HESCH HE 5422 MR Manuale utente

HE 5422 MR
Differential pressure regulator with measuring hose cleaning
Operating manual
Translation of the operating manual
(Original version German)

2Operating manual HE 5422 MR
Version 1.2 • Item number #342232 • 25.03.2019
Imprint
HESCH Industrie-Elektronik GmbH
Boschstraße 8
D-31535 Neustadt
Germany
Phone +49 (0) 5032 9535-0
Fax +49 (0) 5032 9535-99
Internet: www.hesch.de
E-Mail: info@hesch.de
District court Hanover
HRB 111184
Tax-No.: 34/200/22524
VAT No.: DE813919106
Management:
Walter Schröder, Werner Brandis
Publisher:
HESCH Industrie Elektronik GmbH, Documentation Department
Copyrights
© Copyright 2014 HESCH Industrie-Elektronik GmbH. All rights reserved. The content
including pictures and the design of this manual are subject to copyright protection and
other laws for protection of intellectual property. The dissemination or alteration of the
content of this manual is prohibited. Moreover, these contents may not be copied, dis-
seminated, altered or made accessible to third parties for commercial reasons.

Operating manual HE 5422 MR 3
Version 1.2
Table of contents
1 Foreword. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
1.1 Information regarding the usage of these operating instructions. . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 Legal provisions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
2.1 Symbols and basic safety information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Safety during the individual phases of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3 Device description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Display and control elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.3 Differential pressure column . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
5 Electrical commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
5.1 Safety notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 Supply voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3 Connection diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.4 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.5 Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6 Parametrization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
6.1 Parametrization using device keyboard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.2 Offset for zeroing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.3 Parametrization using the Service-PC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.4 Parameter protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.5 Reset of factory settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
7.1 Normal operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
7.2 Testing function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.3 Differential pressure measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
7.4 Measuring hose cleaning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
8 Error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
9 Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
10 Maintenance and service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
10.1 Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Chapter 1 Foreword
4Operating manual HE 5422 MR
Version 1.2
1 Foreword
1.1 Information regarding the usage of these operating instruc-
tions
Structure
Target group
These operating instructions are intended for qualified electricians that will install, wire, commission
and parametrize the HE 5422 MR Differential Pressure Regulator.
Chapter 1 Foreword
Information on chapter structure, document history, intended use and device
safety.
Chapter 2 Safety information
Important safety information regarding the Differential Pressure Regulator.
Chapter 3 Device description
Description of the Differential Pressure Regulator, control elements and techni-
cal specifications.
Chapter 4 Installation
Dimensions of the device and scope of delivery.
Chapter 5 Electrical commissioning
Connection of supply voltage and signals.
Chapter 6 Parametrization
Parametrization on the device or with a service PC.
Chapter 7 Operation
Information regarding operation, differential pressure measurements, measur-
ing hose cleaning and error messages.
Chapter 8 Error messages
Information regarding error messages that are shown on the display and indi-
cated by the flashing LEDs.
Chapter 9 Declaration of conformity
Chapter 10 Maintenance and service
Information regarding control operations and disposal

Chapter 1 Foreword
Operating manual HE 5422 MR 5
Version 1.2
Document history
Date / Version Description
10/2013 / 1.0 First creation
04/2014 / 1.1 Chapter 3.1, 3.4, 5.2, 5.3: Changed value for wide-range power supply
(100 – 240 VAV). Chapter 2.2: Changed value for surface temperature. Chap-
ter 6.1: Supplemented factory setting of Δp-Measuring-range (mbar). Chapter
9: Added declaration of conformity. Chapter 8: Added error message (E 4).
03/2019 / 1.2 Chapter 3.4 Technical data:
Operating temperature in EX zone added.

Chapter 1 Foreword
6Operating manual HE 5422 MR
Version 1.2
1.2 Legal provisions
Manufacturer
HESCH Industrie-Elektronik GmbH, Boschstraße 8, D-31535 Neustadt, Germany
Intended use
The HE 5422 MR Differential Pressure Regulator serves the purpose of measuring the dif-
ferential pressure using filter elements as part of the industrial fabric filter technologies and
to operate a valve control unit. The differential pressure is monitored by two alarm thresh-
olds.
The control unit can be operated within the usage and ambient conditions stated in this
manual without causing any safety risks.
The manufacturer is not liable for improper usage and the resulting personnel injuries or
damage; the risk lies entirely with the operator. Failure to comply with the above mentioned
criteria regarding intended use may void the warranty – the manufacturer cannot be held li-
able for damage to the device in this case.
Personnel qualification
Only qualified electricians with the appropriate knowledge in the field of electrical engineering are
allowed to conduct any work on the Differential Pressure Regulator.
Device safety
The device was built and tested in accordance with VDE 0411 / EN 61010-1 and has left the fac-
tory in an operationally safe condition. In order to maintain this condition and to ensure safe opera-
tion, the user has to follow the instructions and warnings contained in this manual, see chapter 2
"Safety information" on page 7.

