Koso REXA Electraulic Xpac Manuale utente

IOM 05/09

Xpac Installation Manual -- Version 5.1 (5/08)
REXA
Electraulic Actuators & Drives
2

Xpac Installation Manual -- Version 5.1 (5/08)
REXA
Electraulic Actuators & Drives i
Contents:
Safety Considerations iv
INTRODUCTION 1
1 OVERVIEW 3
1.1 Actuator 4
1.2 Control Enclosure 5
1.3 Menu Calibration 5
1.4 Operational Summary 5
1.5 Optional Equipment 7
1.5.1 Position Transmitters 7
1.5.2 Manual Override 7
1.5.3 Limit Switches 7
1.5.4 Alarm Relay 7
1.5.5 Surge Control 7
1.5.6 Pulse Input 8
1.5.7 Auxiliary Controls - External 8
1.5.8 Auxiliary Controls - Remote Manual 8
1.5.9 Spring Failure 8
1.5.10 Accumulator Failure 8
1.5.11 Stem Boot 8
1.5.12 Split Clamps 9
2 DELIVERY 10
2.1 Receipt 10
2.2 Storage 10
2.3 Unpacking 10
3 OIL
11
3.1 Level Check 11
3.2 Filling 11
3.3 Oil Weeping 12
4 MECHANICAL INSTALLATION 13
4.1 R Series (Rotary) 13
4.1.1 Fail In Place Installation 13
4.1.2 Universal Rotary Spring Failure 13
4.1.3 Stroke and Adjust Option 14
4.2 L Series (Linear) 14
4.2.1 Elastic Coupling 14
4.2.2 Fail In Place Installation 16
4.2.3 Linear Spring Failure 16
4.3 D Series (Drive) 17
4.3.1 Mounting 17
4.3.2 Drive Arm 18
4.4 Control Enclosure 19
5 ELECTRICAL INSTALLATION
20
5.1 Motor Power Cable 20
5.1.1 Enclosure Termination 21
5.1.2 Actuator Termination 21
5.2 Feedback Cable 22
5.2.1 Enclosure Termination 22
5.2.2 Actuator Termination 22
5.3 User Connections 24
!

Xpac Installation Manual -- Version 5.1 (5/08)
REXA
Electraulic Actuators & Drives
ii
5.3.1 Actuator Power 24
5.3.2 Control Signals 25
6 OPERATION 29
6.1 Auto Mode 29
6.2 LOCAL Mode 30
6.3 SEtUP Mode 31
6.3.1 Cal - Calibration Sub-Menu 32
6.3.2 ACC - Acceleration Sub-Menu 35
6.3.3 CtL - Control Sub-Menu 36
7 START-UP CONSIDERATIONS 38
7.1 Wiring 38
7.1.1 Module Cable 38
7.1.2 Feedback Cable 38
7.1.3 Electrical Power 38
7.2 Electrical Noise 39
7.2.1 Provide A Good Earth Ground 39
7.2.2 Options If Actuator Is Still Noisy 39
7.2.3 Noise Pick-up On Surrounding Equipment 40
7.3 Mechanical Restriction/ Binding 40
7.3.1 Lateral Misalignment 40
7.3.2 Longitudinal Misalignment 41
7.4 Tuning 41
7.5 Output 42
7.5.1 Fail In Place Actuators 43
7.5.2 Spring Failure Actuators 43
7.6 Temperature 43
8 ERROR CODES 45
8.1 Loss of Feedback, E-Fb 45
8.2 Stall, E-St 45
8.3 No Control Signal, E-CS 45
8.4 Bumpless Transfer, E-bt 46
8.5 Driver Fault, E-dF 46
8.6 Incorrect Direction, E-dr 46
8.7 Triple Power Supply, E-PS 46
ADDENDUM: CYLINDER END STOPS 47
Figure
1.A Xpac 3
1.B Linear Actuator Assembly 4
1.C Hydraulic Schematic 6
4.A Universal Spring Alignment 14
4.B Stroke Adjustment 14
4.C Drive Base Bolting 18
4.D Drive Arm 18
4.E Ambient Temperature 19
5.A Control Enclosure Connections (B&C Power Modules) 26
5.B Control Enclosure Connections (2C Power Modules) 27
5.C Actuator Connections 28
5.D Module Connection 21
6.3A Gain 31
6.3B B/C Initial Parameter Settings 35
7.5A Typical Temperature Versus Speed 42

