Hoffer Flow Controls HRT1 Manuale utente

HP-313
July 2009
Model: HRT1
Flow Rate Indicator/Totalizer With
HARTCommunications Protocol
USER’S MANUAL
HP-313
April 2018
107 Kitty Hawk Lane ●P.O. Box 2145 ●Elizabeth City, NC 27909
1-800-628-4584 ●(252) 331-1997 ●Fax (252) 331-2886
www.hofferflow.com email: [email protected]




HFC 9907-B
_________________________________________________________
NOTICE
Hoffer Flow Controls, Inc. makes no warranty of any kind with regard to this
material, including, but not limited to, the implied warranties of merchantability
and fitness for a particular purpose.
This manual has been provided as an aid in installing, connecting, calibrating,
operating, and servicing this unit. Every precaution for accuracy has been taken in
the preparation of this manual; however, Hoffer Flow Controls, Inc. neither
assumes responsibility for any omissions or errors that may appear nor assumes
liability for any damages that result from the use of the products in accordance
with information contained in the manual.
HOFFER FLOW CONTROLS' policy is to provide a user manual for each item
supplied. Therefore, all applicable user manuals should be examined before
attempting to install or otherwise connect a number of related subsystems.
During installation, care must be taken to select the correct interconnecting wiring
drawing. The choice of an incorrect connection drawing may result in damage to the
system and/or one of the components.
Please review the complete model number of each item to be connected and locate
the appropriate manual(s) and/or drawing(s). Identify all model numbers exactly
before making any connections. A number of options and accessories may be added
to the main instrument, which are not shown on the basic user wiring. Consult the
appropriate option or accessory user manual before connecting it to the system. In
many cases, a system wiring drawing is available and may be requested from
Hoffer Flow Controls.
This document contains proprietary information, which is protected by
copyright. All rights are reserved. No part of this document may be photocopied,
reproduced, or translated to another language without the prior written consent
of Hoffer Flow Controls, Inc.
HOFFER FLOW CONTROLS’ policy is to make running changes, not model
changes, whenever an improvement is possible. This affords our customers the
latest in technology and engineering. The information contained in this
document is subject to change without notice.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ALL OTHER WARRANTIES,
EXPRESSED OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.HFC SHALL
NOT BE LIABLE FOR ANY LOSS OR DAMAGE RESULTING,DIRECTLY OR INDIRECTLY,
FROM THE USE OR LOSS OF USE OF THE GOODS.WITHOUT LIMITING THE
GENERALITY OF THE FOREGOING,THIS EXCLUSION FROM LIABILITY EMBRACES THE
PURCHASER'S EXPENSES FOR DOWNTIME OR FOR MAKING UP DOWNTIME,DAMAGES
FOR WHICH THE PURCHASER MAY BE LIABLE TO OTHER PERSONS,DAMAGES TO
PROPERTY,AND INJURY TO OR DEATH OF ANY PERSONS.HFC NEITHER ASSUMES
NOR AUTHORIZES ANY PERSON TO ASSUME FOR IT ANY OTHER LIABILITY IN
CONNECTION WITH THE SALE OR USE OF HFC'S GOODS,AND THERE ARE NO ORAL
AGREEMENTS OR WARRANTIES COLLATERAL TO OR AFFECTING THE AGREEMENT.
PURCHASER'S SOLE AND EXCLUSIVE REMEDY IS THE REPAIR AND/OR REPLACEMENT OF
NONCONFORMING GOODS AS PROVIDED IN THE PRECEDING PARAGRAPHS.HFC SHALL
NOT BE LIABLE FOR ANY OTHER DAMAGES WHATSOEVER INCLUDING INDIRECT,
INCIDENTAL,OR CONSEQUENTIAL DAMAGES.

HFC 9907-B
________________________________________________________________
LIMITED WARRANTY POLICY FOR HOFFER FLOW CONTROLS
________________________________________________________________
HOFFER FLOW CONTROLS, INC. ("HFC") warrants HFC's Precision Series and API
Series of turbine flowmeters to be free from defects in material and workmanship under
normal use and service, only if such goods have been properly selected for the service
intended, properly installed and properly operated and maintained as described in the
turbine flowmeter manual. Reference "turbine flowmeter manual" for specific details. This
warranty shall extend for a period of five (5) years from the date of shipment to the
original purchaser and covers the Precision Series, API Series and CT Series of
flowmeters supplied with their standard hybrid ceramic ball bearings only. All other HFC
products carry a one (1) year warranty. This warranty is extended only to the original
purchaser ("Purchaser"). Purchaser's sole and exclusive remedy is the repair and/or
replacement of nonconforming goods as provided in the following paragraphs.
In the event Purchaser believes the Hoffer product is defective, the product must be
returned to HFC, transportation prepaid by Purchaser, within the appropriate warranty
period relative to the product. If HFC's inspection determines that the workmanship or
materials are defective and the required maintenance has been performed and, has been
properly installed and operated, the product will be either repaired or replaced, at HFC's
sole determination, free of additional charge, and the goods will be returned, transportation
paid by HFC, using a transportation method selected by HFC.
Prior to returning the product to HFC, Purchaser must obtain a Returned Material
Authorization (RMA) Number from HFC's Customer Service Department within 30 days
after discovery of a purported breach of warranty, but not later than the warranty period;
otherwise, such claims shall be deemed waived. See the Return Requests/inquiries Section
of this manual.
If HFC's inspection reveals the Hoffer product to be free of defects in material and
workmanship or such inspection reveals the goods were improperly used, improperly
installed, and/or improperly selected for service intended, HFC will notify the purchaser in
writing and will deliver the goods back to Purchaser upon receipt of Purchaser's written
instructions and agreement to pay the cost of transportation. If Purchaser does not respond
within thirty (30) days after notice from HFC, the goods will be disposed of in HFC's
discretion.
HFC does not warrant the product to meet the requirements of any safety code of any
state, municipality, or other jurisdiction, and Purchaser assumes all risk and liability
whatsoever resulting from the use thereof, whether used singlely or in combination with
other machines or apparatus.
This warranty shall not apply to any HFC product or parts thereof, which have been
repaired outside HFC's factory or altered in any way, or have been subject to misuse,
negligence, or accident, or have not been operated in accordance with HFC's printed
instructions or have been operated under conditions more severe than, or otherwise
exceeding, those set forth in the specifications.
________________________________________________________________
FOR NON-WARRANTY REPAIRS OR CALIBRATIONS, consult HOFFER FLOW CONTROLS
for current repair/calibration charges. Have the following information available BEFORE
contacting HOFFER FLOW CONTROLS:
1.
P.O. number to cover the COST of the repair/calibration,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to the product.
________________________________________________________________

