User’s Manual
UPS On-Line 1000VA Rack

2
Manual
www.kraun.it
FOREWORD
MANUAL INSTRUCTION
Thanks for purchasing our UPS, it is safe and reliable, so few maintenance is required.
Read this manual carefully and completely. It includes instructions of safety installation and operation. They
will help your UPS obtain the longest life and service. This manual accounts the internal working principle and
the relative protection functions. This manual also contains information about the usage of the equipment.
Please obey the instructions and all the warning stated in the manual or on the machine. Don’t operate the
machine before finishing reading the safety and operation instructions.
Note:
Because of the continuous improvements, our products may differ somewhat from the contents included in
this manual. You can contact local office to get the information when necessary.

3
Manual
www.kraun.it
CONTENT
1. SUMMARY 4
1.1. INTRODUCTION 4
1.2. FUNCTIONS AND CHARACTERISTICS 4
2. SAFETY INSTRUCTION 6
2.1. SAFETY INSTRUCTION 6
2.2. SYMBOLS INDICATION 6
3. PRODUCT INTRODUCTION 7
3.1. THE APPEARANCE OF THE PRODUCT 7
3.2. THE PRINCIPLE OF THE PRODUCT 8
4. INSTALLATION 8
4.1. UNPACKING AND INSPECTION 8
4.2. NOTES 8
4.3. UPS INPUT CONNECTION 9
4.4. UPS OUTPUT CONNECTION 9
4.5. INSTALLATION 10
4.5.1. Plastic base installation 10
4.5.2. cabinet installation bracket assembly 10
4.5.3. tower/rack assembly 11
5. PANEL DISPLAY, OPERATION AND RUNNING 12
5.1. FACEPLATE DISPLAY ILLUMINATION 12
5.1.1. keys function 12
5.1.2. the descriPtion of led disPlay lamP functions 13
5.1.3. lcd disPlay functions 14
5.2. OPERATION 15
5.2.1. start uP oPeration 15
5.2.2. turn off oPeration 15
5.2.3. uPs self-test/mute test oPeration. 16
5.3. PARAMETER SETTING 16
5.3.1. eco mode setting 16
5.3.2. byPass outPut setting 17
5.3.3. outPut voltage setting (oPtional function) 18
5.4. PARAMETERS INQUIRING 19
5.5. RUN MODE 20
5.5.1. byPass mode 20
5.5.2. line mode 21
5.5.3. battery mode 21
5.5.4. eco mode 21
5.5.5. fault mode 22
6. MAINTENANCE 23
6.1. BATTERY MAINTENANCE 23
7. TROUBLESHOOTING AND PERFORMANCE OF PRODUCT 24
7.1. LED INDICATION AND WARNING TABLE 24
7.2. TROUBLESHOOTING 26
7.3. EMC STANDARD/SAFETY STANDARD 27
7.4. PRODUCT PERFORMANCE 27
7.4.1. electric Performance 27
7.5. COMMUNICATION INTERFACE 28
7.5.1. rs232 communication interface 28
7.5.2. rs232 cable sPecifications 29
7.5.3. oPtional communication interface 29

4
Manual
www.kraun.it
1. SUMMARY
1.1. INTRODUCTION
UPS(uninterruptible power supply) is a kind of power supply equipment that provides uninterruptible, high
quality and efficient and reliable AC power to the loads, it also has functions of protection and monitoring.
The UPS plays a very important role in power supply of computer and its network, communication, finance,
electricity, transportation, national defense, college, scientific research institutes and so on.
This 1KVA product is designed as advanced ON-LINE UPS that provide the multiple functions and good per-
formance.
1.2. FUNCTIONS AND CHARACTERISTICS
1. Advanced IGBT modules are used in our UPS. The electronic components we used can work normally for
more than 300,000 hours.
2. Digital control technology with high efficiency and the most reliable controller algorithm design are used
to optimize the output parameters of the machine.
3. Self-diagnose before start. It can find potential problems of the UPS in time to avoid any losses.
4. Double conversion on-line topology which makes the output of the UPS a pure sine wave electricity with
constant frequency and voltage, low noise and no interruption of the main power fluctuation. It provides
more comprehensive and perfect protection for the users’ equipments.
5. No transfer time for the output of the UPS when the main power fails or restores. It meets the high stan-
dard and high request of the precise instruments.
6. The bypass function. When UPS meets a fault, it can transfer to bypass with no interruption to supply
power to loads and provide alarm.
7. Advanced voltage compensation technology. It makes the input voltage range from 115v to 295v which
reduces the battery usage and enhances the adaptive ability against the bad main power variation.
8. The AC input frequency is 50Hz/60Hz. Advanced wide frequency input technology makes the input fre-
quency range wider. When the output frequency is 50Hz, the range of the AC input frequency is 45Hz-
55Hz, When the output frequency is 60Hz, the range of the AC input frequency is 55Hz-65Hz.The UPS has
a good compatibility with generator. It is suitable for different types of single-phase generators.
9. The advanced PFC( power factor correction)technology on the input of the UPS makes the input power
factor more than 0.98. It increases the power efficiency, removes the harmonic noise from UPS to utility,
lowers the UPS operational cost. It’s really an economic environmental protection power supply.
10. Intelligent function without surveillance. When main power is on blackout, the UPS will start battery
mode to supply power to loads.
When battery voltage is low, UPS will protect itself and shut down automatically. When main power
restores, UPS will detect main power to determine whether the voltage and frequency are normal. If
normal, UPS will turn on automatically to supply power to loads; if abnormal, UPS will start charger to
charge the battery. The UPS will not turn on to supply power to loads until the voltage and frequency
of the main power restore normally.
11. Cold start function. When there is no main power, UPS can be started by battery pack. It can meet the us-
ers’ emergency needs. The cold start function is quite strong. UPS can be cold started under the full load
situation.