Chapter 2 Safety information
Operating manual HE 5422 MR 7
Version 1.2
2 Safety information
2.1 Symbols and basic safety information
This chapter contains important safety provisions and information. In order to protect against per-
sonnel injury and damage, it is necessary to carefully read this chapter before working with the de-
vice.
Used symbols
The following symbols are used in this manual. All safety information notes are structured in a uni-
form manner.
Warning of personnel injury!
The severity of the danger is indicated by the respective signal word, see page 8.
Warning of explosive atmosphere!
Warning of dangerous electrical voltage!
Warning of material damage due to electrostatic charging!
Warning of material damage!
Note!
Indicates possible malfunctions and provides information regarding optimal oper-
ating conditions.

Chapter 2 Safety information
8Operating manual HE 5422 MR
Version 1.2
Signal words
DANGER!
Indicates an immediate danger with high risk that will result in death or serious injury if not avoided.
WARNING!
Indicates a possible danger with medium risk that may result in death or serious injury if not
avoided.
CAUTION!
Indicates a danger with low risk that might result in slight or moderate injury if not avoided.
Structure of warning notes
All warning notes in these operating instructions are structured in a uniform manner. The pictogram
designates the type of danger.
SIGNAL WORD!
An informative text describes the danger and suggests how it can be avoided.

Chapter 2 Safety information
Operating manual HE 5422 MR 9
Version 1.2
2.2 Safety during the individual phases of operation
The following safety notes must be observed when installing the device and during operation.
Danger of electric shock!
Disconnect the power supply before working on the device. Install the electrical
lines in accordance with the respectively applicable local regulations (VDE 0100
in Germany). Lay the measuring lines separately from the power lines. Produce a
connection between the protective ground connection (in the respective device
carrier) and a protective ground.
Danger of electric shock!
Any interruption of the protective ground in the device carrier may cause the de-
vice to become dangerous. Deliberate interruptions are not permissible. If it can
be assumed that safe operation is no longer possible, then the device shall be
put out of commission and be secured against unintended operation or re-activa-
tion.
Danger of electric shock!
Do not open the device under voltage! When opening the devices or removing
covers and parts, live parts may become exposed. Connecting points may also
be live!
Caution!
The device may not be put into operation when there is visible damage on the
device.
Caution!
Observe the accident prevention regulations applicable to the system, such as
BGV A 3 "Electrical Systems and Equipment" during installation, commissioning,
maintenance and troubleshooting.
Caution!
Clean soiled contacts using oil-free compressed air or spirit and a lint-free cloth.
Material damage due to electrostatic charging!
Observe the safety measures according to DIN EN 61340-51/-3 in order to pre-
vent electrostatic discharging!

Chapter 2 Safety information
10 Operating manual HE 5422 MR
Version 1.2
The following provisions must be observed:
Attach the cables to the cable glands correctly.
Provide unneeded housing bores with locking bolts.
It is only permitted to clean the housing with wet cleaning agents in order to avoid static
charging.
It is required to clean the device in order to prevent increased dust formation.
Electrical connection!
Install the electrical lines in accordance with the respectively applicable local reg-
ulations (VDE 0100 in Germany). Lay the measuring lines separately from the
power lines. Produce a connection between the protective ground connection (in
the respective device carrier) and a protective ground.
Explosion protection!
The device is suitable for operation in explosion zone 22 with the lid closed. Prior
to opening the device, it has to be ensured that there are no explosive ambient
conditions, such as dust development.
The device is marked with:
II Not suitable for mines susceptible to firedamp
3D Dusts, normal safety
T135°C Surface temperature
IP65 Protection class: dust-proof, scoop-proof
Troubleshooting!
When beginning to troubleshoot, all possible sources of error regarding additional
equipment or cables (measuring cables, wiring, slave devices) should be taken
into consideration. If no error source can be found after examining these points,
we recommend to send the device to the supplier.
Decommissioning!
Disconnect the power supply entirely if the device is to be decommissioned. Se-
cure the device against inadvertent operation!
If the device is interconnected with other devices and/or equipment, the effects of
the deactivation should be considered prior to disconnecting the device and the
appropriate precautions should be taken beforehand.