LG GHP SUPER Manuale utente

INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national
wiring standards by authorized personnel only.
• Please retain this installation manual for future reference after reading
it thoroughly.your set and retain it for future reference.
www.lg.com
Model : GPUW***BSS
GP*W***B6*
GP*W***B2*
P/NO : MFL67737304
ENGLISH

• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition-
er is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
ENGLISH
TIPS FOR SAVING ENERGY
2
TIPS FOR SAVING ENERGY

3
IMPORTANT SAFETY INSTRUCTIONS
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
WARNING
It can result in serious injury or death when the directions are ignored
CAUTION
It can result in minor injury or product damage when the directions are ignored
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
•
Installation of all field wiring and components MUST conform with local building codes or, in the
absence of local codes, with the National Electrical Code 70 and the National Building Construction
and Safety Code or Canadian Electrical Code and National Building Code of Canada.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment mal-
function, property damage, personal injury and/or death.
Installation
• Only licensed electricians should do all electrical work according to “Electric Facility Engineer-
ing Standard” and “Interior Wire Regulations” and the instructions given in this manual and
always use a specific circuit.
- If the power supply capacity is inadequate or electrical work is performed improperly, electric
shock or fire may result.
• Only licensed technicians should install the fuel gas pipes and do the piping work.
- Improper installation may cause fire or explosion.
• Always ground the product
- There is a risk of fire or electric shock if not grounded.
• Always install a circuit breaker and dedicated switch.
- If not installed, it may cause fire or electric shock.
• Do not use a damaged circuit breaker or dedicated switch.
- It may cause fire or electric shock.
• For the installation of gas heat pump, always contact an authorized service center.
- Improper installation may result leak, fire or electric shock.
• For the re-installation, always contact the service center.
- Improper installation may result leak, fire and electric shock.
• Do not disassemble, repair, or modify the air conditioner on your own.
- It may cause fire or electric shock.
• Do not store or use flammable gas or combustibles near the air conditioner.
- There is a risk of fire or failure of product.
!
!
!
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS

• Always use the correctly rated breaker or fuse.
- Use of overrated breaker or fuse, or metal copper wires may cause fire or failure of the air
conditioner.
• Prepare for strong wind or earthquake and install the unit fixed in the ground at the specified
place.
- There is a risk of death, property damage, or injury.
• When installing and moving the air conditioner to another site, do not charge it with a differ-
ent refrigerant from the refrigerant R410A specified on the unit.
- If a different refrigerant is mixed with the original refrigerant, the refrigerant cycle may mal-
function and the unit may be damaged.
• Do not use the R22 manifold gauge.
- Always use the high-pressure R410A manifold gauge for a stable charging.
• Do not use the R22 pipes and installation materials for the R410A installation. (do not mix
them up)
- Mixing the R22 refrigerant oil with the R410A oil will cause a hydrolysis, and may lead to fire
or failure of the air conditioner.
• Install the air conditioner onto a sturdy place where it can sustain the weight.
- Improper location may cause the air conditioner to fall and get damaged.
• Do not reconstruct to change the settings of the protection devices.
- If the protection device is shorted and modified, and operated forcibly, fire or explosion may
result.
• Always use a vacuum pump or Inert (nitrogen)gas when doing leakage test or air purge.
- Use of oxygen, compressed air and flammable gases may cause fire and explosion.
There is risk of death, property damage, or explosion.
• Check what kind of fuel gas is used.
- Using an incorrect type of gas may cause the operation failure of the engine and the mal-
function of the engine combustion, and result a carbon monoxide poisoning and the break-
down of the engine.
• Do not combine the exhaust drain hose of the indoor unit and the outdoor unit.
- Combining the exhaust drain hose will make the exhaust flow backward in and increase the
risk of carbon monoxide poisoning.
• Install the outdoor unit properly to prevent a reversed flow of the exhaust gas.
- Exhaust gas flowing backward into a building may cause carbon dioxide poisoning.
• If the air conditioner is installed in a small room, measures must be taken to prevent to refrig-
erant concentration from exceeding the safety limit when the refrigerant leaks.
- If the refrigerant leaks and exceeds the safety limit, hazards due to lack of oxygen in the
room could result.
• Ventilate before operating air conditioner when refrigerant gas leaks.
- If the refrigerant contacts inflammables such as welding flame, hazardous gas may result.
• The power of indoor and outdoor units must be separated when installing.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
4

IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
5
Operation
• Do not extend or modify a power cord on your own.
- It may cause fire or electric shock.
• Use a dedicated power cord.
- It may cause fire or electric shock.
• Keep the air conditioner (control panel) from getting wet. Do not wash the air conditioner with
water.
- There is a risk of electric shock or failure of the air conditioner.
• Do not touch the main power switch with wet hands.
- It may cause fire or electric shock
• When the air conditioner is soaked (flooded or submerged), contact service center.
- It may cause fire or electric shock
• Do not touch the heat exchanger fins.
- The sharp fins may cause injury.
• Do not change the reconstruction and the setting of the protection devices.
- If the pressure switch, thermal switch, or other protection device is shorted or operated
forcibly, or unspecified parts are used, fire and explosion may result.
• Do not operate the air conditioner with the shutoff valve closed when gas leaks.
- Operating the air conditioner during gas leaks may result fire or explosion.
• Do not block the inlet or outlet of indoor/outdoor units.
- Since the fan rotates at high speed during operation, it may cause injury or failure of the aid
conditioner.
CAUTION
Installation
• Always check for gas leakage after installation or repair of the air conditioner.
- It may cause failure of the air conditioner.
• Do not install the product where the noise or hot air from the outdoor unit could disturb your
neighbors.
- It may cause a conflict with your neighbors.
• Keep level even when installing the product.
- Uneven height of the air conditioner may result a shaking and leakage.
• Do not install the air conditioner in an area where the gas leaks.
- If the gas leaks around the unit, property damage may result.
• Do not use the air conditioner for special purposes, such as storing works of art, animals and
plants, or sensitive devices.
- If the air conditioner is used for these purposes, property damage may result.
• Keep the unit away from children.
- The heat exchanger fins are very sharp. It can cause the injury, such as cutting the finger.
The damaged fins may result in degradation of capacity.
• When installing the unit in a hospital, communication station, or similar places, provide suffi-
cient protection against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or
radio communication equipment may cause the air conditioner to operate erroneously, or fail
to operate. On the other hand, the air conditioner may affect such equipment by creating
noise that disturbs medical treatment or image broadcasting.
!

6IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Do not install the product where it is exposed to sea wind (salt spray) directly. Build a fence
around the unit, if necessary.
- Corrosion caused by the sea wind (salt spray) may result a product malfunction or inefficient
operation.
• Keep animals and plants from the direct air of the outdoor unit inlet/outlet or exhaust gas.
- It may harm animals and plants.
Operation
• Do not obstruct the air passage of the outdoor unit inlet/outlet/drain hose.
- It may cause failure of the unit or carbon monoxide poisoning.
• Do not climb on the outdoor unit or place any objects on it.
- It may cause property damage or injury if falling or electric shocked.
• Do not touch the exhaust gas outlet of the outdoor unit.
- It may cause burns.
• When the oil or coolant leaks from the outdoor unit, contact service center.
- Such leakages may damage the outdoor unit and the other accessories (waterproof sheet) as
well.
Precautions during electrical work and transportation
• Do not put a tension force on the power cables when installing.
- The cables may cut off and generate heat due to a high tension, and it may cause fire. Do
not replace the damaged power cables on your own. Instead, contact A/S center for replace-
ment.
• Always use a dedicated power cables.
- Use power cables of sufficient current carrying capacity and rating. It may cause fire or elec-
tric shock.
• Beware of the damage to the stand from long-term use.
- It may cause injury or property damage.
• Be careful when transporting the air conditioner.
- Do not carry a product weighing more than 20kg on your own.
- Some products use PP bands for packaging. Do not use any PP bands for the transportation
purpose.
- Do not touch the heat exchanger fins. You may cut your fingers.
- When transporting the air conditioner, make sure to suspend it at the specified positions on
the unit base. In addition, be sure to support the unit at four points to prevent it from slipping
sideways.
• Safely discard the packing materials.
- Some packing materials, such as nails and other metal or wooden parts, may cause stabs or
other injuries.
- Tear apart and throw away plastic packaging bags so that children will not play with them.
Children playing with plastic bags face the danger of suffocation.

