IGD TOCSIN i700 Guida

TOCSIN i700
INSTALLATION
AND
USER INSTRUCTIONS
Triton House
Crosby Street
Stockport
SK2 6SH
England
Tel: +44 (0)161 483 1415
Fax: +44 (0) 161 484 2345
Email: [email protected]
Website: www.internationalgasdetectors.com
FS646773
REF: ROS 66-8 V10.1
EMS696504

Table of Contents
Specification
CE Declaration
Overview
Interface Wiring
19" Rack Systems
Highway Splitting
Production Menu (Password 200)
Wiring Relay Outputs
Accepting and Resetting Alarms
Test FIRE Input Channels
Addressable relay Cards
Testing Addressable Relays
Modbus
Common Alarms
Copy Alarms
FIND Command
Mimic Panels
Battery Backup Run Time
Alarm Actions
User Menu (Password 100)
Zero & Calibrate Command
Channel Setup
Powering 3rd Party Devices
Setting Alarm Levels
Test Addressable Sensors
Operating System
Engineering Menu (Password 50)
Integrated Battery Backup
20
24
27
36
16
6
4
3
5
17
18
19
21
26
28
30
31
34
43
44
51
45
40
46
39
41
42
49
Page 2 of 52

NOTE: Operation on an incorrectly selected supply voltage will damage the controller
Should the control panel be used in conjunction with portable generating equipment, care should be taken to ensure that
the electrical supply is within the tolerance band described above. The control panel may be stored at temperatures
0 0
between 0 C and 55 C. If stored at low temperatures and then brought into a warmer environment, condensation may
form on some components. In such a situation , this condensation should be allowed to evaporate prior to use of the
equipment. If stored at high temperature, care should be taken to ensure that humidity condensation does not enter
critical electrical components, for example the power supply. The Control Panel is designed to operate within
o o
specification for ambient temperature between 0 C and 55 C, relative humidity up to 95% ( non-condensing ).
Switch Selection Option 110V AC (88 to 132V AC) 47 to 63Hz
AC Mains Powered 230V AC (176 to 264V AC) 47 to 63 Hz
Standard voltage and frequency range is:-
This product must be earthed in accordance with local safety regulations.
DC Low Voltage Powered 18 to 30V DC
The Control Panel leaves the factory configured for the supply voltage stated on the customers order.
!Warning !
On installation alarms will need to be configured to signal when monitored gas levels have breached safe limits. The
control panel will be shipped in a semi-configured state which must be checked and configured during commissioning to
match the applications cause and effect requirements. Failure to do so will result in an ineffective system.
Power Source 88 to 132V AC (110V AC Selected) or 176 to 264V AC (230V AC Selected)
Display 2 x 16 backlight LCD
Operating Temperature 0°c to 55°c
Operating Humidity Up to 95% non-condensing
Resolution 0.00% or ppm Range Dependant
Update Rate 1 Second
Size (mm) 255 (H) x 265 (W) x 100 (D)
Protection Standard IP54
Inputs Up to 4 or up to 8 x 4-20mA loops
8 analogue 4-20mA loopsInputs
2 x RS485 data highways for up to 64 detectors (700+)
3 x configurable SPCO relays (7 Amp non conductive load)
1 x fault SPCO relays (7 Amp non conductive load)
1 x solid state audio/sounder 24VDC
Outputs (Standard)
1 x solid state visual/flasher 24VDC
Outputs (Optional)
Optional Equipment Battery backup 1.2Ah or 2.4Ah
CE Declaration BS EN61000-6-4 EMC Compatibility 'Emissions'
Weight 3.65 KG
BS EN 61000-6-2:2001 EMC Compatibility 'Immunity'
BS EN 61010-1: 2001 Safety requirements, electrical equipment
Who should read this manual.
This manual is intended for use by trained installers of gas detection systems who are technically competent and
have all necessary tools to undertake installation and maintenance on this type of equipment.
You should not undertake any of the procedures in this manual if you do not have access to the correct equipment,
have not undertaken training on this or similar equipment or are not technically qualified to install this equipment.
Calibration gases and test equipment is available from IGD.
Failure to install and maintain the equipment properly can render the detection system ineffective.
47 to 63 Hz 150 Watts DC Option Available
Additional 8 way relay cards, I/O Nodes
Gas Detectors
Check ratings for maximum I/O from PSU
Page 3 of 52

