Power Factor Controller
Prophi®12R / 12RS
Manual
Manual
Version 4.0 - E
SupplyVoltage: 110-440V
Version 4.0 E, 11/2019
cos 0.987 IND
1 2 3 4 5 6 7 8 9 10 11 12
j
AUTO MODE
------------------
Power Factor Controller
Prophi12R/ Prophi 12RS

Prophi®12R / 12 RS
2
!
CAUTIONS:
1. High voltage !
2. The device may only be used indoor !
3. Make sure that the discharge time set in controller
matches capacitor discharge time !
UNDERCOMPENSATED
------------------
Q-Diff= 82kvar
1 2 3 4 5 6 7 8 9
HARMONICS [V]
23456789
10 11 12 13 14 15 16 17
2.0%
1.0%
0%
AUTO-MODE
ERROR MESSAGE
DISPLAY-MODE
BARGRAPH-MODE
10 11 12 A M
AUTO MODE
------------------
cos 0.987 IND
1 2 3 4 5 6 7 8 9 10 11 12 A M
j
------------------
phi
cos
Q
dif
0.960
19.5
kvar
IND
1 2 3 4 5 6 7 8 9
10 11 12 A M
------------------

Prophi®12R / 12 RS
3
CONTENTS
Section 1 General / type series and accessories 3
Section 2 Installation of the controller / connection diagram 5
2.1 Current measurement 6
2.2 Programming of phase-correction
2.3 Error messages: Alarm- / Message relay 7
Section 3 Operating modes 7
Section 4 Automatic operation / display functions 8
Section 5 Programming
5.1 Automatic initialization 9
5.2 Manual programming 10
5.3 Programming lock 13
Section 6 Manual operation 1&2 / Programming of fixed stages 14
Section 7 Service menu, Test run 15
Section 8 Expert mode 16
8.1 Expert mode 1
8.2 Expert mode 2 18
Section 9 Control principle 19
Section 10 Display editor 20
Section 11 Initial operation 20
Section 12 Maintenance and warranty 20
Section 13 Interface 21
Annex: Annex 1 Troubleshouting 23
Annex 2 Technical data 24
Annex 3 Table of control series 25
Description of control-series editor
Annex 4 Default settings 26
Application Mixed dynamic compensation 28
Cascading of controllers
Application Real current measurement 29
Alarm and status notifications 30
Handling-diagram / short reference 31
Application Coupling of compensation systems 27
- 2 -

Prophi®12R / 12 RS
4
Section1 General
The power factor controller Prophi 12 (single phase) enlarges the product range of power
factor control devices by a useful combination of the well known features with the
advantages of a better visualization.
The big graphic display enables a user-friendly programming and gives further benefits
such as larger display in the Display-mode and the display of various parameters in
bargraph-mode.
With the additional “ESCAPE”-button a backward navigation in all menus is possible.
The “HELP”-button allows an interactive help in the particular menu item
(German/English).
The controller is characterized by its user friendly operating interface via menu driven
plain text display. The display of several grid parameters, the storage of different values
as well as the possibility of test run allow a simple error analysis and system monitoring.
If required, an automatic initialization is possible which reduces the start-up operation to
a minimum.
R 12 respectively 13 switching outputs
RExtended supply-voltage range 110...440V
R20 pre-programmed control series with self optimized intelligent control behavior
RControl series editor for individual control series
ROperation and display completely menu-driven
RIlluminated graphic display 128 x 64 dots
R4 quadrant operation
RAutomatic initialization possible
RDisplay of several grid parameters also in large letters
RDisplay of harmonics of voltage and current, also as bar diagram
RDisplay and monitoring of temperature
RMonitoring of the particular capacitor output
RStorage of maximum values of grid parameters as well as switching operations
and switch-in times of particular capacitor contactors
RManual/automatic operation
RProgramming of fixed steps or skipping of single outputs possible
RZero voltage switch off
RError display of different states and alarm output (relay)
RError storage
RTest run of the system with error analysis
RPanel-mounted instrument 144 x 144 x 53 mm
RFirmware update possible
Version with interface only:
Radditional external input (function programmable), e.g. for 2nd parameter set
Radditional freely programmable alarm relay, e.g. for fan, status notification
Rserial interface RS485, for controller coupling, integration into networks
Rvisualization, programming and data processing via PC by enclosed software
RParameterization of the controller via PC
RUsage as system interface
RUsage with accessory MMI6000/MMI7000 for real current or remote measuring
RConnection of system accessory (e.g. datalogger)
- 3 -