7
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
Precautions before a test run
• Turn on the main power at least 5 hours before starting operation in case of low outdoor tem-
perature.
- Starting operation immediately after turning on the main power many result in severe dam-
age to internal parts. Keep the power switch turned on during operation. Keep the power
switch turned on during operation.
• Do not touch any of refrigerant pipes during or right after operation.
- The refrigerant pipes during or right after operation can get very hot or cold depending on the
refrigerant condition which flows through the pipes, compressor, and refrigerant cycle parts.
If you touch the pipes with the refrigerant passing through, you may get burned or frostbite.
• Do not operate the air conditioner with the product panels or guards removed.
- Rotating, hot, or high-voltage parts can cause injury.
• Do not turn off the main power immediately after stopping the operation.
- Wait at least for 5 minutes before turning off the main power. Otherwise, it may result in
water leakage or other problems.
• Auto-addressing should be done with the power of all indoor and outdoor units connected.
Auto-addressing should also be done after replacing the indoor unit PCB.

8TABLE OF CONTENTS
ENGLISH
TABLE OF CONTENTS
2TIPS FOR SAVING
ENERGY
3IMPORTANT SAFETY
INSTRUCTIONS
9COMBINATION OF
OUTDOOR UNIT
11 ACCESSORIES
13 INSTALLATION
PROCESS
14 SELECTION OF
INSTALLATION SITE
17 OUTDOOR UNIT
INSTALLATION
25 REFRIGERANT PIPING
33 PIPE CONNECTIONS
BETWEEN
INDOOR/OUTDOOR
UNITS
38 LEAK DETECTION
39 PIPE INSULATION
41 VACUUM AND
REFRIGERANT CHARGE
44 ELECTRICAL WIRING
57 ADDITIONAL
FUNCTIONS
64 SELF-DIAGNOSIS
FUNCTION
69 REGULAR
MAINTENANCE

COMBINATION OF OUTDOOR UNIT
ENGLISH
9
Combination of Outdoor Unit
Chassis Name Capacity [kW (btu/h)] Chassis Combinations
UPB
GPUW160B2C/B6C/B6S
GPUW200B2C/B6C/B6S
GPUW250B2C/B6C/B6S/BSS
45 (153 600)
56 (191 100)
71 (242 300)
UPB
UPB
GP-W320B2C/B6C
GP-W360B2C/B6C
GP-W400B2C/B6C
GP-W450B2C/B6C
GP-W500B2C/B6C
90 (307 100)
101 (344 600)
112 (382 100)
127 (433 300)
142 (484 500)
System Capacity
[kW (btu/h)]
Number of Indi-
vidual Outdoor
Units
Individual Outdoor Unit Capacity [kW (btu/h)]
45 (153 600) 56 (191 100) 71 (242 300)
Master Slave Master Slave Master Slave
1 1
1 1
1 1
2 1 1
2 1 1
2 1 1
2 1 1
2 1 1
COMBINATION OF OUTDOOR UNIT
GHP Model
45 (153 600)
56 (191 100)
71 (242 300)
90 (307 100)
101 (344 600)
112 (382 100)
127 (433 300)
142 (484 500)

10 COMBINATION OF OUTDOOR UNIT
ENGLISH
Precautions to take when installing in a series
CAUTION
• When an indoor unit is connected to more than 100% of outdoor unit capacity, the cooling
and heating performance of the indoor unit running may be reduced.
• When installing indoor units in a series, install in descending order of outdoor unit capacity
as follows.
!
ڸڹ
A
(Master)
B
(Slave)
A ≥B
①Connecting pipe on the indoor unit
②Connecting branch duct between outdoor units
Questo manuale è adatto per i seguenti modelli
20
Indice
Altri manuali LG Condizionatore d'aria

LG
LG AMNH09GAF11 Manuale utente

LG
LG LT-H242PLE0 Manuale utente

LG
LG USUW186K3A0 Manuale utente

LG
LG U24WU42 Guida rapida

LG
LG MULTI F MAX Manuale di installazione e funzionamento

LG
LG LM-2063H3L Manuale utente

LG
LG LWHD1200FR Manuale utente

LG
LG W09TCM-CB60 Manuale utente

LG
LG LM50 Manuale operativo

LG
LG L1210ER Manuale utente

LG
LG ATNQ18GPLE7 Manuale utente

LG
LG LWHD1200FR Manuale utente

LG
LG LPUC808FA0 Manuale utente

LG
LG LP1214GXR Manuale utente

LG
LG ATNQ24GPEL6 Manuale utente

LG
LG JW-Q12WUZA Manuale utente

LG
LG AMNQ24GTPB0 Manuale utente

LG
LG AMNQ09GSJA0 Guida rapida

LG
LG APNQ24GS1A3 Manuale utente

LG
LG MULTI V IV PRO JRUN180LLS4 Manuale utente