EC Declaration of Conformity
TOCSIN i700
Declares that the product listed as:
Addressable & analogue Gas Detection Control Panel
Issued by: Oliver IGD Limited, Stockport, SK2 6SH , United Kingdom
Signature: Declaration of Conformity in accordance with EN ISO/IEC 17050-1:2004
Name: Andrew J Collier M.I.O.D
Position: Managing Director Date: 1.January 2019 Declaration Ref: I700-DEC-1
Octagon House
EMC Tested by:
TUV - SUD
Concorde Way
PO 15 5RL Fareham
Are in conformity with the provisions of the following European Directive(s) when installed, operated, serviced and maintained
in accordance with the installation and operating instructions contained in the product documentation.
And that the standards and/or technical specifications referenced below have been applied or considered.
2004/108/EC EMC Directive
2006/95/EC Low Voltage Equipment Directive (note not applicable to 24V DC Powered Versions)
EN 61779-1:2000
EN 61000-6-2: 2005
EN 50271:2001
EN 61000-3-2/A2: 2009
EN 61000-6-4: 2007
Technical File Reference
EN 61000-3-3: 2008
EMC Generic standards. Emission standard for industrial environments
EMC Limits. Limitation of voltage changes, voltage fluctuations and flicker in public low-voltage
supply systems, for equipment with rated current ≤ 16 A per phase
Electrical apparatus for the detection and measurement of flammable gases, general
requirements and test methods.
Electrical apparatus for the detection and measurement of combustible gases, toxic gases or
Oxygen: requirements and tests for apparatus using software and or digital technologies.
Excluding requirements for SIL
EMC Generic standards. Immunity for industrial environments
EMC Limits. Limits for harmonic current emissions (equipment input current ≤ 16 A per phase)
T700-TF9
TUV Certificates and reports can be checked on-line at
https://www.tuev-sued.de/industry_and_consumer_products/certificates
Oliver IGD Limited of
Stockport, SK2 6SH
Issuers name and address:
United Kingdom
Crosby St,
Triton House
Page 4 of 52
Wrexham Industrial Estate,
United Kingdom
Quality Assurance Notification Number:
Quality Assurance Certificate Number
Units 16-18 Abenbury Way,
Wrexham, LL13 9UZ
16PQAN0014
2585
Oliver IGD Limited Operate an
Independently assessed ATEX/IECEX
QAN.
Oliver IGD Limited operate an independently
assessed ISO9001:2015 Quality Management and
ISO14001:2015 Environmental Management System
United Kingdom
BSI Assurance UK LTD,
London, W4 4AL
Certificate Numbers
FS0646773 & EMS696504
Select Oliver IGD when prompted on the website to view certificates
Certificate Number
E8N 15 02 91327 001

L N E
PSU SET TO 230V AC
Tocsin 700 Panel Overview
2 x 16 LCD Display
24V DC Panel Power Digital Inputs
Jog Wheel
3 off Configurable
Relay Outputs
With Activation
Indication Lamps
Sounder/Flasher
Outputs
Fault Relay Outputs
RS 485 Detector
Data Highway
Connector Port 1
‘C1’
(Addressable Versions)
RS 485 Detector
Data Highway
Connector Port 2 ‘C2’
(Addressable Versions)
8 off 4-20mA Loop Inputs
Mains/DC Input
(Check Supply Option Before Use)
Grounding Points
RS232 Comm
Port
Backup Battery
Battery Connector
Power to Main PCB
24V PSU Input
Volt Free Contact Opens On Loss of Mains Power
Label Indicates
Voltage Input as
Shipped From Factory
By Default 230V AC
Use Switch to Change
if Necessary
Page 5 of 52
IMPORTANT
When first powering systems which include an IGD battery backup the batteries MUST be connected first for
correct operation. During initial startup the panel software will check the battery condition, if mains power is
applied first then the batteries cannot be functionally checked and the panel will report an error.
Control panels are usually shipped pre-configured with a basic alarm strategy. Before installation check the
documentation provided to ensure the programmed cause and effect matches the site requirement. If it does
not then the system will need to be re-programmed by the installer using the embedded panel software or
PC based T700 setup software.