Xpac Installation Manual -- Version 5.1 (5/08)
REXA
Electraulic Actuators & Drives iii
APPENDICES
A. Drawings
B. Quick Reference
C. Optional Features
D. Canadian Standards Association
(CSA) Approved for Hazardous Area
Class I, Division 2, Groups B, C & D
E91001 Relay Option Board, E91002 Position Transmitter
Class I, Division 1, Groups B, C & D
E. Mechanical Limit Switches
F. Seat Loading Cylinder
G. Accumulator Failure
H. Booster Pump Configuration
P. Pulse Operating System
R. Redundant Construction
S. Surge Control Option
T. Screw Terminals
X. D Size Power Module
Figure *
C.1 Non-Alarming Loop p. 2
C.1 Alarming Loop p. 2
C.A Flow Characteristics p. 11
F.A SLC Feedback Board p. 2
P Pulse Auxiliary Board p. 1
R.1 Single Enclosure - Electronics p. 4
R.2 Interconnection Wiring Diagram p. 5
T.1 Screw Terminal Junction Enclosure p. 1
T.2 Wiring Connections p. 2
X.1 Speed Profile p. 8
X.2 Recommended Initial Parameter Settings p. 8
X.3 Effect of Parameter on Performance p. 8
Diagrams
½D Size Control Enclosure Assembly
½D Size Wiring Diagram
½D and D Size Control Enclosure—NEMA 4X Steel
D Size Control Enclosure Assembly
D Size Wiring Diagram
2D Control Enclosure Assembly—NEMA 4X Steel
2D Size Wiring Diagram
2D Size Control Enclosure
Junction Box; ½D, D and 2D size—actuator end
* Please note that the page numbers for these figures refer to the individual
Appendix indicated by the first letter.

Xpac Installation Manual -- Version 5.1 (5/08)
REXA
Electraulic Actuators & Drives
iv
SAFETY CONSIDERATIONS
SHOCK HAZARD:
Hazardous voltage levels are present in the actuator. Only qualified service
and installation personnel should install or adjust this device.
ALIGNMENT:
Insure that the actuator shaft is in line with the valve plug stem. Misalign-
ment could damage the actuator and driven device or cause injury to
installation personnel.
AVOID ACCIDENTAL STARTING:
When installing the actuator, insure that line power to the unit is shut off.
When power is applied, the actuator may immediately respond to the control
signal. Inadvertent motion could damage the actuator and driven device
or cause injury to installation personnel.
IMPORTANT
:
When machining the control enclosure, thoroughly clean any metal chips
or residue from the enclosure before applying power.
HYDRAULIC OIL:
The standard oil used in REXA actuators or drives is Castrol Syntec SAE
5W-50 motor oil. Oil for special applications such as food grade would
be noted on the serial plate. The introduction of other fluids may cause
damage to the unit.
SPRING UNDER TENSION:
REXA actuators, denoted by an E, R or U in the model number, contain a
spring under tension. Failure to properly remove this force before disas-
sembly can cause serious injury to maintenance personnel. Contact REXA
for disassembly instructions.
RELIEVING INTERNAL PRESSURE:
When the electric power is off (fail in place units) or the motor is not turn-
ing, hydraulic pressure remains locked within the cylinder. This internal
pressure must be relieved before disconnecting any hydraulic fitting. Open
the cylinder bypass (3/16” hex) located on the power module for fail in place
units or remove electric power to the solenoid on spring fail units. See
section 3.M2 of the Trouble Shooting and Repair Manual.
!
!
!
!
!
!
!
!

