IFM AC422S Manuale utente

Original operating instructions
Fail-safe SmartPLC
SafeLine
with Ethernet/IP slave interface
AC422S
80283446/00 03/2019
UK

2
Contents
1 Preliminary note ...................................................................................................4
1.1 Symbols used ................................................................................................4
2 Safety instructions ...............................................................................................4
2.1 General ..........................................................................................................4
3 Items supplied......................................................................................................5
4 Functions and features ........................................................................................6
4.1 Electrical voltage supply ................................................................................6
4.2 Configuration interfaces X3 and X8 ...............................................................6
4.3 AS-i interfaces ...............................................................................................6
4.4 Local safe inputs and outputs X4 ..................................................................7
4.5 Fieldbus interfaces X6 and X7 .......................................................................7
5 Installation............................................................................................................7
6 Operating, connection and display elements .......................................................8
6.1 Operating and connection elements ..............................................................8
6.2 LED indicators ...............................................................................................9
6.2.1 Device LED H1 .....................................................................................9
6.2.2 Interface LEDs on X6, X7 .....................................................................9
6.2.3 Interface LED on X8 .............................................................................9
7 Electrical connection ..........................................................................................10
7.1 Wiring...........................................................................................................10
7.2 Connect the supply voltage ......................................................................... 11
7.2.1 Standard configuration: 24 V power supply and AS-i power supply/
supplies ........................................................................................................ 11
7.3 Connect sensors / actuators ........................................................................12
8 Operation ...........................................................................................................12
8.1 Notes on the EMC-compliant operation .......................................................12
8.2 Settings ........................................................................................................13
8.2.1 Language selection ............................................................................13
8.3 Navigation ....................................................................................................14
8.3.1 Navigation elements ...........................................................................14
8.3.2 Pictograms and main navigation ........................................................15
8.3.3 OSC (Online Support Center) .............................................................16

3
UK
9 Diagnostics ........................................................................................................17
10 Maintenance, repair and disposal ....................................................................17
11 Approvals / tests ...............................................................................................17
12 Additional documents.......................................................................................17
13 Technical data ..................................................................................................18
13.1 Safety classification ...................................................................................19
14 Scale drawing ..................................................................................................20

4
1 Preliminary note
Technical data, approvals, accessories and further information at www.ifm.com.
This document applies to devices of the type
"Fail-safe SmartPLC with Ethernet/IP slave interface" (art. no.: AC422S).
It is part of the device and contains information about the correct handling of the
product.
This document is intended for qualified electricians. These specialists are people
who are qualified by their training and their experience to see and to avoid
possible hazards that may be caused during operation of the device. Installation
and set-up must be carried out by staff qualified in functional safety.
► Read this document before using the device.
► Keep this document during the service life of the device.
1.1 Symbols used
► Instructions
> Reaction, result
[…] Designation of keys, buttons or indications
→ Cross-reference
Important note
Non-compliance may result in malfunction or interference.
Information
Supplementary note
2 Safety instructions
2.1 General
► Observe these operating instructions.
► Adhere to the warning notes on the product.
• In case of non-observance of notes or standards, especially when tampering
with and/or modifying the unit, any liability and warranty is excluded.
• The safe operation of the device is only ensured when the specified
requirements are complied with.
• The applicable technical standards for the corresponding application must be
complied with.
• For installation the requirements according to EN 60204 must be observed.

5
UK
• In case of malfunction of the device contact the manufacturer. Tampering with
the unit is not allowed.
• Do not insert any objects into the device.
• Prevent metal foreign bodies from penetrating.
• After installation of the system perform a complete function check.
• Only use the unit under the specified operating conditions (→ Technical data).
In case of special operating conditions please contact the manufacturer.
Use of the unit in the vicinity of chemical and biological media as well as
ionising radiation is not permitted.
• In case of any questions please contact the safety authorities in your own
country.
WARNING
In case of improper handling of the product, the safety and physical
integrity of persons and machinery cannot be guaranteed.
Death or serious irreversible injuries may result.
► Note all remarks on installation and handling given in these instructions.
► The device must only be used under the specified operating conditions and in
accordance with use as prescribed below.
3 Items supplied
1 fail-safe SmartPLC AC422S
3 Combicon connection terminals
1 original operating instructions AC422S
1 EU declaration of conformity
• Service address list with ifm contacts
If one of the above-mentioned components is missing or damaged, please contact
one of the ifm branch offices.
Device manual and programming manual are not supplied. These are
available at: www.ifm.com.