Prophi®12R / 12 RS
5
The controller is supplied as standard for an operating voltage of 110...440 VAC (+-10%),
a measuring voltage of 30...440 V~ (L-N) resp. 50...760V~(L-L) and a measuring current
of 5A or 1A. A voltage converter is required for different operating voltages.
Caution!
Voltages which exceed the specified voltage range can damage the
device !
- 4 -
!
Operating mode:
- Automatic
- Program.
- Manual oper.
- Service
- Expert Mode
- Osci - Mode
- Display Editor
ENTER/ OK
Confirmation
storage of
values
Increase
selected
parameter
HELP
opens
Help pages
Reduce
selected
parameter
Escape
previous
page/value
in the display
Front view
Rear view
H
H
E
E
L
L
P
P
E
E
S
S
C
C
Alarm relay
Power Factor Controller
1 2
EXT. IN-/OUTPUT
ON INTERFACE RS 485
SERVICE
Gnd B A PE
ext. Input
110...230V
message-
relay
terminating-
resistor
capacitor contactors 1 - 6 capacitor contactors 7 - 12
P1 P21 72 83 94 105 116 12
MADE IN GERMANY
RJ45
Art.no.:
Ser.no.:
50 - 760 V~ (L-L)
Meas.voltage: 30 - 440 V~ (L-N)
Supply volt.: 110...440VAC 50/60Hz
L N L1 N k l
(L3) (L2)
a b
supply volt. meas.voltage meas.current

Prophi®12R / 12 RS
6
Section 2 Installation and connection of the controller
The device is designed to be incorporated into the front panel of a PFC-cabinet. It requires
a switchboard section of 138 x 138 mm to DIN 43700/ IEC 61554. The controller is
inserted from the front and is attached by means of the appended clamps. The
controller may be inserted only by qualified technicians and must be operated in
accordance with the specified safety regulations.
Before the device is connected up, all leads and cables must be checked to ensure that no
current is flowing through them and the current converter must be short-circuited. Care
should be taken to ensure that the measuring voltage and current are in the correct phase
2
position. The measuring-current circuit must be wired with copper leads of 2.5mm . The
connection should be set up as shown below. The specified safety regulations must be
observed.
The measuring voltage may lie in the range from 30...440 V~ (L-N) resp. 50..760V~ (L-L)
(programming of phase correction needed)
The operating voltage is 110...440 VAC +/- 10%.
The coil voltage for the capacitor contactors and the measuring voltage
must be drawn from the same phase conductor, as only the measuring
voltage is monitored. (Protection against direct reconnection of the
capacitor contactors in the event of momentary single-phase power
failure)
Connection plan
- 5 -
L1 ( R)
L2 ( S)
L3 ( T)
N
meas.current
Im ( 5A/1A)
1. capacitor
branc
h
supply
voltage
Vb
meas.
voltage
Vm k l
P1 P 2
1 2 3 4 5 6 7 8 9 10 11 12
capacitor
co ntactors 1-6
alarm
relay
ca pacitor
co ntactor s 7-12
power factor
controller
T 6,3 A
T 2A
T 2A
PE
K1
a b
Ub Um Im
(L) (N) L1 N k l
(L3) (L2)
Power feed Load side
!

Prophi®12R / 12 RS
7
2.1 Current measurement
When installing the current converter, care should be taken to ensure that the load
current and capacitor-current flows through it. The outputs of the compensation network
must be installed behind the current converter (in the direction of current flow). If the
device is connected up via sum-current converters, the overall conversion ratio is
entered.
2.2 Programming of phase-correction - e.g. connection directly L-L (400V)
Adjustment of phase-correction between voltage and current in the meas. system is done
in expert mode 1
Example :
Meas.current: L1
Meas. voltage: L3-L2
Phase U/I [ 90°]
- 6 -
L1 ( R)
L2 ( S)
L3 ( T)
N
Me as.cu rrent
su pply-
voltage
Vb
me as. -
vo ltage
L2 -L3 k l
T 2A
T 2A
PE
Ub Um Im
(L) (N) L3 L2 k l
using meas. current meas. voltage phase-angle
Preset: L1 L1 - N 0°
L1 L1 - L2 30°
L1 (k<->l) L2 - N 60°
L1 L3 - L2 90°
L1 L3 - N 120°
L1 L3 - L1 150°
L1 (k<->l) L1 - N 180°
L1 (k<->l) L1 - L2 210°
L1 L2 - N 240°
L1 L2 - L3 270°
L1 (k<->l) L3 - N 300°
L1 (k<->l) L3 - L1 330°
kK k K
lL l L
Feed 1 Feed 2
K L K L
Measurement via sum current converter
Current
measurement
k l
k l
Example:
C.converter 1: 1000/5A
C.converter 2: 1000/5A
Sum-current converter: 5A+5A/5A
C.converter ratio is: 2000/5A

