innovair 18K Manuale operativo

Thank you very much for purchasing this Air Conditioner. Please
read this use and installation instructions carefully before installing
and using this appliance and keep this manual for future reference.
Hyper Heat Condenser
User and Installation Manual

NOTE:
●This heat pump air conditioner has been designed for the following temperatures.
Operate the heat pump air-conditioner within this range.
DC Inverter Unitary Series
Model
Mode
Outdoor working temperature
Maximum
Minimum
18K/24K/36K
Cooling Operation
14℉(-10℃)
Heating Operation
75℉(24℃)
-13℉(-25℃)
42K
Cooling Operation
14℉(-10℃)
Heating Operation
75℉(24℃)
-4℉(-20℃)
Contents
Safety instructions..........................................................................................................................................1
Refrigerant flow diagram................................................................................................................................3
Installation instruction....................................................................................................................................5
Installation diagram ........................................................................................................................................5
Transportation and handling before installation ............................................................................................6
Installation locations selection........................................................................................................................6
Drainage elbow and drain hose installation ...................................................................................................6
Outdoor unit installation ................................................................................................................................7
Refrigerant piping...........................................................................................................................................7
Wiring ..........................................................................................................................................................10
Trial run .......................................................................................................................................................14
Original instructions
●Storage condition: Temperature -13~140℉ (-25~60℃)
Humidity 30%~80%

1.This air conditioner uses new refrigerant HFC (R410A).
2.Since the max. working pressure is 550psig (3.8MPa), some of the piping and installation
and service tools are special.
3.This air conditioner uses power supply: 208-230V ~, 60Hz.
Please read these SAFETY PRECAUTIONS carefully to ensure correct installation.
·Be sure to use a dedicated power circuit, and do not put other loads on the power supply.
·Be sure to read these SAFETY PRECAUTIONS carefully before installation.
·Be sure to comply with SAFETY PRECAUTIONS of installation manual, because it contains
important safety issues. Definitions for identifying hazard levels are provide below with their respective
safety symbols.
WARNING:Hazards or unsafe practices which COULD result in severe personal injury or death.
CAUTION: Hazards or unsafe practices which COULD result in minor personal injury or product
or property damage.
·Please carefully file indoor and outdoor unit manual away for future reference.
WARNING
1
Safety precautions

·Perform grounding
Does not connect the earth wire to a gas pipe, water pipe, lightning rod or telephone earth wire.
Defective grounding could cause an electric shock.
·Do not install the unit in a place where an inflammable gas leaks.
If gas leaks and accumulates in the area surrounding the unit, it could cause an explosion.
·Fasten a flare nut with a torque wrench as specified in this manual.
When fastened too tight, a flare nut may break after a long period and cause a leakage of refrigerant.
·Install an earth leakage breaker depending on the installation place(where it is humid).
If an earth leakage breaker is not installed, it could cause an electric shock.
·Perform the drainage/piping work securely according to the installation manual.
·If there is a defect in the drainage/piping work, water could drop from the unit and household goods
could be wet and damaged.
CAUTION
2
·Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.
·This appliance is not intended for use by persons (including children) with reduced physical, sensory
or mental capabilities, or lack of experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person responsible for their safety.
·Children should be supervised to ensure that they do not play with the appliance.
·If the appliance is fixed wiring, the appliance must be fitted with means for disconnection from the
supply mains having a contact separation in all poles that provide full disconnection under over
voltage category III conditions, and these means must be incorporated in the fixed wiring in
accordance with the wiring rules.
·If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified persons in order to avoid a hazard.
·The appliance shall be installed in accordance with national wiring regulations.
·Servicing shall only be performed as recommended by the equipment manufacturer.
·The method of connection of the appliance to the electrical supply and interconnection of separate
components is detailed in below part. The wiring diagram with a clear indication of the connections
and wiring to external control devices and supply cord is detailed in below part.
·In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not
be supplied through an external switching device, such as a timer, or connected to a circuit that is
regularly switched on and off by the utility.
·It is necessary to allow disconnection of the appliance from the supply after installation. The
disconnection may be achieved by incorporating a switch in the fixed wiring in accordance with the
wiring rules. During service and when replacing parts, be sure to disconnect the appliance from its
power source. If the disconnection is not foreseen, a disconnection with a locking system in the
isolated position shall be provided.
·The information of dimensions of the space necessary for correct installation of the appliance
including the minimum permissible distances to adjacent structures is detailed in below part.
·This appliance is intended to be used by expert or trained users in shops, in light industry and on
farms, or for commercial use by lay persons.
·Instructions on addition charging of refrigerants are detailed in below part.
Safety instructions
Safety precautions

