Honeywell RedLINK Manuale utente

RedLINK™Wireless System
With Equipment Interface Module
® U.S. Registered Trademark.
Copyright © 2008 Honeywell International Inc.
All rights reserved.
Wireless control for up to 3 Heat/2 Cool heat pump systems or up to
2 Heat/2 Cool conventional systems.
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical
shock or equipment damage.
MERCURY NOTICE: If this product is replacing a control that contains mercury in a
sealed tube, do not place the old control in the trash. Contact your local waste
management authority for instructions regarding recycling and proper disposal.
Must be installed by a trained, experienced technician. Read these instructions
carefully. Failure to follow these instructions can damage the product or cause a
hazardous condition.
System
Installation
Guide
Español: vea la página 20 • Français : voir la page 39
Installation guide for:
• Wireless equipment interface module
• FocusPRO®wireless thermostats
• Wireless remote control
• Wireless outdoor air sensor
• Return air sensor

RedLINK™ Installation Guide (EIM)
2
System installation at a glance
The THM5320R equipment interface module (EIM) provides control of all
heating and cooling equipment from any FocusPRO wireless thermostat.
Thermostat
Outdoor
air sensor
Remote
control EIM
Installation procedure
Mount and wire EIM ....................................................Pages 3-4
Install batteries in wireless devices ................................Page 5
Link all devices to wireless network ..........................Pages 5-7
Exit wireless setup ............................................................Page 8
Customize thermostat (installer setup) ....................Pages 8-12
Mount thermostat and outdoor sensor..........................Page 13
To replace system components if needed, see page 15
For system-specific wiring guides, see pages 16-17
4
6
5
3
2
1
DISCONNECT POWER BEFORE BEGINNING INSTALLATION. Can cause electrical
shock or equipment damage.
HVAC equipment
If you have more than one Equipment Interface Module (EIM): Thermostats are
linked to specific EIMs. Optional accessories must be linked to each EIM separately.

Español: vea la página 20 • Français : voir la page 39
3
Mount and wire EIM
1
Mount EIM on wall near HVAC equipment, or on the equipment itself.
Do not install inside HVAC equipment. Use screws & anchors as appropriate
for mounting surface.
EIM wiring
Wiring must comply with local electrical codes.
Strip 1/4” insulation, then insert wires
as shown.
Press tabs only to remove wires from
terminal block if necessary.
Continued on next page >>
Install EIM Install return air sensor (optional)
Install sensor on return air duct at least 12”
(305mm) upstream from ventilator, humidifier
or dehumidifier (do not mount downstream)
Drill 1/4” hole
(6.4mm)
The return air sensor maintains safe indoor
temperature if thermostat power is lost.

EIM wiring guide
Stage 1 heat
FURNACE
Transformer
Stage 2 heat
Fan
24Vac 120Vac
Air conditioning
Compressor
(stage 1)
Compressor
(stage 2)
Return
air sensor
Changeover
relay
Backup heat
(gas/electric)
Relay **
Fan relay
Compressor
(stage 1)
Compressor
(stage 2)
Return
air sensor
EQUIPMENT INTERFACE MODULE
CONVENTIONAL SYSTEMS
EQUIPMENT INTERFACE MODULE
HEAT PUMP SYSTEMS AIR HANDLER
Transformer
24Vac 120Vac
A/B/C/D unused
(reserved for future use)
A/B/C/D unused
(reserved for future use)
See detailed wiring guides for specific system
types on pages 16-17.
4
RedLINK™ Installation Guide (EIM)
** L terminal sends continuous output when thermostat is
set to EmHeat. L terminal is for use with zone panels.

Install batteries in wireless devices
2
When system wiring is complete, install batteries in all devices. Make sure
batteries are inserted properly (see polarity marks on illustrations below).
Link all devices to wireless network
3
Restore AC power, then press the CONNECT
button at the EIM and wait for green
flashing light to begin linking devices to
the wireless network (see pages 6-7).
If the light stops flashing before you
have linked all devices, press CONNECT
again.
Press CONNECT
Thermostat
Install quick reference cardInstall 2 fresh AA
batteries
Remote control (optional) Outdoor air sensor (optional)
Install 3 fresh AA
batteries
Install 2 fresh AA
lithium batteries
Flashing status light times out after 15
minutes of inactivity. Press CONNECT again if
necessary.
5
Español: vea la página 20 • Français : voir la page 39
Programmable models only
Continued on next page >>
If light does not flash, another EIM/wireless
adapter may be in wireless setup mode. Exit
wireless setup at the other EIM/wireless
adapter.

Link thermostat to wireless network
Wireless Setup
00
NextBack
Wireless Setup
36 52
Back Next
Wireless SetupWireless Setup
Back
Press NEXT (always leave zone number set
to zero).
Press NEXT (or see page 11 to change the
zone name if needed).
Press CONNECT to establish a link to the
wireless network.
After a brief pause, the confirmation
screen at left should be displayed, to
verify that the wireless connection has
been established.
Press DONE to display the home screen.
Wireless SetupWireless Setup
Connected
Done
Zone number
Zone name
Connect
6
RedLINK™ Installation Guide (EIM)
Zone numbers 1-4 are for use with TrueZONE
panels only.
If E1 appears, see error codes on page 14.
Change zone name only if you have more than
one thermostat and EIM.