Prophi®12R / 12 RS
8
Display-Mode Harmonics as bar-diagram
Active capacitor
branches
Control direction
(here connected-in)
Supply display
(for 4-quadrant
operation)
The control direction is symbolized
by a closed arrow
The connecting-in arrow is always
located after the maximum possible
number of stages (end stop)
An open arrow indicates that the
required blocking time (discharge
time) is running before an impending
switching step
A double arrow symbolizes fast
switching of several branches
Connecting-in
Connecting-out
By pressing the cursor buttons,
the display of capacitor stages can be changed:
AUTO MODE
------------------
cos 0.987 IND
1 2 3 4 5 6 7 8 9 10 11 12
j
------------------
------------------
U HARMONICS [V]
I
Q
23456789
10 11 12 13 14 15 16 17
223.0 V
268 A
107
kvar
2.0%
1.0%
0%
By activating the ENTER-button the selected display can be stored as standard main display.
2.3 Error-Messages: Alarmrelay / Message-relay*
The PROPHI 12R is equipped with an alarm relay. Version /RS features an additional message relay.
The functions may be programmed as follows:
Alarm relay: Setting under Message relay: Setting under Remark
Programming: 14 Alarm relay INTERFACE: 1 MESSAGE RELAY
0 13th step Alarm relay=13.th step
1 OFF OFF
2 ERROR ERROR ERROR-summary report
3 ERROR inverse ERROR inverse List of errors see page 12
4 FAN FAN ERROR:relay closed in case of error
5 Supply Supply ERROR inverse (factory setting):
6 Undercurrent Undercurrent contact open in case of error
7 Harmonics Harmonics
8 Overcompensated Overcompensated
9 Undercompensated Undercompensated
10 Warning switch. oper. Warning switch. oper.
11 Modbus-Error Modbus-Error
12 \ Modbus-Error \ Modbus-Error
13 MMI-Error MMI-Error
14 C-defect C-defect
15 Fixed step OUT ext. input triggers fixed step
Adjustment and masking of all ERRORS is possible in the ExpertMode 2. The adjustment is valid for
both relays.
Section 3: Operating modes
When the operating voltage is switched on, the device briefly displays its designation and software
version, then changes to its normal operating status (automatic operation).
further messages
compare last cover
page !

Prophi®12R / 12 RS
9
Section 4 Automatic operation - display of network parameter
The device is set to automatic operation as standard (not AUTO-INIT). Capacitor stages
are then automatically connected in or out in order to reach the target power factor. This
happens if the required reactive power is approx. 1/3 higher than the value of the
smallest capacitor step.
In automatic operation, various network parameters can be displayed by repeatedly
pressing the "ENTER” key:
Action Display
ENTER 1 LINE VOLTAGE in V /%
ENTER 2 APPARENT CURRENT in A /%
ENTER 3 REACTIVE POWER in kvar /%
ENTER 4 ACTIVE POWER in kW /%
ENTER 5 APPARENT POWER in kVA /%
ENTER 6 DIFF. kVAR TO TARGET COS
ENTER 7 FREQUENCY in Hz /min / max
ENTER 8 TEMPERATURE in °C / °F
ENTER 9 HARMONICS V / %, I / %
Selection via arrow-keys
ENTER 10 HARMONICS THD-V/%, THD-I/%
11 Compensation power in kvar
ENTER 12 ENERGY
(kWh, kvarh, consumption, delivery)
reset in: service / max.value reset
ENTER Software version
ENTER Return to: 1
The power value specifies the total power (3-phase) assuming symmetrical load. If no
key is pressed for 120 seconds, the display automatically returns to the operating status!
Under “13 Date-Time” the date format 12h/24h setting can be changed by the arrow
buttons (only version /RS).
ENTER
ENTER 13 DATE - TIME
Repeated pressing of the "Operating Mode” key takes the user to the various menus:
- 8 -
Auto operation Programming
Expert Mode 2
Manual operat.
Display-Editor back to 1
Service
Expert Mode 1
AUTO-MODE
------------------
AUTO-MODE
------------------
3 REACTIVE POWER
118 kvar
10 HARMONICS THD rel.
V 1.7% I 0.8%
INTERFACE

Prophi®12R / 12 RS
10
5.1. Automatic initialization
available only, if in ExpertMode 2: „2 Auto-Init = YES“
With the automatic initialization the PROPHI 12 will automatically recognize the
parameters of the PFC-system. It also serves as plausibility check and storage of these
parameters - the user only has to make very little or even no adjustments.
Start of the initialization process is done from the menu point “PROGRAMMING” by
pressing the button “ ”
AUTO-INIT [YES] to be confirmed with pressing the ENTER button.
Now either the values of the current transformer OR the value of the smallest step of the
system have to be keyed in. The input of one of these values is absolutely mandatory.
After input (confirm with ENTER) the automatic test run of the controller is executed.
é
3 test-runs will be performed during which all stages are being switched on and off. All
necessary parameters are collected, evaluated and stored. Under certain circumstances
3 additional test-runs may be required for a proper initialization.
After successful finalization of AUTO-INIT the device will switch to normal operation.
In case of recognition of any discrepancies (plausibility) or of inaccurate connection, the
detected error will be displayed in plain text after finalization of AUTO-INIT and can be
eliminated. (see possible error messages at the end of the manual). AUTO-INIT may be
repeated then.
- 9 -
AUTO-INIT
------------------ AUTO-INIT
------------------ AUTO-INIT
------------------
1 CURRENT TRANSF.
[ UNKNOWN ]
4 POWER 1.STAGE
[25].00 kvar
START TEST
E
E
S
S
C
C
Section 5: Programming
Pressing the key once takes the user into the PROGRAMMING mode.
[ ].
The values are changed by pressing the keys:
Subsequent pressing of the key stores the value and takes the user to the next
parameter.
“ESCAPE” allows return to previous menu item.
To quit programming mode in any step, press the key:
The display always shows the parameter and the set value. Values that can be edited are
generally put into square brackets