Refrigerant flow diagram
3
UNIT A
UNIT B
UNIT A
UNIT B
COMPRESSOR
INDOOR UNIT OUTDOOR UNIT
Cooling cycle
Heating cycle
18K
UNIT A
UNIT B
UNIT C
UNIT A
UNIT B
UNIT C
COMPRESSOR
INDOOR UNIT OUTDOOR UNIT
Cooling cycle
Heating cycle
24K

Refrigerant flow diagram
Cooling cycle
Heating cycle
COMPRESSOR
INDOOR UNIT OUTDOOR UNIT
VAPOR LIQUID SEPARATOR
36K
Cooling cycle
Heating cycle
COMPRESSOR
INDOOR UNIT OUTDOOR UNIT
VAPOR LIQUID SEPARATOR
42K
EEV E
EEV D
EEV C
EEV B
EEV D
EEV C
EEV B
EEV A
EEV A
4

Installation diagram
Figures in this manual are only a simple presentation of the unit, it may not match the external appearance of the unit you purchased.
Installation must be performed in accordance with the national wiring standards by authorized personnel only.
outdoor unit
5
Air intake distance from
the wall should be
over 4in.(100mm)
Air intake distance from the wall
over 14in.
(350mm)
air outlet distance from the wall
should be over 20in.(500mm)
should be over 4in.(100mm).
Distance from
the obstacle
should be over
12in.(300mm).
Installation instructions

6
Installation instructions
Put Cloth or Paper
Transport the product as close to the installation location as
practical before unpacking.
·Handling Method
When hanging the unit, ensure a balance of the unit, check
safety and lift up smoothly.
(1) Do not remove any packing materials.
(2) Hang the unit under packing condition with two ropes,
as shown in Fig below.
·Handling
If have no package to move, Please protect with cloth
or paper.
CAUTION:
Before choosing the installation site, obtain user approval.
·Where it is not exposed to strong wind.
·Where airflow is good and clean.
·Where it is not exposed to rain and direct sunshine.
·Where neighbors are not annoyed by operation sound or hot air.
·Where rigid wall or support is available to prevent the increase of operation sound or vibration.
·Where there is no risk of combustible gas leakage.
·Where it is at least 3m away from the antenna of TV set or radio. An amplifier may be required for the affected
device.
·Install the unit horizontally.
·Please install it in an area not affected by snowfall or blowing snow. In areas with heavy snow, please install a
canopy, a pedestal and/or some baffle boards.
Avoid the following places for installation where air conditioner trouble is liable to occur.
·Where there is much machine oil.
·Salty places such as seaside.
·Where sulfide gas is generated such as a hot spring.
·Where there is high-frequency or wireless equipment.
NOTE:
When operating the air conditioner in low outside temperature, be sure to follow the instruction describe below.
·Never install the outdoor unit in a place where its air inlet/outlet side may be exposed directly to wind.
·To prevent exposure to wind, install the outdoor unit with its air inlet side facing the wall.
·To prevent exposure to wind, it is recommended to install a baffle board on the air outlet side of the outdoor unit.
transportation and handling before installation
Installation locations selection
Drainage elbow and drain hose installation
Install Drainage Elbow and Drain Hose
·The condensate water may drains from the outdoor unit
when the unit operates in heating mode. In order to avoid
disturbing neighbors also to protect the environment, it is
necessary to install a drainage elbow and a drain hose to
drain out the condensate water.
·Please do the drainage work before the indoor unit and
outdoor unit are connected. Otherwise, it will be difficult
to install drainage elbow after the machine becomes
immovable.)
·Connect the drain hose (field-supplied, inside diameter:
15mm) as shown in the figure for drainage.
Drain hose
Drainage elbow
NOTE:
Do not use the drain elbow in the cold region. Drain
may freeze to stop the fan runs.

