IFM Efector600 TN2531 Manuale utente

Operating instructions
Electronic temperature sensor
TN2531
704467 / 00 10 / 2008
UK

2
Contents
1 Preliminary note....................................................................................................3
1.1 Symbols used.................................................................................................3
2 Safety instructions ................................................................................................3
3 Functions and features.........................................................................................4
4 Function................................................................................................................4
4.1 Communication, parameter setting and evaluation ........................................4
4.2 Switching function ..........................................................................................5
4.3 Analogue function...........................................................................................5
5 Installation ............................................................................................................7
6 Electrical connection.............................................................................................8
7 Operating and display elements...........................................................................9
8 Menu...................................................................................................................10
8.1 Menu structure .............................................................................................10
8.2 Explanation of the menu............................................................................... 11
9 Parameter setting ...............................................................................................12
9.1 General parameter setting............................................................................12
9.2 Configuration of the display (optional)..........................................................14
9.3. Setting of the output signals for OUT1 ........................................................14
9.3.1 Setting of the output function...............................................................14
9.3.2 Setting of the switching limits ..............................................................14
9.4 Setting of the output signals for OUT2 .........................................................14
9.4.1 Setting of the output function...............................................................14
9.4.2 Scaling of the analogue value .............................................................14
9.5 User settings (optional) ...............................................................................15
9.5.1 Zero point calibration...........................................................................15
9.5.2 Setting of the delay time for OUT1 ......................................................15
9.5.3 Setting of the error behaviour of the outputs .......................................15
9.5.4 Setting of the switching logic for OUT1 ...............................................15
9.6 Service functions ..........................................................................................15
9.6.1 Reading of the min/max values for the system temperature ...............15
9.6.2 Reset of all parameters to factory setting............................................15

3
UK
1 Preliminary note
1.1 Symbols used
►Instruction
> Reaction, result
[…] Designation of pushbuttons, buttons or indications
→Cross-reference
Important note
Non-compliance can result in malfunctions or interference.
2 Safety instructions
Please read this document prior to set-up of the unit. Ensure that the product is•
suitable for your application without any restrictions.
Improper or non-intended use may lead to malfunctions of the unit or to un-•
wanted effects in your application. That is why installation, electrical connec-
tion, set-up, operation and maintenance of the unit must only be carried out by
qualified personnel authorised by the machine operator.
Checkthecompatibilityoftheproductmaterials(→12Technicaldata)withthe•
media to be measured in all applications.
10 Operation..........................................................................................................16
10.1 Reading of the set parameters ...................................................................16
10.2 Fault indication ...........................................................................................16
11 Scale drawing ...................................................................................................17
12 Technical data...................................................................................................18
12.1 Setting ranges ............................................................................................19
13 Factory setting..................................................................................................19

4
3 Functions and features
The unit monitors the system temperature in machinery and plant.
4 Function
4.1 Communication, parameter setting and evaluation
The unit displays the current system temperature.•
It generates 2 output signals according to the parameter setting.•
OUT1 Switching signal for system temperature limit value.
OUT2 Analogue signal for system temperature.
It moreover provides the process data via IO-Link.•
The unit is laid out for fully bidirectional communication. So, the following op-•
tions are possible:
Remote display: Reading and displaying the current system temperature.-
Remote parameter setting: Reading and changing current parameter settings-
with the FDT service program ifm Container or via IO-Link.
Using the FDT service program ifm Container, the current parameter settings-
can be stored and transferred to other units of the same type.
The program library of the available DTM objects can be found at www.ifm.com
→Service→Download.
Device-specific parameter lists for IO-Link parameter setting are available at:
www.ifm.com→Selectyourcountry→Datasheetdirect:

5
UK
4.2 Switching function
OUT1 changes its switching state if it is above or below the set switching limits
(SP1, rP1). The following switching functions can be selected:
Hysteresisfunction/normallyopen:[OU1]=[Hno](→fig.1).•
Hysteresisfunction/normallyclosed:[OU1]=[Hnc](→fig.1).•
First the set point (SP1) is set, then the reset point (rP1) with the requested differ-
ence.
Windowfunction/normallyopen:[OU1]=[Fno](→fig.2).•
Windowfunction/normallyclosed:[OU1]=[Fnc](→fig.2).•
The width of the window can be set by means of the difference between SP1 and
rP1. SP1 = upper value, rP1 = lower value.
1 2
T = system temperature; HY = hysteresis; FE = window
4.3 Analogue function
[OU2] defines if the set measuring range is provided as a 4...20 mA signal•
([OU2] = [ I]) or a 0...10 V signal ([OU2] = [U]).
Analogue start point [ASP] defines at which measured value the output signal•
is 4 mA / 0 V.
Analogue end point [ AEP] defines at which measured value the output signal•
is 20 mA / 10 V.
Minimum distance between [ASP] and [AEP] = 5 K.