Xpac Installation Manual -- Version 5.1 (5/08)
REXA
Electraulic Actuators & Drives v
ACCUMULATOR FAILURE OPTION:
REXA actuators denoted by an A in the model number contain an accumulator
charged with high-pressure nitrogen. These actuators also have an automatic
recharging cycle for the accumulator. Failure to properly follow installation
instructions may cause serious injury to maintenance personnel and/or dam-
age to equipment.
NPT PLUG AND CONDUIT CONNECTIONS:
During assembly, Loctite 767 compound—or its equivalent—must be used
on threads of all NPT plug and conduit connections to ensure a watertight
seal.
!
!


REXA
Electraulic Actuators & Drives
Xpac Installation Manual -- Version 5.1 (5/08)
1
INTRODUCTION
REXA Xpac actuators and drives are Electraulic (self-contained,
electro-hydraulic) devices. They are controlled by a dedicated micro-
processor located within the control enclosure and operated by a fluid
power system in the power module. Suitable for 100% duty cycle
service, the Xpac is ideal for any automatic control application.
The Xpac product line is offered in three different series. The R
Series are quarter turn actuators designed to operate rotary devices
(ball valves, butterfly valves, directly coupled louvers, etc.). The L
Series are designed for linear applications. The D Series of drives
are derived from the rotary actuator and designed to operate louvers
and dampers.
When ordering spare parts or requesting information on a specific
actuator, please have available the actuator serial number. This is
located on a stainless steel name tag attached to the actuator.
Units supplied to the provisions of Class I, Division 2, Groups B,
C & D or Class I, Division 1, Groups B, C & D require additional
installation procedures to comply with agency approvals. Refer
to Appendix D for details.

Xpac Installation Manual -- Version 5.1 (5/08)
2REXA
Electraulic Actuators & Drives
The model number provides a physical description of the mechanical portion of the actuator. The cyl-
inder size, Power Modules and failure mode are described in this simple system.
Model Number
_ _ _ _ _ – _ _ – _ – _
Spring Fail Option
(Upon Power Loss)
P: None - Lock in Place
U: Universal (Rotary)
E: Extend (Linear)
R: Retract (Linear)
A: Accumulator Failure
R Series - Xpac Rotary
L Series - Xpac Linear
D Series - Xpac Drives
Torque – Rotation
Thrust – Stroke
Series
Power Modules
B: Single B
C: Single C
½D: Single ½D
D: Single D
2D: Two D Manifold
2C: Two C Manifold
2B: Two B Manifold
P9: Booster Pump, 9
Rotary
Drive
L SERIES
Thrust Rated Strokes
(lbs) (in inches)
2,000 –.75, –2, –4 –6, –8, –11
4,000 –.75, –2, –4
5,000 –.75, –2, –4, –6, –8, –11, –16, –22
10,000 –.75, –2, –4, –6, –8, –11, –16, –22
15,000 –.75, –2, –4, –6, –8, –11, –16, –22
20,000 –.75, –2, –4, –6, –8, –11, –16, –22
30,000 –.75, –2, –4, –6, –8, –11, –16, –22
40,000 –.75, –2, –4, –6, –8, –11, –16, –22
50,000 –.75, –2, –4, –6, –8, –11, –16, –22
60,000 –.75, –2, –4, –6, –8, –11, –16, –22
80,000 –.75, –2, –4, –6, –8, –11, –16, –22
120,000 –.75, –2, –4, –6, –8, –11, –16, –22
custom
For Example: L4000-4-C-P
A linear series Xpac with 4000 lbs of thrust and C size Power Module. Lock in position
upon loss of power. Any stroke is adjustable up to 4 inches.
R2500-90-B-U
A rotary series Xpac with 2500 inch-lbs of torque and B size Power Module. Spring failure
upon loss of power. Any rotation is adjustable up to 90 degrees.
R or D SERIES
Torque Rotation
(inch-lbs) (degrees)
600 –90, –120
1,200 –90, –120
2,500 –90, –120
5,000 –90, –120
10,000 –90, –120
20,000 –90, –120
50,000 –90, –120
100,000 –90, –120
200,000 –90, –120
400,000 –90, –120
custom
Linear
Indice
Altri manuali Koso Controllori