Table 3: Lug details
Option Input voltage Frequency Line side lugs
BBL per phase Wire range
Grounding lug
wire range,
quantity
Circuit breaker 460 V 60 Hz 3 4/0 - 500 MCM #6-350, 3 bbl
8. Input power wiring conductors must have a current rating equal to or greater than the
minimum circuit ampacity for the chiller rating. See Note 12. The diameter of the wire is
determined by NEC, and the lug wire range of the circuit breaker is as noted in Table .
9. The OptiView™ Control Center has automatic control of the chilled water pump. The chilled
water pump motor starter (5M) holding coil is supplied for 115 V, 50 Hz or 60 Hz. The power
requirements for the water pump starter (5M) must be a maximum of 2 A holding and 10 A
inrush. If power requirements exceed this value, furnish the coil for line voltage, and control
relay with 115 V coil. See Note 17.
- The pump operates during chiller start up, chiller operation, shutdowns, and when in
freeze protection mode.
- For manual chilled water pump control, in applications where ambient conditions
can lead to below-freezing temperatures, do not use the manual chilled liquid pump
operation unless there is sufficient logic to operate the pump when the ambient
temperature is ≤ 36°F (2.2°C). If manual pump control can be guaranteed at operation
at ≤ 36°F (2.2°C), then connect a manual start/stop switch as shown in Form 160.88-
PW2 Field Connections Diagram for the 115 VAC coils only.
Table 4: Conduit details
Input voltage Frequency Chiller motor code Maximum number of
conduits
460 V, 60 Hz 60 Hz M2 3 (3 in.)
10. Wire #14 AWG copper for one-way distance of less than 175 ft (53.34 m). Wire #12 AWG
copper for one-way distance of more than 175 ft (53.34 m), but less than 300 ft (91.44 m).
11. Refer to the wiring diagram for YORK Control Center and Field Control Modifications, Form
160.88-PW2.
12. The branch circuit overcurrent protection device for the YVAM chiller must be a time delay
type. It must have a rating that is the standard fuse or circuit breaker size that is required to
protect the field supply wiring conductors, as outlined by the NEC.
13. The YVAM input power supply wiring ampacity is calculated using the UL60335-2-40,
101.DVB.2.1
14. The YVAM chiller is equipped with a UL-listed circuit breaker. Fast-acting semiconductor fuses,
down-stream of the circuit breaker, provide additional protection to the chiller. Ground fault
is employed on the circuit breaker and the drive controls.
15. The minimum value of line impedance is determined by the chiller's power when it is
provided from a transformer with a kVA rating equal to five times the rated power of the
chiller. The transformer is specified to have 3% impedance. The supply voltage requirements
at the auxiliary panel input terminals are defined in the following table.
Table 5: Voltage ranges
Input voltage Frequency Voltage range Minimum applied voltage at
start-up
460 V Hz 60Hz 414 V to 508 V 391 V
Field Connections Diagram for Model YVAM Chiller with M2 Compressor6