Lennox SunSource Manuale utente

Page 1
LITHO U.S.A.
507154-01
3/2013
Supersedes 506555-01
SAMPLE PERMIT
APPLICATION PACKAGE
SOLAR - KIT / ACCESSORIES
SUNSOURCE®HOME ENERGY SYSTEM SAMPLE PERMIT APPLICATION
PACKAGE
E2013 Lennox Industries Inc.
Dallas, Texas, USA
Application
This document is provided as guidance. Installation of a
utility-interactive solar photovoltaic system generally
requires a permit from the local authority having
jurisdiction (AHJ). This document provides a typical format
for a residential permit application to install a SunSource®
Home Energy System.
TABLE OF CONTENTS
Application 1
A1 — System Summary 2
A2 — Site Plan 2
A3 — Module Layout 3
B1 — Wiring Diagram 4
B2 — Wiring Calculations 6
C1 — PVWatts Calculations 7
D1 — Labels 9
E1 — PVC AC Module Datasheet 10
E2 — Microinverter Datasheet 12
E3 — Module Attachment Hardware Datasheet 14

Page 2
A1 — System Summary
For Construction: March 15, 2013
Project #: 412
Client: Mr. Jeff Bailey
Address: Corsicana, TX
System Size: 3.180 kW
Module: Solar World SW-265
Microinventer: Enphase
Project Report
The following design describes a Solar PV system with a peak STC DC size of 3.180 kW
and an estimated electrical generation of 4828 kWh per year.
The modules are mounted on the south facing roof with an 185º azimuth at a 32º tilt. The solar PV AC array consists of
(12) SW-265 solar modules with each solar module in the array connected to an Enphase M215 microinverter. They
have 96% CEC efficiency rating
From each module, DC power is connected directly to an Enphase microinventer mounted below each module.
240VAC power from the microinventer passes through a renewable energy credit meter; next, through a disconnect
switch and then ties into solar source breaker located in the Lennox SunSource®XC21-060 (5-Ton) air conditioner.
Utility: United Cooperative Service
A2 — Site Plan
N
D
H
C
E
F
Elevation @ Utility Meter
Site Plan
1
NTS
UTILITY
METER
2/A1
AB
FROM PV ARRAY AC SOLAR DISCONNECT
EXISTING 60A HVAC
DISCONNECT; FED
FROM HVAC
BREAKER LOCATED
IN MAIN SERVICE
PANEL
2
SCALE 1/2” = 1' - 0”
G
SCHEDULE OF COMPONENTS
APhotovoltaic array
BMicroinverters
CRenewable energy credit meter (if requested by electric utility)
DAC utility disconnect
EHVAC unit (existing)
FHVAC disconnect (existing
GMain service panel (existing)
HUtility meter (existing

Page 3
A3 — Module Layout
1Module Layout
SCALE: 1/8” = 1’- 0”
SOUTH FACING ROOF: 3.18 KW PV ARRAY DETAILS
S(12) SW-265 solar PV AC modules in one AC circuit.
S(12) Enphase M215602LLS22 (240)
S90MPH designed wind speed and exposure category B.
SComposition shingle roof on 1/2” OSB decking with 2” x 6” at 24” O. C.

Page 4
B1 — Wiring Diagram
Figure 1. SunSource®Home Energy System Electrical Layout

Page 5
B1 — Alternate Wiring Diagram

Page 6
B2 — Wire Calculations
AC Wire Sizing
Description AC run from inverter through ACV disconnect to solar source
breaker.
1. Design Current
SMicroinverter Maximum Current 15 A AC Maximum Current 15 A AC
2. Wire Size
SMaximum average ambient
temperature 115°F (46°C) Temperature De-rate
Factor 0.87
SNumber of current wires 2 per conduit Conduit de-rate
factor 1
SMaximum wire temperature allowed 167°F (75°C)
SSelected wire size 10 AWG
SInsulation type THHN/THWNN-2 Specified wire
ampacity 30.45 amps
3. Conduit size
SConduit specified ¾”
SConduit type EMT
4. Breaker size
SAC over-current protection device
(OCPD) size specified 20 A AC Minimum breaker
size 20 A AC
SVoltage rating of OCPD 240 VAC Maximum breaker
size 30
5. Voltage drop
SVnom 240 VAC Voltage drop .96 VAC
SInom 12.0 A AC Voltage loss percent
age 0.4%
SWire distance 45 feet (13.7 meters) Power loss 11 watts

Page 7
C1 — PVWatts Calculations

Page 8
C1 — PVWatts Calculations (continued)

Page 9
D1 — Labels
USED ON SOLAR
DISCONNECT
SWITCH
USED ON HVAC
DISCONNECT
SWITCH
USED ON UNIT
CB10 PLASTIC
COVER
USED ON UNIT
CB40 PLASTIC
COVER
USED NEXT TO
CIRCUIT
BREAKER IN
MAIN PANEL.
SOURCE CIRCUIT DISCONNECT FOR
SOLAR
−−−−−−−−−−−−−−−−−−−
(DISCONNECT BOTH POWER SOURCES
BEFORE PERFORMING REPAIRS OR
OPENING EQUIPMENT SERVICE PANEL)

Page 10
E1 — Module Data Sheet
COMPONENT MATERIALS
265 Wp
Cells per module 60
Cell type Mono crystalline
Cell dimensions 6.14 in. x 6.14 in.
Front Tempered glass
(EN 12150)
Frame Clear anodized
aluminum
Weight 47 lbs.
SYSTEM INTEGRATION PARAMETERS
Maximum system voltage SC II 1000V
Maximum system voltage USA NEC 600V
Maximum reverse currents 16A
Number of bypass diodes 3
UL Design Loads Two rail system 113 psf downward,
64 psf upward
UL Design Loads Three rail system 170 psf downward,
64 psf upward
IEC Design Loads Two rail system 113 psf downward,
50 psf upward
THERMAL CHARACTERISTICS
265 Wp
NOCT 115F
TCISC 0.004%/K
TCVOC –0.30%/K
TCPMPP –0.45%/K
Operating Temp. –40F to 185F
ADDITIONAL DATA
265 Wp
Power Tolerance −0 Wp / +5 Wp
J−Box IP65
Connector MC4
Module ef’iciency 15.81%
Fire rating UL (790) Class C
PERFORMANCE
Performance
Under
1Standard Testing
Conditions
2Performance At 800 W/M
2,
Normal Operating Cell
Temperature (NOCT),
AM 1.5
Maximum Power Pmax 265 Wp 187.6 Wp
Open Circuit
Voltage Voc 38.1V 34.3V
Maximum Power
Point Voltage Vmpp 31.9V 28.7V
Short Circuit
Current Isc 8.82A 7.12A
Maximum Power
Point Current Impp 8.33A 6.66A
1Standard Testing Conditions at 1000W/m
2
, 25C, AM 1.5
2
Minor reduction in ef’i
Altri manuali per SunSource
1
Indice