KBR multimax 3D6 Manuale utente

EDEBDA0210-3313-1_EN
User manual
Technical parameters
Your partner for
network analysis
Load management system
3D6
multimax
System IEnglish

© KBR Kompensationsanlagenbau GmbH
Subject to typesetting and printing errors
or technical changes.
2
EDEBDA0210-3313-1_EN

V3.00 3
EDEBDA0210-3313-1_EN
KBR multimax 3D6
Table of contents
1 Introduction......................................... 5
1.1 User manual .......................................... 5
1.2 Intended use......................................... 5
1.3 Explanation of
safety relevant symbols .................... 6
1.4 Safety notes........................................... 7
1.5 Product liability.................................... 8
1.6 Disposal .................................................. 8
2 Range of functions ............................. 9
2.1 Monitoring of the energy
consumption ........................................ 9
2.2 Energy optimization system with
trend calculation ................................. 9
2.3 Switching the consumers using
compensation power ........................ 9
2.4 Switch-o of consumers via relay
outputs..................................................10
2.5 Decentralization
through substations.........................10
2.6 Status recording via message
modules................................................10
2.7 Maximum prewarning contact ....10
2.8 Power measurement
by means of energy pulses
of the energy supplier.....................11
2.9 Counter pulse monitoring .............11
2.10 Measuring period synchronization
by energy supplier pulse................11
2.11 3 target values for consumption
limits ......................................................11
2.12 Error message functions.................12
2.13 Long term memory ..........................12
3 Device overview ................................13
4 Installation...........................................14
4.1 Device memory,
battery-buered................................14
4.1.1 Inserting or replacing backup
battery:..................................................14
4.2 Device installation ............................15
4.3 Connections........................................15
5 Control and display panel..............17
5.0 Description of buttons and
displays, factory settings, setting
ranges....................................................17
6 Overview of system parameters..24
7 Description of parameters.............25
7.0.1 General parameters..........................25
8 Line parameters.................................31
8.1 Counter inputs ...................................38
8.2 Module management......................39
8.3 I/O parameters ...................................39
8.4 Clock time / date ...............................40
8.5 Bus parameters ..................................41
8.6 Display parameters...........................41
8.7 Alarm parameters .............................43
8.8 Password / reset.................................43
9 Description of the display..............45
9.1 Pactual...................................................45
9.2 Potential ...............................................46
9.3 Line data...............................................46
9.4 I/O status ..............................................47
9.5 Ptarg trackes .......................................47
9.6 Counter values ...................................48
9.7 Current error messages...................48
10 Technical data multimax 3D6 .......49
10.1 General technical data
of additional modules .....................49
10.2 Technical data of the multimax 3D6
basic module ......................................50

KBR multimax 3D6
V3.00
EDEBDA0210-3313-1_EN
4
Table of contents
10.2.1 Operating and display elements 50
10.2.2 Device memory..................................50
10.2.3 Power supply ......................................51
10.2.4 Hardware inputs...............................51
10.2.5 Electrical connection .......................51
10.2.6 Hardware outputs.............................52
10.2.7 Mechanical data and dimensioned
drawing of the basic module........52
10.2.8 Environmental conditions /
electrical safety ..................................53
10.2.9 Mechanical data and
dimensioned drawing of the
multimax 3F96-DS display.............54
10.2.10 Serial interface ...................................55
10.2.11 Protective measures - overvoltage
and lightning protection................55
11 Connection of
additional modules ..........................56
11.1
Functional description relay output
module multisio 1D4-4RO ISO ......... 56
11.2 Relay output module
connection chart...............................56
11.3 Relay output module LED display57
11.4 Function of scan button .................57
11.5 Function of the DIP switches ........58
11.6 DIP switch settings ...........................59
11.7 Functional description digital
input module multisio 2D2-4DI...59
11.8 Digital input connection chart.....60
11.9 Digital input module LED display60
11.10 Function of scan button .................61
11.11 Function of the DIP switches ........61
11.11 DIP switch settings ...........................62
Settings ................................................................64
Output lines energy control system..........70
Output lines energy control system..........71

V3.00
KBR multimax 3D6
EDEBDA0210-3313-1_EN
5
Introduction
1 Introduction
Thank you for choosing this KBR quality product.
In order to familiarize yourself with the operation and conguration of the
device, we recommend that you read this manual thoroughly, so that you are
able to make use of the entire range of functions of this high-quality product.
The individual chapters serve to explain the technical details of the device and
show how to avoid damage by means of proper installation and start-up.
1.1 User manual
This user manual is included in the scope of delivery of the device and must be
accessible for the user at all times (e.g. in the switchgear cabinet). Even when
the device is resold to third parties, the manual remains part of the device.
Although we used the utmost care in assembling this user manual, we would
like to thank you in advance for notifying us about any errors or ambiguous
descriptions you might notice.
1.2 Intended use
This device is intended for the optimization of energy consumption and to
avoid expensive load peaks.
The system assists you in monitoring the energy consumption of your devices,
helps you to make optimum use of your tari and permanently lower your
energy costs.
However, its use cannot replace the careful planning of your system.
Furthermore, it is absolutely necessary that you take the time to carefully
congure your system in the device and plan how you want to switch-o your
consumers before you put it into operation.

