IBC control MiniMax Manuale utente

IBC
control
Made in Sweden
MANUAL
CONTROL UNIT FOR ROTATING HEAT EXCHANGER
MiniMax
Article no. F21037501
Set of EMC-glands as an option


Installation Instructions 2
Mounting 2
Safety instructions 3
Manufacturer's declaration 4
Description of functions 5
Technical data 6
Functions 6
- DIP switch 7
- Operational indications 8
- Alarms 8-9
- Settings via
potentiometer 10
- Push button 10
Connection diagram 11
Connections 11-12
Checks before powering up
the control unit
12-13
Putting the equipment
into operation
13
EMC installation 14
EMC gland 14
Personal notes 15-17
TABLE OF CONTENTS

Warning indication e control unit must only be used in perfect technical condition.
Any damage that may aect safety must be dealt with
immediately.
Maintenance/Repairs e function of the control unit should be checked regularly.
Troubleshooting and repairs may only be performed by trained
personnel.
Prescribed electrical protection must be implemented.
Disposal and recycling When replacing components or when the control unit in its
entirety need replacing, please follow the advice below:
e aim should always be maximum possible
recycling of raw materials, with minimum possible
environmental impact.
Never dispose of electrical components with ordinary waste,
always use the designated collection points.
Disposal should be as environment-friendly as the technology
allows in terms of environmental protection and recycling.
INSTALLATION INSTRUCTIONS
MOUNTING
Mounting hole 5 ø
Mounting hole 5 ø
2

SAFETY INSTRUCTIONS
Safety instruction refers to instructions whose specic intent is
to avoid the risk of personal injury and to prevent damage to
equipment.
Danger! Electrical current to electrical components!
NOTE! Switch o main power before removing the cover.
Never touch electrical components or contacts while main
current is switched on. Risk of electric shock, resulting in
serious injury or death.
Residual voltage remains in connected terminals
even aer main power has been switched o.
e following symbols and references are used in this description. ese instructions
are important; they apply to personal and technical safety during operation.
23

4
MANUFACTURER'S DECLARATION
Manufacturer IBC control AB
Brännerigatan 5 A, SE-263 37 Höganäs, Sweden
Product Control unit for rotating heat exchanger
Type designation MiniMax
Article number F21037501
EU directive
applied to the
product
e manufacturer's declaration of conformity with the requirements of the
EMC Directive 2004/108/EC.
e control unit is approved according to the requirements of the EMC
Directive 2004/108/EC and is tested according to standard EN 61800-3:2004,
emission category C1 and immunity category C2.
All control units comply with the Low Voltage Directive 2006/95/EC,
standard EN 61800-5-1.
is product also complies with RoHS Directive 2011/65/EU.
Höganäs 2016-03-01
IBC control AB
Christer Persson
MD

•MiniMax (enclosed IP54) is a modern, vector modulated frequency converter, with the
additional functions necessary for optimum control of rotating heat exchangers.
e control unit can handle all input signals currently used in the market.
•Heat exchanger rpm and thus thermal eciency are governed by the control unit so that
wheel speed is proportional to the input signal from the control centre.
•If the input signal is less than the set threshold value the rotor is stopped.
•When the rotor has been at a standstill for 1/2 hour, cleaning begins and the rotor turns
for 10 seconds at minimum rpm.
•e rotation monitor (a magnet tted to the rotor with an associated magnetic sensor)
stops the converter and generates an alarm in the case of a broken belt or similar.
•In the event of over- or under voltage on the mains, short circuit or earth fault and
tripped thermal contact in the motor, the control unit trips and generates an alarm.
•e control unit restarts automatically following a power failure.
•e motor should not be disconnected from the control unit while under load.
•e control unit can be equipped with extra cards. e following cards are available:
- Dierential temperature regulator with electrical heating output
- 2-rotor module
DESCRIPTION OF FUNCTIONS
45

Overload 2 min/30 min 3.5 A
Internal fuse **) 4 AT
Acceleration time
Retardation time
0-30 s
0-30 s
Ambient temperature,
non condensing
-25 - +45 OC
Protection form IP54
Weight 1.2 kg
Dimensions, HxWxD 198x165x60 mm
Input voltage 1x230-240 V +/-15%
50/60 Hz
Power input, max. 650 W
Input current, max 2.8 A
Incoming fuse, max 10 A
Output voltage*) 3x0-230 V
Min frequency 1-20 Hz
Max frequency 40-100 Hz
Motor output, max 370 W
Motor current, max 1.9 A
* Exact value cannot be obtained with a digital measuring
instrument
** e fuse protects both motor and electronics
Reset button
Operational
indications
Alarm indications
Adjustments
TECHNICAL DATA
FUNCTIONS
DIP switch
Operational / Alarm indications
6
}
Boost
Acc
Ret
Threshold / Tröskel
Min rpm
Max rpm

DIP SWITCH
67
Input signal 1 2 3 4 5 6 7 8 9 10
Potentiometer 0 0 0 0 0 0
0-5 V 0 0 0 0 0 0
0-10 V 1 0 0 0 0 0
0-20 V 0 1 0 0 0 0
1-5 V 0 0 1 0 0 0
2-10 V 1 0 1 0 0 0
5-10 V 1 0 0 1 0 0
10-0 V 1 0 0 0 0 1
10-2 V 1 0 1 0 0 1
10-5 V 1 0 0 1 0 1
0-20 mA 0 0 0 0 1 0
4-20 mA 0 0 1 0 1 0
Cleaning
1
Cleaning function set to ON position.
When the wheel has stopped for
30 minutes, the cleaning function is
activated and the wheel rotates at
minimum speed for 10 seconds.
Rotation monitor 1 Rotation sensor set to ON position.
High speed* 1e wheel rotates at the set maximum
rpm when the switch is set to ON.
Low speed* 1e wheel rotates at the set minimum
rpm when the switch is set to ON.
*) Manual operation (test mode)

OPERATIONAL INDICATIONS
On "Power on" is lit continuously.
It ashes when the control unit has tripped.
Run Comes on when the motor is to rotate, i.e. when the input signal exceeds
the threshold value.
Rotation Flashes when the magnet passes the magnetic sensor, regardless of the
rotation monitor DIP switch setting.
Flashes even if the input signal is lower than the threshold value.
Rotation monitor
Probable fault cause
during installation
Probable fault cause
during operation
Alarms and trips unless a pulse is received every 5 minutes.
- Magnet facing the wrong way
- Magnetic sensor incorrectly connected; see “Connections” on
pages 11 -12.
- Too wide a gap between the magnetic sensor and magnet; max 15 mm
-Broken belt
- Belt slipping
- Stuck wheel
- Magnetic sensor or magnet not intact
Overtemp. motor
Probable fault cause
Alarms and trips if motor winding temperature is too high.
e thermal contact in the motor reverts to normal mode when the
temperature drops.
See "Overcurrent" on page 9.
Overvoltage Alarms and trips if the input voltage exceeds 276 V for more than
4-5 seconds.
Undervoltage Alarms and trips if the input voltage falls below 195 V for more than
4-5 seconds.
ALARMS
All alarms remain in state.
Continued on next page
8
Altri manuali per MiniMax
1
Indice