IQsocket IQTB-TC840 Manuale utente

User guide www.IQtronic.com
Intelligent power
sockets
IQsocket IQTB-TC840
…makes your li e more com ortable
User guide
Double IP thermometer/thermostat,
hygrometer/hygrostat with
datalogger and scheduler based on
user's condition.
IQTB-TC840
or FW 1.0.3

User guide www.IQtronic.com
Important noti ication ....................................................................... 3
1
Product description ......................................................... 4
1.1 Possible use of the device IQTB-TC840 ............................................. 4
2
Installation ..................................................................... 5
2.1 Description o the device board, inputs and outputs ................... 5
2.2 Installation dimensions. .............................................................. 6
2.3 Power supply o the IQTB-TC840 ................................................ 6
3
Device con iguration ....................................................... 7
3.1 Displaying current values. ........................................................... 7
3.1
Setting device parameters ...................................................... 10
3.3 Utility ......................................................................................... 12
3.2
SNMP MIB table ...................................................................... 12
3.5 Description o connectors and board .......................................... 13
3.6 Set output - menu or setting the output relays manually,
automatically by the scheduler, by conditions, di erentially or
equithermal table. ............................................................................ 14
4
Use o the button DEF ................................................... 17
5
So tware ....................................................................... 17
5.1 Utility IQlocator.exe ................................................................... 17
6
Reading values using SNMP protocol. ............................ 19
6.1
Reading values rom history using SNMP. .............................. 20
7
Reading using XML ormat, ile status.xml .................... 21
8
Speci ications ................................................................ 22
9
Warranty and sa ety recommendations ......................... 22

©2016 IQtronic technologies Europe, s.r.o.
P ge 3 of 22
Important noti ication
This product is not supposed to be used for medic l pplic tion.
The product h s to be inst lled within suit ble covering providing the
protection g inst short circuits nd cont cts with other conductive p rts of the
set.
It is designed for indoor inst ll tions. When inst lling outdoors, use mounting
c sing with ppropri te cover ge.
The product cont ins no rep ir ble p rts nd is f ctory-tested for full
function lity.
Do not rep ir d m ged product by yourself nd send it to the m nuf cturer's
di gnostics.
Improper wiring nd short-circuits on bo rd connections m y le d to
perm nent d m ge of the product, which is not covered by the m nuf cturer's
w rr nty.
This product must be inst lled by qu lified person. Its inst ll tion must be
performed in ccord nce with relev nt regul tions for inst ll tion pl ce.
The m nuf cturer reserves the right to modify this m nu l or the firmw re
without notific tion.
M nuf cturer of this device ssumes no responsibility for ny d m ge, injury,
loss or expenses incurred due to errors or omissions in ny inform tion of the
m nu l.

©2016 IQtronic technologies Europe, s.r.o.
P ge 4 of 22
1Product description
IQTB-TC840 IQTRONIC IP SMART BOARD is double IP LAN
thermometer/thermost t or hygrometer / hygrost t. It is device for
utom tic monitoring function of the temper ture / humidity / pressure, with
the possibility of w tching their limits, including the d t stor ge in the intern l
memory up to one ye r, including visu liz tion using gr ph nd its setting.
All v lues c n be re d vi SNMP protocol v.1.0. It Displ ys nd rchives lso
the extreme v lues with time st mp of cre tion / registr tion.
The product is equipped with one Ethernet interf ce with the m n gement vi
HTTP nd:
1. Two output rel ys with ch ngeover cont cts of 1A / 30VDC - resistive
lo d. It lso includes controller for inductive lo d.
2. Two univers l inputs for connecting temper ture nd humidity-pressure
sensors with possibility of st nd rd DS18B20 with r nge of -55 to 125
degrees C.
3. Integr ted temper ture sensor on bo rd of the device
4. LED indic tors for displ ying output st tes.
5. Passive POE RJ45 with wide-range power supply rom 6 to 36V
DC +- 20%.
6. Very low power consumption o 1W
7. Possibility of inst l tion on DIN r il using DIN d pter.
The v lues visu lis tion is re l-time, thus it is possible to monitor the current
v lues in re l time.
1.1 Possible use of the device IQTB-TC840
•Any monitoring of temper ture, humidity both rel tive nd bsolute, lso the
dew point nd pressure - depending on the extern l sensor, i.e. s IP LAN
thermost t, hygrost t.
•Monitoring sensor v lues nd storing them. And lso displ ying to / from the
d t logger with the possibility of d t re ding using SNMP.
•M nu l control of two outputs.
•Autom tic control of the outputs - by progr mm ble scheduler with up to 30
v ri ble records, by exceeding / dropping below the limits , by their
difference - differenti l control or equitherm l t ble - equitherm l control.
•M nu l control of outputs directly from the m in menu, by pressing I using
SNMP.