Tocsin 700 Interface wiring
Sounder Alarm
Max Current
150mA 24V DC
These 3 relays can be assigned,
named, zoned etc using the Tocsin
700 operating software.
Dedicated fault relay output, this output
is energised in normal operation
In all Cases:
Relay contact ratings.
7A @ 250V AC Non-Inductive
7A @ 30V DC Non-Inductive
Spike suppression must be fitted
Note that FAULT relays are normally
energised on power up.
Addressable control panel versions only.
See 'Addressable Sensors' Section
24V DC
24V DCAUDIO
OUTPUT
VISUAL
OUTPUT
SOUNDER O/P
WARNING LAMP O/P
Enclosure
Ground
Enclosure
Ground
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 1000M.
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 1000M.
Blue
Red
Black
Red
Blue
TOCSIN 102/A
TOXIC GAS
DETECTORS
TOCSIN 102IR
FLAMMABLE GAS/
CO2 DETECTORS
+24V DC
B
A
0V
Note Flasher on
with alarm level 1.
Buzzer on with
alarm level 2.
NO NC
COM
AL1
AL2
AL3
0V DC
4-20mA IN
+24V DC
GND
GND
Page 6 of 52

Tocsin 700 Interface wiring...continued
T106P Pellistor
Flammable Gas
Detectors
1.5mmSQ See Panel
for recommended cable
types.Max cable
run 1000M.
0V DC
4-20mA IN
+24V DC
GND
ZERO
FAULT
CAL
360
CHASS
24V DC
B
A
GND
mA
P Y W
Common
Active
Compensator
mA+360CONC0V mA-
Page 7 of 52

Tocsin 700 Interface wiring...Digital Port
Located at the top edge of the Tocsin
700 card is a 4 way connector used to
allow digital interface to the Tocsin 700
operating system as follows:
0V common
Password Inhibit
Reset Alarms
Inhibit Alarms
1 2 3 4
Page 8 of 52

0V DC
4-20mA IN
+24V DC
GND
Tocsin 700 to Tocsin 103 2 wire Detector Series
Tocsin 700 Interface wiring...continued
Enclosure
Ground
4-20mA Toxic
And Oxygen Gas
Detectors
1.5mmSQ See Panel
for recommended cable
types. Typical max cable
run 500M.
24V DC
SCREEN
4-20mA
Page 9 of 52

0V DC
4-20mA IN
+24V DC
GND
Tocsin 700 Interface wiring...continued
Tocsin 700 to Tocsin 103 3 wire Detector Series
Enclosure
Ground
4-20mA Flammable
And CO2 Gas
Detectors
Cable Guidance Panel
It is imperative to use cabling which suits
the environment in which the T700 and its
sensors are to be used. The following is intended
as a guide.
Fit 1.5mm SQ cable for analogue systems
Fit 2.5mm SQ cable for addressable systems
Use
Pirelli LSX type cable for office/light commercial
un-zoned installations
Steel Wire Armored or CY cable for medium/heavy
industrial un-zoned installations
Mineral Insulated Pyro cable for all hazardous
area zoned installations.
Note in all cases the T700 Panel must be installed outside
of any hazardous area and must be supplied via
a fused spur.
1.5mmSQ See Panel
for recommended cable
types. Max cable
run 1000M.
Screen
0V DC
24V DC
4-20mA
GND
Page 10 of 52