ICM Controls ICM330 Manuale utente

Installation, Operation &
Application Guide
For more information on our complete
range of American-made products – plus
wiring diagrams, troubleshooting tips and
more, visit us at www.icmcontrols.com
Installation of the ICM330 shall be performed by trained technicians only. Adhere to all local and
national electric codes.
Disconnect all power to the system before making any connections.
Caution!
• Line voltage:120,208,240,277,and480VAC
• Control voltage:18-30VAC
• Current:4ampsmaximum
• Frequency:50-60Hz
• Operating temperature:-40ºFto+176ºF(-40°Cto+75°C)
• Probes:
–Temperature:Thermistor,10Kohmat77°F(25°C)
–Pressure:ICM380(orderedseparately)
• Heat pump override:24VACN.C.orN.O.
• Weight:12ounces(341grams)
Note:TheICM330shouldbeappliedtomotorsandequipmentthathavebeendesignatedbytheir
respectivemanufacturersascapableofbeingspeedcontrolled.
• Mounting:
– Surfacemountusing(2)#8screws
– ItisrecommendedthattheICM330bemountedawayfromthecondenserexhaustairinorderto
maintainloweroperatingtemperatures
Specifications
ICM330
Head Pressure Control with
Optional Heat Pump Override
Regulates head pressure via temperature or pressure input
Connections for ICM330 at 120/208/240/277 VAC
1. Removepowerfromsystem.
2. FieldinstallawirefromLine 1wireto120/280 VACterminal.
3. CutLine 2wire;afxmotorsidetoMotor 2terminalandlinesidetoLine 2terminal.
4. Make24VAC,probeandHPconnections.
5. Verifywiringiscorrect.
6. Powerupsystemandcheckoperation.
FieldInstalledWire
1. Removepowerfromsystem.
2. FieldinstallawirefromLine 1wireto480 VACterminal.
3. CutLine 2wire;afxmotorsidetoMotor 2terminalandlinesidetoLine 2terminal.
4. Make24VAC,probeandHPconnections.
5. Verifywiringiscorrect.
6. Powerupsystemandcheckoperation.
Connections for ICM330 at 480 VAC
Field
Installed
Wire
Connections for Heat Pump System at 480 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLine 1wireto480 VACterminal.
3.CutLine 2wire;afxthecommonfromthedefrost
board’sfanrelaytotheMotor 2terminalandtheLine
fromthecontactortotheLine 2terminal.
4.Make24VAC,probeandHPconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Connections for Heat Pump System at 120/208/240/277 VAC
1.Removepowerfromsystem.
2.FieldinstallawirefromLINE 1wireto120/280VACterminal.
3.CutLine 2wire;afxthecommonfromthedefrostboard’s
fanrelaytotheMotor 2terminalandtheLinefromthe
contactortotheLine 2terminal.
4.Make24VAC,probeandHPconnections.
5.Verifywiringiscorrect.
6.Powerupsystemandcheckoperation.
Example
1.Onlyoneprobetypecanbeusedatatime,temperatureORpressure.
2.AtypicalinstallationisshowninAppendixsection.Thetemperatureprobecan
beattachedtotheU-bend.Usetheprovidedthermo-tapetosecuretheprobe
totheplaceofattachment.
3.Whenusingapressureprobe,installitonthedischargelinetransducertting.
4.AtemperatureorpressureprobeisconnectedtoICM330asshowninthe
respectivewiringdiagrambelow.
Installing and Connecting the Probe
TemperatureProbe
BLUEWHITEGREENREDBLACK
PRESSURE TRANSDUCER
Field Installed Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM NC
Defrost Board
Field Installed Wire
PSC
Fan
Motor
Run
Capacitor
Fan
Relay
COM NC
Defrost Board
1.For non-heat pump applications,theheatpumpselectjumpermustbeintheDefault(N.O.)
position,andtheHPterminalsmustbeleftunconnected.
2.SettheCutoutSpeedandtheHardStartTimetotheappropriatepositionsforthetypeofmotoryou
have(seebelow).
Connections for Air Conditioning Only