©2016 IQtronic technologies Europe, s.r.o.
P ge 5 of 22
2Installation
2.1 Description o the device board, inputs and outputs
DEF This button is for ouputs control – short press. Or for the f ctory
def ult settings.
10M Eth Ethernet RJ-45 j ck. P ssive PoE support (incomp tible with
802.3 f, 6-36VDC ± 20%).
6-24VDC Power connector, recommended volt ge is 12VDC ± 20%.
O1,O2 Yellow LED – outputs st tus.
PWR Red LED, blinks t interv ls of 1 sec – regul r oper tion.
ETH Green LED, sby shining indic tes connection to Ethernet. By
dimming indic tes its ctivity.
GND 0VDC potenti l for sensors (yellow wire, yellow pin pin)
T1,T2 Sensor input for temper ture sensor (white wire, green pin)
VDD Power supply for sensors (green wire, green pin pin)
NC,C1,NO Output 1 - rel y cont cts - switch ble, 1A/30VDC m x.
NC,C2,NO Output 2 - rel y cont cts - switch ble, 1A/30VDC m x.
Note: Improper wiring nd short-circuits on bo rd connections m y le d to
perm nent d m ge of the product, which is not covered by the
m nuf cturer's w rr nty

©2016 IQtronic technologies Europe, s.r.o.
P ge 6 of 22
2.2 Installation dimensions.
2.3 Power supply o the IQTB-TC840
The device c n be powered from wide power supply from 6V to 36VDC thus
with sufficient toler nce for running on b ttery power. But must not exceed
40VDC. It's lso possible to power it vi p ssive POE directly from the
Ethernet connector.
The power scheme using the p ssive POE device
After connecting to volt ge will blink ll LEDs, PWR will be blinking regul rly.
The device is now re dy to use.
Recomendation: The recommended power supply is 12Vdc ±20%. This
device h s not comp tible power input with 48V IEEE 802.3 f PoE, it c n be
used with p ssive POE only
!

©2016 IQtronic technologies Europe, s.r.o.
P ge 7 of 22
3Device con iguration
- Connect the connecting c ble to the computer vi n RJ45 connector to the device.
- Set up the following on PC network c rd, to which the device is connected:
192.168.0.11, m sk 255.255.255.0
-Option lly run IQloc tor.exe pplic tion th t loc tes the device nd it is possible to
ch nge the ddress directly in the device, see. Ch pter 9.
- The def ult IP ddress of the device is 192.168.0.100.
- St rt the Web browser with def ult ip:
- In c se of using n li s NetBIOS n me - IQTB-TC840
3.1 Displaying current values.
The p ge will displ y ll d t ; the current st te of the outputs; both of
temper ture sensors; device temper ture; their extreme v lues; current time
obt ined from the NTP; st tus of ch nge counters of outputs. All these v lues
c n be re d using SNMP protocol version 1.0 or possibly djust the output
rel y. It is lso possible to set sending TRAP p cket in c se of exceeding one or
more of the conditions.
V lues c n be re d nd reset vi SNMP. You c n lso re d the stored v lues
from the d t logger.

©2016 IQtronic technologies Europe, s.r.o.
P ge 8 of 22
Clicking on rect ngles of output st tuses - red/green color indic tes the st tus
of outputs - on / off, it is possible to ch nge this st te to the opposite. With
e ch ch nge, the counter will incre se by one.
By clicking on the inputs rect ngle we displ y the temper ture history - there
h ve v lues in the gr ph the s me course nd they only serves s n ex mple
of d t present tion.
The gr phs h ve d ily, weekly, monthly nd ye rly interv l.
Note: All v lues is shown with period 500ms. The refresh of m in p ge is not
required. Press output rect ngle re for ch nge rel y outputs.

©2016 IQtronic technologies Europe, s.r.o.
P ge 9 of 22
To proper displ y the gr ph, you must h ve Fl sh pl yer inst lled, which is
not, for s fety re sons, st nd rdly en bled in your browser.
If we w nt to h ve det iled overview of the history, use the d t filter on the
bottom left.
Where you c n djust everything you need to displ y d t , their cl ssific tion,
or obt ining of st tistic l v ri bles. VIn the gr ph, there re lso minimum nd
m ximum v lues m rked by bl ck tri ngle. Visu liz tion of d t l rger
interv l, such s the se son h s resulted in sm ller displ y selection of
v lues without ver ging. The most accurate representation o ers daily
interval, in which is shown in the graph, each value that is obtained by
reading the values o the sensor every 3 minutes.
Checkbox FILL will displ y gr ph with fillings from its current v lue to the
xis X.
Note: Correct NTP settings is required for norm l function lity of d t logger.
All d t logger d t s is possible to re d from history by SNMP lso.

©2016 IQtronic technologies Europe, s.r.o.
P ge 10 of 22
It is also possible to set by a filter minimums and maximums for displaying the
graph. If offsets are set to 0, then they will not apply and the graph is
displayed whole from min to max.
3.1 Setting device parameters