6
4 Functions and features
The fail-safe SmartPLC SafeLine AC422S integrates two AS-i masters, a safe
PLC, a non-safe PLC, a WEB server and an Ethernet/IP slave interface with 2-port
switch.
The fail-safe SmartPLC SafeLine
• controls the exchange of data to the sensor / actuator level.
• can be used as a safe and a non-safe controller (PLC).
• communicates with the higher-level control level via Ethernet/IP.
• visualises sensor/actuator data on the integrated WEB server.
• allows device configuration via the WEB server.
4.1 Electrical voltage supply
• Device supply from 24 V (AUX)
4.2 Configuration interfaces X3 and X8
• RJ45, twisted pair (10 Mbps and 100 Mbps)
• TCP / IP - Transport Control Protocol / Internet Protocol
• UDP/IP - User Datagram Protocol
• EtherCAT (Master) including FSoE (Fail Safe over EtherCAT)
• Modbus TCP (master / slave)
• 3S fail-safe network-global variables
• HTTP server
• CODESYS programming interface
• Secure network variables
• OPC UA server
• CODESYS Web visualisation
4.3 AS-i interfaces
• 2 AS-i masters
• AS-i Power24 compatible
• Ground-fault detection

7
UK
4.4 Local safe inputs and outputs X4
In the following they are called Safe-IO.
• 8 connection terminals for
- up to 4 safe inputs according to SIL3 / PL e / category 4
- up to 8 non-safe inputs
Use safe inputs always with two channels.
• 4 connection terminals for
- up to 2 safe semiconductor outputs according to SIL3 / PL e / category 4
- up to 4 non-safe outputs
4.5 Fieldbus interfaces X6 and X7
• Ethernet/IP
• DLR support
• 10 Mbps and 100 Mbps
5 Installation
The device must only be installed, connected and put into operation by a qualified
electrician as the safe function of the device and machinery is only guaranteed
when installation is correctly carried out.
The installation and connection must comply with the applicable national and
international standards. Responsibility lies with the person installing the device.
► Fix the device onto a 35 mm raised rail.
► Vertical installation (upright).
► Adhere to a minimum distance of 30 mm between the ventilation holes
(perforated sheet) and other parts.
► Maximum operating altitude: 2000 m above sea level
► The protection rating of the device is IP 20. The device must be installed at a
protected location (e.g. control cabinet with IP 54).
► In the event of degree of soiling 2 the device has to be installed in a control
cabinet with min. protection rating IP 54.
► Lay the cables in a cable duct.

8
► Keep the installation space of the device free from electrically-conductive
particles.
Ensure a condensation-free environment. Avoid excessive dust, vibration
and shock. The air circulation through the vents must not be impeded.
Avoid installation in direct vicinity of frequency inverters or other interfering
sources.
6 Operating, connection and display elements
6.1 Operating and connection elements
12
0
11
1: Device LEDs H1 green / yellow / red
2: Softkeys

9
UK
3: Navigation buttons
4: AS-i bus und FE connection X1
5: 24V device voltage supply X2
6: Connection for 24V Safe-IO voltage supply and local inputs/outputs X4
7: Front fl ap
8: Slot for SD card
9: Confi guration interface X3
10: Confi guration interface X8
11: Ethernet/IP interface IN X7
12: Ethernet/IP interface OUT X8
6.2 LED indicators
6.2.1 Device LED H1
The LED on the front panel signals the state of the device and the connected
systems.
LED status Description
Green LED on: > Device has been started.
> There is no warning message.
> There is no error message.
Yellow LED flashes slowly (0.5 Hz): > There is a warning message.
> There is no error message.
Red LED flashes quickly (2 Hz): > There is an error message.
6.2.2 Interface LEDs on X6, X7
LED status Description
Green LED on: > Physical connection OK
LED yellow flashes: > Reception of data
6.2.3 Interface LED on X8
LED status Description
Yellow LED on: > Physical connection OK
LED green flashes: > Reception of data

10
7 Electrical connection
The unit must be connected by a qualified electrician.
► Disconnect power before connecting the device.
► Observe the national and international regulations for the installation of
electrical equipment.
► Connect the device as indicated on the terminals.
► Ensure an electrical connection between the fail-safe SmartPLC
SafeLine AC422S (terminal X1, pin 5 FE) and the ground of the
installation.
7.1 Wiring
Terminal X1 Pin Description
AS-i 2 + 1 AS-i + for AS-i line 2
AS-i 2 - 2 AS-i - for AS-i line 2
AS-i 1 + 3 AS-i + for AS-i line 1
AS-i 1 - 4 AS-i - for AS-i line 1
FE 5 Functional earth
6 not connected
Terminal X2 Pin Description
24 V 1 +24 V device supply
GND 2 GND
Terminal X4 Pin Description
1...8 IN1...8
9...12 OUT1...4
13,14 GND
15,16 +24 V power supply Safe-IO module
Indice
Altri manuali IFM Portale

IFM
IFM mobileIoT CR3145 Manuale utente

IFM
IFM ZB0929 Manuale utente

IFM
IFM CR3157 Manuale utente

IFM
IFM AL1350 Manuale utente

IFM
IFM ZB0929 Manuale utente

IFM
IFM Ecomat 300 AC1421 Guida all'applicazione

IFM
IFM CR3158 Manuale utente

IFM
IFM mobileIoT CR3156 Manuale utente

IFM
IFM AL1940 Guida all'applicazione

IFM
IFM AIK050 Manuale utente
Manuali Portale popolari di altre marche

LST
LST M500RFE-AS Manuale utente

Kinnex
Kinnex Media Gateway Manuale utente

2N Telekomunikace
2N Telekomunikace 2N StarGate Manuale utente

Mitsubishi Heavy Industries
Mitsubishi Heavy Industries Superlink SC-WBGW256 Manuale utente

ZyXEL Communications
ZyXEL Communications ZYWALL2 ET 2WE Manuale utente

Telsey
Telsey CPVA 500 - SIP Manuale utente