Mode of Operations
Whenusingatemperatureprobe,thecontrolwillmaintaincondensertemperaturebetween7°Fabove
and7°FbelowdialedTemperatureSetpoint.ThedialTemperatureSetpointrangeis70°Fto140°F.
Whenusingapressureprobe,thecontrolwillmaintaincondenserpressurebetween20psigaboveand
20psigbelowdialedPressureSetpoint.ThedialPressureSetpointrangeis35psigto465psig.
Theisnocorrelationbetweendialtemperatureandpressurescalesonthecontrol.
Whenthemotorstartsrunningitwillhard startforthelengthoftimedictatedbythehard startdial
setting.Afterthehard starttimehaselapsed,themotorspeediscontrolledbytheprobereading,
temperatureorpressure.Thegreenlightturnsonwhenthemotorrunsatfullspeed.
Asthesensedtemperature/pressuredecreases,theoutputvoltagedecreases.Theyellowlightturnson
duringmotorvariablespeed.Theoutputvoltagemaydecreasetotheminimumvoltagedictatedbythe
cutout speeddial.Astemperature/pressuredecreasesfurther,theoutputvoltagegoestozerovolts.
Theyellowlightturnsoff.
Thecutoutspeeddialadjuststhemotorvoltagerange.Setthecutout
voltagedialaccordingtothetypeofmotoryouhave.
Sleeve Bearing Motors: Setthecutoutspeeddialtothemiddleof
thesleevebearingrange.Inthisrange,
themotorcanrundownapproximately40-
50%ofthefulllinevoltage,whichallows
sufcientRPMsforcoolingandlubrication.
CAUTION!:
Withsleevebearingmotors,itisimportantnotto
adjustoutsidethesleevebearingrangeorbearingfailuremayresult.
Ball Bearing Motors:SetthecutoutspeeddialtotheMINpositionintheballbearingrange.This
positionoffersthegreatestrangeofspeedcontrol.AttheMINsettingthemotor
canrundowntoapproximately20-30%ofthefulllinevoltage.
Note:Afterstartingattherecommendedsettingsforeithersleeveorballbearingmotors,youcanne
tunethecutoutspeedtoachievethedesiredresults.
Setting the Cutout Speed
DuringtheHard Startmode,fullvoltageisappliedtothemotor
duringstartuptoovercomewindmillingandtolubricatethebearings.
Thepositionofthehardstartdialdeterminesthetimeperiodofthe
hardstartmode.Thedialcanbeadjustedbetween0.2secondsand
approximately4seconds.
Setthehardstartdialaccordingtothetypeofmotoryouhave.If
youhaveaball bearing motor,setthehardstartdialtotheMIN
position.Ifyouhaveasleeve bearing motor,setthehardstartdial
tothemiddleofthesleevebearingrange.
Afteryoubeginattherecommendedsetting,youcannetunethehardstarttimewithinthe
recommendedrangeforthetypeofmotoryouhave.
Itisrecommendedthatyouusetheminimumpossiblehardstarttimetoavoidblowingtoomuchcoldair
overthecondenser.
Thehardstartmodeappliesfullvoltagetothemotorforthesettimeperiod.Afterwards,themotorspeed
isdictatedbythetemperature/pressuresensor.
Setting the Hard Start Speed
Appendix A
°C °F Resistance (KΩ)
0° 32° 32.7
5° 41° 25.4
10° 50° 19.9
15° 59° 15.7
20° 68° 12.5
25° 77° 10.0
30° 86° 8.1
35° 95° 6.5
40° 104° 5.3
45° 113° 4.4
50° 122° 3.6
Temperature vs. Probe Resistance
Appendix B
Pressure (psig) Voltage (Vdc)
0 0.5
50 0.9
100 1.3
150 1.7
200 2.1
250 2.5
300 2.9
350 3.3
400 3.7
450 4.1
500 4.5
Pressure vs. Voltage
ICM330 Typical Installation
Condenser
Sensor
Sensor
ReversingValveforHeat
Pump
T-Stat
Control
Transformer
Terminaltobe
usedfor480VAC
Line1
Line2
LineVoltage Motor1
Motor2
Symptom Problem
Unitfailstostart UsinganACvoltmeter,measurethevoltagebetweenthe24VACterminals.It
shouldreadapproximately24volts.
MeasurethelinevoltagebetweenLINE1andLINE2toconrmthatline
voltageispresent.Checkwiringtothefanmotor.