HRT1 HP-313
CONTENTS
1. INTRODUCTION------------------------------------------------1
Model Number Designation--------------------------------------------- 3
2. SPECIFICATIONS AND PRODUCT FEATURES-------7
2.1 General ---------------------------------------------------------- 7
2.2 Inputs ------------------------------------------------------------ 8
2.3 DC Power/Loop Powered------------------------------------ 8
2.4 Analog Output ------------------------------------------------- 9
2.5 Pulse Output---------------------------------------------------- 9
2.6 Alarm 1 and Alarm 2----------------------------------------- 9
2.7 Physical---------------------------------------------------------- 9
Product Features-------------------------------------------------------- 9
3. INSTALLATION----------------------------------------------- 11
3.1 4-20 mA Current Loop--------------------------------------13
3.2 Flowmeter Input----------------------------------------------15
3.3 Pulse Output---------------------------------------------------16
3.4 Alarm Outputs------------------------------------------------16
3.5 Wiring Summary---------------------------------------------18
4. CONFIGURATION-------------------------------------------- 19
4.1 Local Configuration -----------------------------------------19
4.2 Default Configuration---------------------------------------22
5. OPERATION AND MAINTENANCE--------------------- 23
5.1 Display Parameters ------------------------------------------23
5.2 Saving Grand Total------------------------------------------23
5.3 Clearing the Total--------------------------------------------23
5.4 System Response Time --------------------------------------24
5.5 Error Conditions ---------------------------------------------24
5.6 Battery Replacement Indication --------------------------25
6. HART COMMUNICATIONS------------------------------- 27
6.1 Dynamic Variables-------------------------------------------27
6.2 Universal Commands----------------------------------------28
6.3 Common-Practice Commands-----------------------------28
6.4 Device-Specific Commands--------------------------------29
6.5 Device Status --------------------------------------------------31
6.6 Additional Device Status------------------------------------32
6.7 EDDL – Process Variables ---------------------------------35
6.8 EDDL – Device Diagnostics --------------------------------36
6.9 EDDL – Online -----------------------------------------------36
7. MAINTENANCE----------------------------------------------- 41

HP-313 HRT1
APPENDIX A – DEFAULT CONFIGURATION------------ 43
APPENDIX B – Declaration and Conformity----------------- 45
APPENDIX C – Installation Drawings and Conditions
for Safe Use for Certified Systems------------------------------- 47

Introduction 1
HRT1 HP-313
1. INTRODUCTION
The HRT1 is a loop-powered microprocessor-based flow rate indicator
and totalizer with HART Field Communications Protocol. The
instrument can accept a low-level signal from a magnetic type pickup
coil, logic level pulse signal, or contact closure on the signal input.
Pulses from the signal input are counted and converted into volume and
rate values based on flowmeter calibration settings in the instrument.
The total volume and flow rate is displayed on a two-line liquid crystal
display (LCD). The top line is an 8-digit Total Volume display and the
bottom is a 5-digit Rate display. A 4-20 mA analog signal proportional
to the flowrate is output on the current loop. The HRT1 is configurable
by way of the instrument keypad or via HART communications.
Figure 1 – HRT1 Front Panel Overview
Optional features include 20-point linearization to correct for
flowmeter non-linearities, a Scaled Pulse Output and 2 Alarm Outputs
configurable for Rate or Total.
The instrument may be housed in a NEMA 4X polycarbonate
enclosure, which may be wall mounted or directly mounted on a
flowmeter using an optional riser. Other options include panel mount
or an EX proof enclosure for hazardous areas.

Introduction 2
HP-313 HRT1
This instrument is designed to conform to the EMC-Directive of the
Council of European Communities 89/336/EEC and the following
standards:
Generic Emission Standard EN 61000-6-3
Residential, Commercial & Light Industry Environment.
Generic Immunity Standard EN 61000-6-1
Residential, Commercial & Light Industry Environment.
Electrostatic discharge requirements EN 61000-4-2
Radiated, radio-frequency, electromagnetic immunity EN 61000-4-3
Electrical fast transient/burst requirements EN 61000-4-4
Immunity to conducted disturbances EN 61000-4-6