NOTE:
Model
Outer Diameter of Pipe (in./mm)
Gas
Liquid
18K/24K/36K/42K
3/8(9.52)
1/4(6.35)
Outdoor Installation
Concrete base or alike
Min.4in.(10cm)
Setscrew
(at least 4)
About 16in.(40cm)
About 4in.(10cm)
unit: inch(mm)
Installation instructions
7
[Unit: in. (mm)]
Model
A
B
C
D
E
F
d
18K
33-7/8
(860)
12-3/16
(310)
21-11/32
(542)
13-7/16
(341)
14-1/2
(368)
6-5/8
(168)
7/16*21/32
(11*17)
24K/36K/
42K
37-3/8
(950)
13-3/8
(340)
22-7/8
(580)
14-15/16
(380)
16-1/4
(414)
7-1/4
(185)
5/8
(15)
The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the
outdoor and indoor units, are listed below. The shorter the refrigerant piping is, the better the performance will be.
So the connecting pipe should be as short as possible.
1. Piping requirement
2. Piping material
(1)Prepare the copper pipe on the spot.
(2) Choose dustless, non-humid, clean copper pipe. Before installing the pipe, use nitrogen or dry air to blow away
the dust and impurity on the tube.
Additional refrigerant charge
The unit has been filled with refrigerant, but if L (total pipe length) exceeds standard length, additional
refrigerant (R410A) change is required.
For 18K: Additional refrigerant charge=[L-50ft (15m)]×0.807oz/5ft (15g/m)
For 24K: Additional refrigerant charge=[L-75ft (22.5m)]×0.807oz/5ft (15g/m)
For 36K: Additional refrigerant charge=[L-98ft (30m)]×0.807oz/5ft (15g/m)
For 42K: Additional refrigerant charge=[L-125ft (37.5m)]×0.807oz/5ft (15g/m)
Refrigerant piping
18K
24K
36K
42K
Piping to each indoor unit
(A/B/C/D/E)
ft./m
≤82(25)
≤65.6(20)
≤65.6(20)
≤65.6(20)
Total length of piping between all
units
ft./m
A+B≤
164(50)
A+B+C≤
197(60)
A+B+C+D≤
246(75)
A+B+C+D+E
≤262(80)
Max height difference between
indoor unit and outdoor unit (F)
ft./m
≤49 (15)
max height difference between
indoor units (G)
ft./m
≤25 (7.5)
Model
Item
Outdoor unit
Indoor unit
Pipe length E
B
C
D
E
A
Pipe length A
Height difference F
Height
difference G

3. Processing of Refrigerant Piping
(1) Pipe cutting
·Cut the cooper pipe correctly with pipe cutter.
(2) Burrs removal
·Completely remove all burrs from the cut cross section of the pipe.
·Put the end of the copper pipe downward to prevent burrs from
dropping in the pipe.
(3) Putting nut on
·Remove flare nuts attached to indoor and outdoor units, then put them
on pipe having completed burr removal.
(Not possible to put them on after flaring work).
·Flare nut for pipe depending on the diameter of pipe.
(4) Flaring work
·Perform flaring work using flaring tool as shown below.
(5) Check
·Compare the flared work with the figure below.
·If flare is noted to be defective, cut off the flared section and perform flaring work again.
危 险
!CAUTION
(3)Piping thickness and material use the pipe as below.
Thickness
[inch(mm)]
inch(mm)
Diameter
[inch(mm)]
[inch(mm)]
Wheninstallingpipethrough
thewall,secureacapatthe
endofthepipe.
Correct CorrectIncorrect Incorrect
Correct Incorrect
HoleHole
Attachacap
orvinyltape.
Attachacap
orvinyltape.
Attachacap
orvinylbagwith
rubberband.
Donotplacethepipe
directlyontheground.
Rainwatercan
enter.
Diameter
Tilted Uneven Burred
No good
Good
o
90
Burr Copper pipe
Spare
reamer
Pipe cutter
Flare nut
Copper pipe
Flaring tool
Clutch type Wing nut type
Die
Copper pipe Flare nut Copper pipe
Die
York
Smooth all around
Inside is shining without any scratches
Double Spanner Work
TighteningTorqueforFlareNut
Pipe Size
Torque
8
1/32(0.8)
1/4( 6.35)
1/4( 6.35)
1/4(6.35) 11/32(9.1)
1/2(13.2)
10/16(16.6)
3/4(19.7)
3/8( 9.52)
3/8( 9.52)
3/8(9.52)
1/2( 12.7)
1/2( 12.7)
1/2(12.7)
5/8( 15.88)
5/8( 15.88)
5/8(15.88)
1/32(0.8)
1/32(0.8)
1/32(1.0)
14.75ft-lb (20N·m)
29.5ft-lb (40N·m)
59ft-lb (80N·m)
44.25ft-lb (60N·m)
Installation instructions