to a number of factors,
including the layout of the building, heating and ventilation systems, shelving system arrangements, roofing materials and
the weather. If the sensor is positioned in or above such a layer of air, the sensitivity of the sensor cannot be guaranteed.
Connection and Fixing: Flush Fixing
Connection and Fixing: Surface Mounting (IP 40)
12
WARNING
Take special care when bending
springs to install the unit.
SBB-A
surface
back box
1. 2. 3. 4.
WARNING
Take special care
when bending
springs to
install the unit.
Ø 68 mm
1. 2. 3.
Protective
cover
Fit silicone
gasket if
required.
Installation

4Doc. 7860287, issue 4,
2015-07-07
Helvar 317 High-Bay PIR Presence/Absence Detector: Installation Guide
Technical Data
Connections
DALI: Removable connector block
Wire size: 0.5 mm² – 1.5 mm²
Solid, flexible or stranded
Cable rating: All cables must be mains rated.
Power
DALI supply input: 13 V to 22.5 V
DALI consumption: 20 mA
Sensors
Presence detector: PIR: Passive infrared presence
detector
Infrared receiver: For remote control commands.
Remote control functions
Remote control
handset:
Helvar 303 remote control
Note: Adjust sensitivity using
Designer, or Toolbox (not by remote
control unit).
Range: 5 m – 15 m
Mechanical data
Mounting hole
diameter:
68 mm
Bezel diameter: 88 mm
Recommended
clearance depth
(incl.50mm for
cabling):
80 mm (without protective cover);
100 mm (with protective cover)
Material (casing): Flame retardant ABS and PC/ABS
Finish/Colour: Matt / White RAL 9003
Weight: 120 g
IP code: IP40 without gasket; IP65 with
gasket
Gasket: Silicone ingress protection gasket
(not compatible with surface
mount box SBB-A)
Masks: Two adaptable masks included,
each covering half of the sensor
lens.
Operating conditions
Ambient temperature: 317: 0 °C to +35 °C
317M: –30 °C to +35 °C
Note: The temperature difference
between the detection target and
the background must be at least
4°C.
Relative humidity: Max. 90 %, noncondensing
Storage temperature: 317: –10 °C to +70 °C
317M: –30 °C to +70 °C
Dimensions Protective
cover
Installation in Surface Mount Box SBB-A
(IP 40)
Note: The SBB-A surface mount box must be ordered
separately.
Ø 88 63
58
68
49
60
50
65
73
76
Ø5
Ø76
Conformity and standards
EMC emission: EN 61000–6–1
EMC immunity: EN 61000–6–3
Safety: EN 60730–1
Environment: Complies with WEEE and RoHS
directives.
Helvar Ltd
Hawley Mill
Hawley Road
Dartford
Kent
DA2 7SY
United Kingdom
www.helvar.com
Altri manuali HELVAR Sensore di sicurezza

HELVAR
HELVAR Digidim 311 Manuale utente

HELVAR
HELVAR digidim 313 Manuale utente

HELVAR
HELVAR digidim 319 Manuale utente

HELVAR
HELVAR 311 Manuale utente

HELVAR
HELVAR 318 Manuale utente

HELVAR
HELVAR digidim 314 Manuale utente

HELVAR
HELVAR OB-1501 Manuale utente

HELVAR
HELVAR 314 Tilting Manuale utente

HELVAR
HELVAR Digidim 313 Manuale utente

HELVAR
HELVAR Digidim 317 Manuale utente