1 Important Safety Information
•
Ifnotusingsuppliedflexline,ensureanyflexline that maybeusedfrom the
permanent main fuel supply to the product is rated tothe stated max BTU of the
productandcertified toANSIZ21.75*CSA 6.27.
•
TheEISeriesisnotforusewithsmallLPTanksandmustutilizepermanentfixed
pipingforfuelsupply.
Electrical
•
Verifycorrect 120 VAC –1 amp or 24 VAC–4 amp power supply. Only use the type
specifiedfor this fireplace insert.Refer to the label on the EI Control Panel. All
electronic
applicationsshouldutilizeaGFCI-protectedcircuit.
-
If removing power cord plug and hard wiring within junction box, use only a
certified Electrician and must follow the National Electrical Code (NEC), NFPA
70 and all local codes.
24 VAC powered fireplace inserts:
-
Fire Pit will not perform properly if power supply rating is
below 100W or wire size is too small.
-
HPC highly recommends using our HPC/Sebco 24 VAC
100W power supply series (311-PS1, 311-PS3, 311-PS5
Models)
A Class II 24 VAC, 4 amp, 100 W transformer must be used to power the EI
Control Panel
and be able to beswitched on and off from a remote location to
allow for easy
accessoremergency.
-
24 VAC wire sizing: Wire lengths 75 ft or less: 14 gauge
-
Wire lengths 76 ft or more: 12 gauge
ImportantSafetyInformationforEnd-Users
•
Neverleaveanoperatingfireplace insertunattendedorwithsomeonenot
familiarwith
itsoperationoremergencyshut-offlocations.
•
Bothchildrenandadultsshouldbe alerted tothehazards ofhighsurface
temperaturesand shouldstayawaytoavoidburnsandclothing ignition.
•
Youngchildrenshould becarefullysupervisedwhentheyareintheareaof thefireplace.
•
Keeptheapplianceareaclearandfreefromcombustiblematerials,gasoline,
andotherflammablevaporsandliquids.