Iflightsareashingalternativelythennoprobeisconnectedormalfunctioning
probe.
Whenusingatemperatureprobe,disconnectitanduseanohmmeterto
measuretheresistancebetweenthewires.Itshouldmatchthechartin
AppendixA.
Whenusingapressureprobe,withpowerappliedtothecontrolusea
voltmetertomeasurevoltsDCbetweenGNDandVout.Thereadingshould
beaccordingtothechartinAppendixB.
Thefuseisblownand/
orsignsofdamageon
theunit
Theunithasbeenmiswiredandmaybepermanentlydamaged.
Thefancyclesfrom
ONtoOFFwith
littleornospeed
modulation
Reducehard startstettingtominimumneededtoacceleratethefanmotor.
Excessivehard startcauseslargepressuredropsbyrunningtoomuchcold
airoverthecondenser.
Reducecutoutsettingtominimumneededforthemotorinuse.
Shouldthecyclingpersist,relocatethetemperatureprobeupthecondenser
toincreasesensitivitytotemperaturechangeand/oradjustthetemperature
setpoint.
Thehighpressure
switchtripsoff
See“Unitfailstostart”above
Checkthesetpointandreduceitifneeded
Troubleshooting
1.TheHeat Pumpterminalsacceptthe24VACsignalfromthereversingvalveholdingcoil.Makea
parallelconnectionfromthereversingvalvetotheHEAT PUMPterminals.
Note:Do not apply a voltage higher than 30 VAC to the HEAT PUMP terminals.
2.IftheHeat PumpisintheHeatingmodeandthereversingvalve
isenergized,thentheHeat Pump Selectjumpermustbeinthe
Default(N.O.)position.
3.IftheHeat PumpisintheHeatingmodeandthereversingvalveisnot
energized,thentheHeat Pump SelectjumpermustbeintheN.C.position.
Connections for Heat Pump Systems
N.O.
N.C.
LIAF069-1
7313 William Barry Blvd., North Syracuse, NY 13212
(Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276
www.icmcontrols.com
ONE-YEAR LIMITED WARRANTY
TheSellerwarrantsitsproductsagainstdefectsinmaterialorworkmanshipforaperiodofone(1)year
fromthedateofmanufacture.TheliabilityoftheSellerislimited,atitsoption,torepair,replaceorissue
anon-casecreditforthepurchasepricesofthegoodswhichareprovidedtobedefective.Thewarranty
andremediessetforthhereindonotapplytoanygoodsorpartsthereofwhichhavebeensubjected
tomisuseincludinganyuseorapplicationinviolationoftheSeller’sinstructions,neglect,tampering,
improperstorage,incorrectinstallationorservicingnotperformedbytheSeller.Inordertopermitthe
Sellertoproperlyadministerthewarranty,theBuyershall:1)NotifytheSellerpromptlyofanyclaim,
submittingdatecodeinformationoranyotherpertinentdataasrequestedbytheSeller.2)Permitthe
Sellertoinspectandtesttheproductclaimedtobedefective.Itemsclaimedtobedefectiveandare
determinedbySellertobenon-defectivearesubjecttoa$30.00perhourinspectionfee.Thiswarranty
constitutestheSeller’ssoleliabilityhereunderandisinlieuofanyotherwarrantyexpressed,implied
orstatutory.Unlessotherwisestatedinwriting,Sellermakesnowarrantythatthegoodsdepictedor
describedhereinaretforanyparticularpurpose.
Altri manuali ICM Controls Controllori

ICM Controls
ICM Controls ICM550 Manuale utente

ICM Controls
ICM Controls ICM2909 Manuale utente

ICM Controls
ICM Controls ICM1511 Series Manuale utente

ICM Controls
ICM Controls ICM870-32A Istruzioni generali

ICM Controls
ICM Controls ICM2812ж ICM2812-KIT Istruzioni generali

ICM Controls
ICM Controls ICM271 Manuale utente

ICM Controls
ICM Controls ICM325A Istruzioni generali

ICM Controls
ICM Controls ICM2810 Manuale utente

ICM Controls
ICM Controls ICM271 Istruzioni generali

ICM Controls
ICM Controls ICM492 Manuale utente