6
Current output 4...20 mA
Factory setting Measuring range scaled
In the set measuring range the output signal is between 4 and 20 mA.
The green LED also indicates:
Temperature above the measuring range: Output signal 20...20.5 mA.•
Temperature below the measuring range: Output signal drops to max. 3.8 mA.•
If the detection zone is not reached or is exceeded (T < -60°C or T > +160°C), the output•
behavesaccordingtotheparametersetinFOU2(→9.5.3).
Voltage output 0...10 V
Factory setting measuring range scaled
In the set measuring range the output signal is between 0 and 10V.
The green LED also indicates:
Temperature above the measuring range: Output signal 10...10.3 V.•
If the detection zone is not reached or is exceeded (T < -60°C or T > +160°C), the output•
behavesaccordingtotheparametersetinFOU2(→9.5.4).

7
UK
5 Installation
Using process adapters the unit can be adapted to different process connections.
Adapters have to be ordered separately as accessories.
Immersion depth of the sensor: min. 12 mm in the pipe. If you use the adapter
supplied as accessory the correct immersion depth is ensured.
Mounting dimensions with
M12 adapter
Mounting dimensions with
G¼ adapter
Mounting dimensions with
G½ adapter
For optimum response times:
Orientation of the unit: Connector►
against the flow direction of the
medium.
Before installing and removing the unit: Ensure that no medium can leak at
the process connection.
�
Grease the threads of the process connection (1), adapter (2) and nut (3).►
Note: The sensor tip (A) must not be in contact with grease.
Screw the suitable adapter into the process connection.►
Place the temperature sensor onto the adapter and tighten the nut. Tightening►
torque max. 50 Nm. Ensure that the unit is correctly oriented.

8
6 Electrical connection
The unit must be connected by a qualified electrician.
The national and international regulations for the installation of electrical
equipment must be adhered to.
Voltage supply to EN 50178, SELV, PELV.
Disconnect power.►
Connect the unit as follows:►
1 x positive switching + analogue 1 x negative switching + analogue
Pin 1 Ub+
Pin 3 Ub-
Pin 4 (OUT1) Binary switching output temperature monitoring.•
Data channel for bidirectional communication.•
Pin 2 (OUT2) Analogue signal for temperature.•
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white), 3 = BU (blue), 4 = BK (black)

9
UK
7 Operating and display elements
1 to 8: Indicator LEDs
LED 1: Current temperature in °C.-
LED 2: Current temperature in °F.-
LED 8 = Switching status output 1.-
9: Alphanumeric display, 4 digits
Display of the current system temperature.-
Indication of the parameters and parameter values.-
10: Set button
Setting of the parameter values (scrolling by holding pressed; incrementally by pressing-
once).
11: Mode/Enter button
Selection of the parameters and acknowledgement of the parameter values.-

10
8 Menu
8.1 Menu structure
Indice
Altri manuali IFM Accessori

IFM
IFM PN72 Series Manuale utente

IFM
IFM Efector 500 PNI02X Manuale utente

IFM
IFM OMH551 Manuale utente

IFM
IFM efector160 LR2750 Manuale utente

IFM
IFM OF Series Manuale utente

IFM
IFM VSP003 Manuale utente

IFM
IFM MVQ101 Guida all'applicazione

IFM
IFM Efector 200 OJ51 Series Manuale utente

IFM
IFM OY4**S Series Manuale utente

IFM
IFM EC2061 Manuale utente

IFM
IFM TK61 Series Manuale utente

IFM
IFM JD Guida all'applicazione

IFM
IFM PI28 Series Manuale utente

IFM
IFM O5E7 Series Manuale utente

IFM
IFM Efector 200 OJ Manuale utente

IFM
IFM O3D3 Series Manuale utente

IFM
IFM LW2720 Manuale utente

IFM
IFM UGT58 Series Manuale utente

IFM
IFM PN422 Series Manuale utente

IFM
IFM Ecomat 100 EC2082 Guida