AUDA/AUDS
The automatic sliding damper AUDA is a com-
pressed air powered damper for tight and rapid
closure.
Because the damper is opened and closed auto-
matically, the extraction is always focused on the
connections, extraction points or machines that
for the time being are in use. This maximizes the
extraction power and reduces the energy con-
sumption. It also creates cleaner end products
and machinery, cleaner oors and a healthier
working environment.
Design
As standard, the damper is made of zinc plated steel, but is also available in stainless steel AISI
304/316.
The pipe connections on the damper are equipped with pull ring edge or straight edge, depending
on the diameter (see table on the next page). The damper can also be delivered with connections
for rolled edge or with anges.
Air tightness is achieved by using exible rubber gaskets and sealing rings. Dimensions bigger than
Ø 200 mm, come only with sealing rings.
The standard damper can take a heat with a maximum of +80° C. Sealing rings made of Teon are
available, in cases when higher temperature is being used. Working preassure is 6-10 bar.
The damper is opened and closed by one or two compressed cylinders, depending on the diameter.
The cylinder i maneuvered by a magnetic port connected to the machinery or to a maneuver switch.
With a micro switch mounted on the damper, the fan can for example be turned on or off when the
damper is opened or closed.
1. Pneumatic cylinder
2. Connection 1/8” - 6 mm hose
3. Hose 6 mm
4. Connection 1/8” - 6 mm hose
5. Solenoid valve
6. Silencer/adjustment
7. Cable terminal
8. Coil 230V AC or 24 V AC/DC
9. Screw for manual operation of solenoid valve
10. Sealings
11. Damper housing
12. Damper blade
13. Sealing

Products for dust handling
Lajac AB l www.lajac.se l Maskingatan 10 l S-702 86 Örebro l Tel: +46 (0) 19 32 00 87 l [email protected]
Beteckning Beskrivning
SPDA-01 Solenoid valve
SPDA-02 Coil
SPDA-06 Micro switch
SPDA-07 Micro switch bracket
SPDA-08 Reed sensor
SPDA-09 Bracket for reed sensor
AUDA/AUDS
Measures on the next page
Accessories

Products for dust handling
Lajac AB l www.lajac.se l Maskingatan 10 l S-702 86 Örebro l Tel: +46 (0) 19 32 00 87 l [email protected]
Ø
mm
A
mm
B
mm
C
mm
D
mm
Blade th.
mm
House th.
mm
Weight
kg
50* 293 192,5 145 139,5 2 1,5 2,3
63* 293 192,5 145 139,5 2 1,5 2,3
76* 338 222,5 145 156,5 2 1,5 3
80 338 222,5 125 156,5 2 1,5 3
100 398 263 125 176,5 2 1,5 3,3
102* 398 263 125 176,5 2 1,5 3,3
108* 475 313,5 145 201,5 2 1,5 4
120 475 313,5 125 201,5 2 1,5 4
125 475 313,5 125 201,5 2 1,5 4
127* 475 313,5 145 201,5 2 1,5 4
140 548 363 125 226,5 2 1,5 5
150 548 363 125 226,5 2 1,5 5
152* 548 363 125 226,5 2 1,5 5
160 574 382,5 125 236,5 2 1,5 5,2
180 699 463 125 276,5 2 1,5 6,2
200 699 463 125 276,5 2 1,5 6,2
202* 699 463 125 276,5 2 1,5 6,2
225 847 562 165 347 3 2,0 11,3
250 849 562 165 371 3 2,0 13,5
300 1050 692 165 422 3 2,0 20,1
315 1050 692 165 422 3 2,0 21,1
350 1160 763 165 472 3 2,0 25
400 1310 863 165 522 3 2,0 27,4
450 1192 980 250 623 4 3,0 60
500 1644 1082 250 673 4 3,0 66,7
550 1829 1207 250 713 4 3,0 76,1
600 1964 1292 250 783 4 3,0 85,7
630 2044 1342 250 813 4 3,0 91,1
650 2044 1342 250 813 4 3,0 91,1
700 2324 1542 250 893 4 3,0 119,3
800 2564 1692 260 973 4 3,0 134,9
*with straight edge. The rest is with pull ring edge.
AUDA/AUDS

Products for dust handling
Lajac AB l www.lajac.se l Maskingatan 10 l S-702 86 Örebro l Tel: +46 (0) 19 32 00 87 l [email protected]
Installation and maintenance
Installation
When positioning the damper, the risk of personal injury must be taken into account. The damper
must therefoe be installed outside the working zone, e.g. at least 2,1 meter above the oor level.
As standard, the pipe connections are equipped with clamp rims. Installation can be carried out in
an optional position, but we recommend horizontal.
Connecting pipe work is to be suspended in such a way that the damper is not subjected to rupturing
forces. These can cause the damper to jam och to get stuck.
Electrical installation
Before starting the electrical installation the damper must be connected to the duct work, otherwise
the connections on the damper should be covered securely. Electrical connection must be carried out
by a qualied electrician.
Before starting up
1. Check that the damper blade runs smoothly. This should be done after the mechanical installation.
2. Check that the damper is opened and closed when intended.
Regular maintenance
The damper is maintenance free. When required, it can be cleaned using a cloth dipped in ethylated
spirits.
Troubleshooting when the damper blade jams or gets stuck
1. The damper needs to be cleaned
2. There are rupturing forces in the pipe system
3. The damper blade is damaged
4. Loose sealings
Service switches or lockable master switches for fans must be turned
off when working with the damper.
Declaration of conformity according to EU Directive 2006/42/EC.
Be aware that the unit may not go into service until the machine or the system it is to be included
in, complies with the requirements of the EU machinery directive.
AUDA/AUDS
Questo manuale è adatto per i seguenti modelli
30
Indice