KBR multimax 3D6
V3.00
EDEBDA0210-3313-1_EN
6
1.3 Explanation of safety relevant symbols
This user manual contains notes that must be observed for your personal safety
and to avoid damage to equipment. These notes are identied by a warning
sign or information symbol, depending on the degree of hazard they represent.
"Warning" means that death, major injuries or damage may occur in case the
appropriate safety measures are not taken.
"Caution" means that minor injuries or damage may occur in case the
appropriate safety measures are not taken.
"Note" is an important information on the product, operation or the respective
part of the user manual to which special reference is made.
Disclaimer
The content of this user manual has been carefully reviewed in terms of
the hardware and software described. Certain deviations, however, cannot
be excluded, and the manufacturer is not liable for complete conformity.
The specications made in this user manual are checked on a regular basis,
necessary corrections will be included in the next revision.
Introduction
Warning
Caution
Note

V3.00
KBR multimax 3D6
EDEBDA0210-3313-1_EN
7
Introduction
1.4 Safety notes
In order to prevent operating errors, operation of this device is kept as simple as
possible. This way, you will be able to quickly start working with the device.
In your own interest, however, you should read the following safety notes
carefully. During assembly, the applicable DIN / VDE regulations must be
observed!
Power supply connection, setup and operation of the device must only be
performed by qualied personnel. Qualied personnel in accordance with the
safety notes in this user manual are persons authorized to setup, ground and
mark devices, systems and circuits in accordance with all applicable standards
and regulations.
To avoid the hazard of re and electrical shock, the device must not be subject
to rain or other humidity!
Before the device is connected to its power supply, you will have to check
whether the local power supply conditions comply with the specications on
the manufacturer’s label.
A wrong connection may destroy the device!
When connecting the device, observe the connection chart (see chapter
“Connection chart”) and make sure that no voltage is applied to the connection
lines. Only use proper wiring material and watch the correct polarity when
wiring!
In order to ensure proper and safe operation of the product, it must be trans-
ported, stored, installed and mounted in accordance with the specications
and operated and maintained carefully.
A device showing visible damage must by all means be considered as unt for
operation and must be disconnected from the power supply!
Error detection, repairs and maintenance work may only be carried out in our
facilities or after contacting our service team. Every warranty obligation of the
manufacturer expires if the device is opened without written consent from our
service team. Proper operation can no longer be guaranteed!
Opening the device may expose parts under voltage. Capacitors in the device
may still be loaded, even if the device has been disconnected from all voltage
sources. It is generally not allowed to operate an open device!
Caution

KBR multimax 3D6
V3.00
EDEBDA0210-3313-1_EN
8
Introduction
In systems subject to hazard of lightning, lightning protection must be
provided for all input and output lines!
1.5 Product liability
You have acquired a high quality product. In its manufacture, only components
of the highest reliability and quality were used.
Each device is subject to long-term testing before it is delivered.
Regarding product liability, we refer to our general terms and conditions for
electronic equipment, which you can nd at www.kbr.de.
The warranted properties of the device apply only if it is operated in accordance
with its intended use!
1.6 Disposal
Defective, outdated or no longer used devices must be properly disposed of.
At your request, we will be pleased to dispose of the devices for you.

V3.00
KBR multimax 3D6
EDEBDA0210-3313-1_EN
9
2 Range of functions
The energy control system multimax 3D6 can make a considerable contri-
bution to reducing the energy costs in your company.
2.1 Monitoring of the energy consumption
The peak power is an important cost factor for special tari customers.
By means of intelligent monitoring of the energy consumption, multimax 3D6
provides optimum distribution of the available power and helps to prevent
expensive power peaks.
2.2 Energy optimization system with trend calculation
multimax 3D6 acts as optimization calculator, taking into account the assumed
further energy consumption within the measurement period. Careful adjust-
ments are made to the energy consumption to avoid unnecessary shut-downs
in consideration of the device properties:
2.3 Switching the consumers using compensation power
Negative compensation power causes a switch-o, positive compen-
sation power triggers hookups. Compensation power is the result from the
comparison of the trend power with the target power taking into account the
available consumer power.
Range of functions

KBR multimax 3D6
V3.00
EDEBDA0210-3313-1_EN
10
Range of functions
2.4 Switch-o of consumers via relay outputs
The basic module disposes of 5 non-oating relay contacts to switch o the
consumers involved in the optimization.
Using additional 4-stage components, up to 32 switching outputs can be
realized (see "Connection of additional modules").
NO or NC contact functions can be programmed to switch o the consumers.
2.5 Decentralization through substations
The multimax energy control system with its central component can be
expanded by means of substations. Communication is carried out via a bus line.
2.6 Status recording via message modules
By determining the state of the devices that can be optimized, the optimization
action can be controlled. A message input can be associated to every output.
The multimax 3 load management system receives important information
about the individual consumers via the message inputs. It can be determined
whether
the consumer has been identied as requiring optimization by the input
the consumer has been identied as inactive
There are additional possibilities:
External control of the consumer (permanently on (manual_on)
or permanently o (manual_o))
2.7 Maximum prewarning contact
On the device side, a maximum prewarning contact is available, which can be
connected to any relay output.
Signaling for manual interventions in production processes.
Starting a generator (utility station).
Default as NO contact (if active).
Indice
Altri manuali KBR Controllori

KBR
KBR Multicomp 2F144-NC-1V1C06RO Istruzioni operative

KBR
KBR F144-3PH Manuale utente

KBR
KBR F144-MS-1V1C6-12DO-3 Manuale utente

KBR
KBR multicomp F144-NC-1V1C6DO6RO-2 Manuale per l'uso e la cura

KBR
KBR multicomp F144-MS-1V1C1TI6DO6RO-3 Manuale di servizio

KBR
KBR multicomp D6 Series Manuale di istruzioni

KBR
KBR F144-3PH Manuale utente

KBR
KBR multicomp 4D6-ESBSDS-1V1C6RO Istruzioni operative

KBR
KBR F144-MS-1V1C1TI6DO-3 Manuale per l'uso e la cura

KBR
KBR multicomp F144-MS-1V1C1TI6RO6DO-3 Manuale utente