5
Manual
www.kraun.it
12. UPS protection function:
When the main power input/output voltage is too high or too low, overload, short-circuit, inverter
temperature is too high, low voltage and overcharge of battery, network surge and so on, UPS has a
protection function.
13. 13.Rack-Tower conversion LCD design. No matter what angel to watch the display, only press the key
slightly can meet your perspective needs. The content displayed on the interface is rich. The capacity of
the loads and the battery can be saw directly and the FLASH pictures and fan rotating icon can be dis-
played when charging. So it is easy to know it’s operation. When UPS fails, it can show the fault code, the
machine can be maintained as soon as possible by inquiring fault code table.
14. 14.The UPS can communicate with the computer with intelligent UPS monitoring software through the
RS232 interface. All the parameters clearly display on the communication interface. Computer can control
multiple functions of the UPS directly.
15. 15.Via internal or external SNMP adapter, UPS can go on internet and provide the latest information and
power messages. You can monitor and manage the UPS status through all kinds of network management
system.
16. 16.Convenient USB communication. You can see the operation of the machine completely. Even if the
RS232 interface is occupied or connected at the same time, it will automatically switch to USB connection.
17. 17.ECO function can help you save electricity. When the input mains power is in a fixed range, the loads
is supplied with power by mains power directly, the inverter is on waiting; when input mains power is
abnormal, it transfers to inverter to supply power to loads at once.
18. 18.In order to ensure the power of the important loads can last for a long time, you can plug the impor-
tant loads into the second power down socket. When the battery voltage is below the predetermined
value, only the first cut-off power socket is broken off, the second power down can keep on supplying
power until the battery voltage reaches protect point and shut down.
19. 19.Adopt international standard rack-mounted size. Whether you want to put it on the office desk or in the
rack-mount as a system to manage, It can present your personal style with corresponding components.

6
Manual
www.kraun.it
2. SAFETY INSTRUCTION
This chapter mainly introduce the safety marks and notes of 1KVA-3KVA series on-line UPS. Read this chapter
carefully before operating on the equipment.
2.1. SAFETY INSTRUCTION
There is dangerous voltage and high temperature inside the UPS. During the installation, operation and main-
tenance, please abide the local safety instructions and relative laws, otherwise, it will result in personal injury
or equipment damage. Safety instructions in this manual act as a supplementary for the local safety instruc-
tions.
Our company will not assume the liability that caused by disobey of safety instructions. Please note the fol-
lowing:
1. Don’t use the UPS when the actual load exceeds the rated load.
2. There are high-capacity batteries in the standard type UPS. You mustn’t open the enclo-
sure or it will lead to electric shock. If it needs internal maintenance or battery replace-
ment, please send it to the designated site.
3. Internal short-circuit of the UPS will cause electric shock or fire. So don’t place the contain-
ers equipped with liquid on the top of the UPS so as not to cause danger of electric shock
and so on.
4. Don’t put the UPS in a place with high temperature or humidity as well as the corrosive
gas, much dust.
5. Keep good air circulation between in-vent on front panel and out-vent on back panel.
6. Avoid direct sunlight or near heat-dispensed objects.
7. In case that the smoke appears on the UPS, please cut off the power as soon as possible
and contact the dealer service site.
2.2. SYMBOLS INDICATION
The safety symbols cited in this manual are shown in table 1-1, which are used to inform read-
ers of safety issues that should be obeyed when installation, operation and maintenance.
Safety Symbol Indication
Attention
Static discharge sensitive
Electric shock

