LG AMNQ12GTRA1 Manuale utente

INSTALLATION MANUAL
AIR
CONDITIONER
www.lg.com
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thorough-
ly.
MULTI TYPE CEILING CASSETTE
Copyright © 2012 - 2021 LG Electronics Inc. All Rights Reserved.
MFL65779702
Rev.02_010821
ENGLISH

• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition-
er is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
TIPS FOR SAVING ENERGY
ENGLISH
TIPS FOR SAVING ENERGY
2

3
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation MUST conform with local building codes or, in the absence of local codes, with
the Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical
Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal-
function, property damage, personal injury and/or death.
Installation
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service
Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or
a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the
condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
!
!
!
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS

• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product
failure, and personal injury.
• Do not use the aluminum pipe.
- It will cause gas leakage.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not com-
press air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explo-
sion.
- There is the risk of death, injury, fire or explosion.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the
neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evapora-
tor fins, could cause product malfunction or inefficient operation.
• Do not install the unit in potentially explosive atmospheres.
!
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
4

5
2TIPS FOR SAVING ENERGY
3IMPORTANT SAFETY INSTRUCTIONS
6INTRODUCTION
6Features
7INSTALLATION
7Selection of the best location
8Ceiling dimension and hanging bolt location
10 Drain Piping
12 Wiring Connection
13 Remote Control Preparation
14 INSTALLATION OF DECORATIVE PANEL(ACCESSORY)
17 INSTALLATION INSTRUCTIONS
17 Installer Setting - Setting Address of Central Control
17 Installer Setting - Checking Address of Central Control
18 Installer Setting -How to enter installer setting mode
20 DIP Switch Setting of Indoor unit PCB
TABLE OF CONTENTS
ENGLISH
TABLE OF CONTENTS

Filter
Air Outlet
Air Inlet
Remote
Controller
Name Quantity Shape
for gas pipe for liquid pipe
Clamp metal 2 EA
Insulation for
fitting 1 set
Drain hose 1 EA
Clamp
(Tie Wrap)
8 EA
Washer for
hanging bracket
4 EA
Bolt 4 EA
Other
• Paper pattern for
installation
• Owner's manual
• Installation manual
Screws for fixing panels are attached to decoration panel.
6INTRODUCTION
Features
ENGLISH
INTRODUCTION

INSTALLATION
ENGLISH
7
Selection of the best location
There should not be any heat source or steam near the unit.
There should not be any obstacles to the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
The indoor unit must have the maintenance space.
Read completely, then follow step by step.
Unit:mm
Ceiling
Ceiling Board
Ceiling Board
300 or more
Above 2500
4000 or less
1000
or more
500 or
more
500 or
more
300 or less
Floor
INSTALLATION
* Please use an annexed sheet or the corru-
gated cardboard on the bottom of packing
as installation sheet.
* When using the bottom sheet, please use it
after separating the installation sheet from
packing of the product floor by using a knife
etc as a picture below.
Annexed sheet
Or
Packing corrugated
cardboard on the
bottom
CAUTION
!
In case that the unit is installed near the sea, the installation parts may be corroded by salt.
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.

8INSTALLATION
ENGLISH
Ceiling dimension and hanging bolt location
The dimensions of the paper model for installation are the same as those of the ceiling opening
dimensions.
Ceiling board
TQ/TR Chassis TM/TN/TP/TP-B Chassis
Unit:mm
585~660(Ceiling opening)
517
461
517
585~660
(Ceiling opening)
523
570
570
319
Unit:mm
875(Ceiling opening)
787
(Hanging bolt)
684(Hanging bolt)
671
875(Ceiling opening)
840
Unit size
840
Unit size
Level gauge
Ceiling
Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to the drain direction after considering the direc-
tion of drain hose.
Drill the hole for anchor bolt on the wall.
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
CAUTION
!

INSTALLATION
ENGLISH
9
Use the
ventilation
fan for smoke
-collecting
hood with
sufficient
capacity.
Cooking table
Air conditioner
Take enough
distance
NOTE
!
• Avoid the following installation location.
1Such places as restaurants and kitchen where considerable amount of oil steam and
flour is generated. These may cause heat exchange efficiency reduction, or water
drops, drain pump mal-function. In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a
place where it may not suck oily steam.
2Avoid installng air conditioner in such places where cooking oil or iron powder is gener-
ated.
3Avoid places where inflammable gas is generated.
4Avoid place where noxious gas is generated.
5Avoid places near high frequency generators.
Flat washer for M10
(accessory)
Flat washer for M10
(accessory)
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Nut
(W3/8 or M10)

10 INSTALLATION
ENGLISH
Set screw of
paper pattern (4 pieces)
Keep the length of *( ) mm between
the air conditioner bottom surface
and the ceiling surface
Paper pattern
for installation
90mm
Adjust the same height
False
ceiling board
Ceiling
Keep the length of the bolt
from the bracket to 40mm
Open the ceiling board
along the outer edge of the
paper pattern
Air Conditioner body
False ceiling board
* The following parts are local purchasing.
① Hanging Bolt - W 3/8 or M10
② Nut - W 3/8 or M10
③ Spring Washer - M10
④ Plate Washer - M10
*( ) →TQ/TR : 31~34mm
TM/TM-A/TN/TP/TP-B : 15mm
Drain Piping
• Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
• During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
• The outside diameter of the drain connec-
tion on the indoor unit is 32mm.
- Piping material: Polyvinyl chloride pipe VP-
25 and pipe fittings
• Be sure to install heat insulation on the drain
piping.
- Heat insulation material: Polyethylene
foam with thickness more than 8 mm.
Maintenance
drain port
Upward
routing
not allowed
Pipe clamp
Indoor unit
1/50~1/100
MAX 700mm
CAUTION
!
Tighten the nut and bolt to prevent the
unit from falling.
Indice
Altri manuali LG Condizionatore d'aria

LG
LG HT-C186HLA1 Manuale utente

LG
LG CL8000ER M8004R Manuale utente

LG
LG LS-C1863R/W/B/D/M/CM0 Manuale utente

LG
LG LW2512ER Manuale utente

LG
LG LW7012HR Manuale utente

LG
LG ATNQ18GPLE6 Manuale utente

LG
LG HPWI-C20E Manuale utente

LG
LG TERMINATOR SN05ICEX Manuale utente

LG
LG ARNU07GTUA4 Manuale utente
![LG LZ-H080GBA2 [ARVU053ZEA2] Manuale utente LG LZ-H080GBA2 [ARVU053ZEA2] Manuale utente](/data/manuals/27/2/272ct/sources/lg-lz-h080gba2-arvu053zea2--manual.jpg)
LG
LG LZ-H080GBA2 [ARVU053ZEA2] Manuale utente

LG
LG AS-H096UM0 Manuale utente

LG
LG AMNQ24GTPB0 Manuale utente

LG
LG LMCN125HV Manuale utente

LG
LG ARNU483BRZ4 Manuale utente

LG
LG LT0814CNR Manuale utente

LG
LG Therma V FHNW16606C0 Guida del prodotto

LG
LG PC12ST Manuale utente

LG
LG PQDSBC1 Manuale utente

LG
LG LAN180HYV1 Manuale utente

LG
LG LW1017ERSM Manuale utente