Link remote control to wireless network (optional)
1Make sure the Connected light on the
EIM is flashing (see page 5).
2Press CONNECT at the remote. There will
be a short delay as the remote seeks
a signal from the wireless network.
3When the screen displays
“Connected,” press DONE.
4Press NO at the next screen to save
and exit. (Or press YES and repeat
steps 1-4 to link another EIM.)
WIRELESS SETUP
CONNECT
Link outdoor sensor to wireless network (optional)
1Make sure the Connected light on the
EIM is flashing (see page 5).
2Press the CONNECT button on the back
of the sensor.
3Check thermostat to verify that the
outdoor sensor is working. After
about 15 seconds, the thermostat
should display outdoor temperature
and humidity.
(If you are installing more than one EIM,
repeat steps 1-3 for each.)
Press and release
7
Español: vea la página 20 • Français : voir la page 39
YES NO
CONNECT MORE?
If E1 appears, see error codes on page 14.
The linking procedure may time out if there is
no keypress within 30 minutes. To begin again,
press and hold the blank space (or arrow if
present) in the lower right corner of the screen
until the display changes (about 3 seconds)
Press to link
another EIM
Press to save
and exit

Customize thermostat (installer setup)
5
Function Setting
Press ▲or ▼to change setting
(see tables on pages 9-11)
Press NEXT to display next
function screen
Press DONE to save & exit.
Follow the steps below to begin installer setup. At each function screen,
press ▲or ▼to change the setting as desired, then press NEXT to advance to
the next function screen.
See tables on pages 9-11 for a description of options for each function.
Exit wireless setup
4
Press CONNECT at the EIM to exit wireless setup (light should stop flashing).
10
Back NextDone
00
BackDone Next
To begin, press and hold the FAN and ▲buttons
until the display changes (about 3 seconds).
8
RedLINK™ Installation Guide (EIM)
FAN
Note: The EIM will automatically exit wireless setup after 15 minutes of inactivity.
Note: If installing more than one thermostat and EIM, you must exit wireless setup before
installing an additional thermostat and EIM.

Installer setup tables
0
1
2
3
5
6
7
8
9
10
12
13
14
Zone number
System type
Changeover valve
(O/B terminal)
Fan control
(conventional heat)
Stage 1 heat cycle
rate (CPH= cycles
per hour)
Stage 2 heat
cycle rate (CPH)
Stage 3 heat
cycle rate (CPH)
Emergency heat
cycle rate (CPH)
Stage 1 compres-
sor cycle rate
Stage 2 compres-
sor cycle rate
Manual/Auto
changeover
Adaptive Intelligent
Recovery
Temperature
display
0No zoning (single thermostat used with THM5320R EIM)
[Options: select zone 1, 2, 3 or 4]
0 1 heat/1 cool conventional
1 1 heat/1 cool heat pump (no aux. heat)
2 Heat only (includes Series 20)
3 Heat only with fan
4 Cool only
5 2 heat/1 cool heat pump
6 2 heat/2 cool conventional
7 2 heat/1 cool conventional
8 1 heat/2 cool conventional
9 2 heat/2 cool heat pump
10 3 heat/2 cool heat pump
0 O/B terminal controls valve in cooling
1 O/B terminal controls valve in heating
0 Gas/Oil heat (equipment controls fan)
1 Electric furnace (thermostat controls fan)
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
5 Gas or oil furnaces (less than 90% efficiency)
1 Steam or gravity systems
3 Hot water systems & furnaces of over 90% efficiency
9 Electric furnaces
[Cycle rate options: 1 to 12 CPH]
9 Electric furnace
[Cycle rate options: 1 to 12 CPH]
3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
3 Recommended cycle rate
[Cycle rate options: 1 to 6 CPH]
0 Manual (User options: Heat/Cool/Off)
1 Automatic (User options: Heat/Cool/Auto/Off)
Applies only to Model TH6320
0Off
1On
0 Fahrenheit
1 Celsius
Setup functions Settings & Options (factory default in bold)
9
Español: vea la página 20 • Français : voir la page 39

15
16
26
27
28
32
33
35
Compressor off
time (minimum)
Schedule format
Auxiliary heat
control
Maximum heat
setpoint
Minimum cool
setpoint
Temp. display
offset (indoor)
Temp. display
offset (outdoor)
Humidity display
offset (outdoor)
5 5 minutes (Heat On/Cool On flashes during off time)
[Options: 0 to 4 minutes]
Applies only to Model TH6320
0 Weekday/weekend program schedule
1 Weekday/Saturday/Sunday program schedule
Applies only to Model TH5320
0 Comfort **
1 Economy
90 Max. heat temperature setting is 90°F (32°C)
[Options: 40 to 90°F (4.5 to 32°C)]
50 Min. cool temperature setting is 50°F (10°C)
[Options: 50 to 99°F (10 to 37°C)]
0 Thermostat displays actual temperature
[Options: -3 to +3°F offset (-1.5 to +1.5°C)]
0 Thermostat displays actual temperature
[Options: -5 to +5°F offset (-2.5 to +2.5°C)]
3 Thermostat displays actual humidity
[Other options: 0 = -15%, 1 = -10%, 2 = -5%,
4 = 5%, 5 = 10%, 6 = 15% offset]
** See page 11
Installer setup tables
Setup functions Settings & Options (factory default in bold)
10
RedLINK™ Installation Guide (EIM)
Altri manuali per RedLINK
4
Indice
Lingue:
Altri manuali Honeywell Sistema microfonico
Manuali Sistema microfonico popolari di altre marche

Sennheiser
Sennheiser Evolution Wireless Digital EW-DX EM 2 Manuale utente

Alpha Technologies
Alpha Technologies RBMS Manuale utente

SWIT Electronics Co.,LTD.
SWIT Electronics Co.,LTD. CW-S150 Manuale utente

Shure
Shure UA844 Manuale utente

Panasonic
Panasonic SHFX70 - DVD HOME THEATER WIRELESS SYSTEM Manuale utente

Pyle
Pyle PDWM5000 Manuale utente