7
Manual
www.kraun.it
There are three levers of safety grade: Dangerous, Warning and Attention. The remark is on the right side of
the safety symbol, the detailed comments is behind, shown as following:
DANGEROUS:
Indicate risk of serious injury or death or seriously damage the equipment
WARNING:
Indicate risk of serious injury or damage the equipment.
ATTENTION:
Indicate risk of injury or damage the equipment.
3. PRODUCT INTRODUCTION
3.1. THE APPEARANCE OF THE PRODUCT
Fig 1 Front Panel view
Fig 2 1KVA Rear Panel view
Input
Breaker
Input Mains Power socket Intelligent Slot
GND
Screw
Hole Output
RJ45 net surge
protection USB
Interface RS232

8
Manual
www.kraun.it
3.2. THE PRINCIPLE OF THE PRODUCT
Fig 4 UPS Principle Diagram
1. input filter: Complete filtering the input AC utility power to provide the clean power for UPS.
2. AC/DC converter: Convert the filtered AC mains to DC and boost the DC for DC/AC inverter.
3. DC/DC booster: When the UPS works in battery mode, the circuit boosts the DC for DC/AC inverter.
4. DC/AC inverter: Convert the boosted DC to stable AC output.
5. Bypass: When overload or failure of inverting happen in the UPS, it transfers to bypass mode to supply
power to loads.
6. Charger: Standard unit provides 1A; long backup unit provides 7A/14A.
7. Battery: Sealed Lead Acid Battery.
8. Output filter: Complete filtering the output of the UPS to provide the clean power for loads.
4. INSTALLATION
4.1. UNPACKING AND INSPECTION
1. 1. Unpacking the UPS and check that whether it’s damaged during the transportation. If damaged or
some parts missing, don’t start the machine and inform the carrier and franchiser.
2. 2. Check the annex (please consult Appendix Table 1).
3. 3. Check if the equipment is just what you wanted to purchase. You can affirm through inspecting the
model number on back panel of the equipment.
4.2. NOTES
1. Please place the UPS in a clean, stable environment, avoid the vibration, dust, too humidity, flammable
gas and liquid, corrosive.

9
Manual
www.kraun.it
2. The ambient temperature around UPS should keep in a range of 0°C~40°C. If UPS works above 40°C, it is
required that the rated value of the largest load decreases 12% while the temperature increases the 5°C
every time. The highest temperature cannot be more than 50°C when UPS works.
3. UPS should be placed in a sufficiently ventilated place.
4.3. UPS INPUT CONNECTION
Connect the UPS to the mains by input power cable which is equipped with the UPS.
Fig 5 Input Connection
4.4. UPS OUTPUT CONNECTION
Fig 6 output connection
NOTE
The Input to the group should meet on a very precise phase / neutral connection; though incorrectly con-
nected, on the display will flash “INPUT”.
The solution to this problem is to insert the plug of the group upside down.

10
Manual
www.kraun.it
4.5. INSTALLATION
4.5.1. PLASTIC BASE INSTALLATION
1. two plastic base brackets
2. flatten it after intercrossing intercross as following Figure
Fig 8 1KVA Plastic base assembly
4.5.2. CABINET INSTALLATION BRACKET ASSEMBLY
1. screw A, screw B, two M4 screws ( symmetrical on both sides, a total of four)
Fig 10 Cabinet installation bracket assembly
2. cabinet installation bracket screw hole A, screw hole B are respectively corresponding to two screws
(symmetrical on both sides, a total of four).
Fig 11 Cabinet installation bracket Fig 12 Cabinet installation bracket assembly
Questo manuale è adatto per i seguenti modelli
1
Indice
Altri manuali Kraun UPS
Manuali UPS popolari di altre marche

Pylontech
Pylontech Victron & Pylontech US5000 Manuale utente

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuale utente

Mecer
Mecer ME-1000-WTU Manuale utente

Mustek
Mustek PowerMust 530(B) Plus Manuale di installazione e funzionamento

Emerson
Emerson Liebert NXL series Manuale utente

MAKELSAN
MAKELSAN BOXER SERIES Manuale utente