LS Control PressureBox Manuale utente

User Manual
PressureBox
949-208295 PressureBox Manual Rev.1.1 01/2023 DC/DF

www.lscontrol.dk
PressureBox Highlights
Safety Precautions p. 3
Standards and Directives p. 4
Model Overview p. 5
Technical Specification and Measures p. 6
Connection Diagram and Jumpers p. 7
Choice of pressure area p. 9
Setting-up the PressureBox via Display p. 10
Functionality p. 12
Menu in PressureBox Display p. 13
ModBus Protocol p. 14
This manual is primarily to be used by technicians whom are to set-up and use the PressureBox in an
installation.
It posits that personnel installing this product are in possession of necessary practical experience and
education within the area the product is to be used and also hold necessary authorizations to install
installation materials.
Content
Page 2 of 17
PressureBox has 3 different areas of usage
1. Only showing the measured value
2. As external transducer in installations
3. As regulator with build-in transducer
PressureBox is available in 4 major pressure areas which can be scaled
0-7000Pa - can be scaled to 0-5000Pa, 0-3000Pa or 0-2000Pa
0-2500Pa - can be scaled to 0-1500Pa, 0-500Pa or 0-250Pa
0-500Pa - can be scaled to 0-250Pa, 0-125Pa or 0-50Pa
0-50Pa - cannot be scaled
Each of the major pressure area models are also available in the variants
1 or 2 build-in pressure transduceres
With or without display
More PressureBox models have the possibility for connecting 2 temperature sensors of type NTC or
PT1000
For all models signal output can be chosen to be ModBus or 0-10V / 4-20mA.
Please also refer to model overview on page 5.

www.lscontrol.dk
Safety Precautions
• Please read the entire manual before installing and using the PressureBox.
• In case the instructions in this manual are not followed it may harm the product and suspend any
guarantee.
Be careful not to harm the product during unpacking.
Be sure to follow rules for tools when mounting.
Product must not be disposed of in refuse collection.
Product must be disposed of according to local regulations regarding
disposal of small electronic products.
Page 3 of 17
Do not touch product with wet hands.
Do not store or use product outside recommended temperature area,
and do not expose it to UV-light.
Do not wash product with water or any other liquids.
Product is only to be used in non-condensing environment.
Make sure to be ESD-discharged before operating the buttons under the lid.
Manufacturer
LS Control A/S
Industrivej 12, Gelsted
4160 Herlufmagle
Denmark
+45 5550 5550
Product must not be exposed to direct sunlight.

www.lscontrol.dk
Standards and Directives
PowerBox complies to below standards and directives.
• EN60335-1:2012 - Household and similar electrical appliances (LDV) - safety - Part 1: General
requirements.
• EN60335-1/AC:2014 - Household and similar electrical appliances (LDV) - safety - Part 1: General
requirements.
• EN 61000-6-1:2019 - Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity
standard for residential, commercial and light-industrial environments.
• EN 61000-6-3:2007 - Electromagnetic compatibility (EMC) - Part 6-3: Generic standards - Emission
standard for residential, commercial and light-industrial environments.
• EN 61000-6-3/A1:2011 - Electromagnetic compatibility (EMC) - Part 6-3: Generic standards -
Emission standard for residential, commercial and light-industrial environments.
• EN 61000-6-3/A1/AC:2012 - Electromagnetic compatibility (EMC) - Part 6-3: Generic standards -
Emission standard for residential, commercial and light-industrial environments.
This product complies to RoHS directive, Directive 2011/65/EU
The manufacturer of this product is a member of the compulsory recycling system under the WEEE
directive
Page 4 of 17

www.lscontrol.dk
Model overview
Page 5 of 17
Product
Number
Product Name
Display
Yes/No
NTC /
PT1000
inputs
Number
of trans-
ducers
Pressure
Area
Factory
Setting
40745
PressureBox ED 50 /ES 1088
Yes
2
1
0-50Pa
0-50Pa
40747
PressureBox ED 500 /ES 1088
Yes
2
1
0-500Pa
0-250Pa
0-125Pa
0-50Pa
0-500Pa
40748*
PressureBox Dual E500 24DC /ES 1088
No
0
2
0-500Pa
0-250Pa
0-125Pa
0-50Pa
0-500Pa
40760
PressureBox E 2500 /ES 1088
No
0
1
0-2500Pa
0-1500Pa
0-500Pa
0-250Pa
0-500Pa
40765
PressureBox E 7000 /ES 1088
No
0
1
0-7000Pa
0-5000Pa
0-3000Pa
0-2000Pa
0-7000Pa
40770
PressureBox Dual E 2500 /ES 1088
No
0
2
0-2500Pa
0-1500Pa
0-500Pa
0-250Pa
0-500Pa
40775
PressureBox Dual E 7000 /ES 1088
No
0
2
0-7000Pa
0-5000Pa
0-3000Pa
0-2000Pa
0-7000Pa
40780
PressureBox ED 2500 /ES 1088
Yes
2
1
0-2500Pa
0-1500Pa
0-500Pa
0-250Pa
0-500Pa
40785
PressureBox ED 7000 /ES 1088
Yes
2
1
0-7000Pa
0-5000Pa
0-3000Pa
0-2000Pa
0-7000Pa
40790
PressureBox Dual ED 2500 /ES 1088
Yes
2
2
0-2500Pa
0-1500Pa
0-500Pa
0-250Pa
0-500Pa
40798
PressureBox Dual ED 7000 /ES 1088
Yes
2
2
0-7000Pa
0-5000Pa
0-3000Pa
0-2000Pa
0-7000Pa
* Note: Item number 40748 is equipped with ModBus only. No 0-10V output nor digital input is
available in this model.

www.lscontrol.dk
Technical Specifications
Supply Voltage: 24V AC/DC ±15%
Power Consumption: Less than 200mA
Enclosure: IP54
Weight: 200 g
Storing Temperature: +5ºC to +50ºC
non-condensing
Humidity: 0-97%RH
non-condensing
Operating Temp for models with display
24VAC: 0ºC to +35ºC
24VDC: 0ºC to +40ºC
non-condensing
Operating temp. for models without display
24VAC: -20ºC to +35ºC
24VDC: -20ºC to + ºC50
non-condensing
Temperature Sensor Input: 2 x NTC10K /
PT1000
NTC Temp. Sensor Area: -30ºC til +130ºC
Accuracy: ±1ºC
Pt100 Temp. Sensor Area: -80ºC til +80ºC
Accuracy: ±0,5ºC
Pressure Hose Connection: Ø 4mm
Pressure Area: 0-7000Pa
Pressure Accuracy: ±1,5% of measured
value, ±10Pa
Pressure Area: 0-2500Pa
Pressure Accuracy: ±1,5% of measured
value, ±3Pa
Pressure Area: 0-500Pa
Pressure Accuracy: ±0,75% of measured
value, ±0,15Pa
Pressure Area: 0-50Pa
Pressure Accuracy: ±0,75% of measured
value, ±0,04Pa
For accuracy of pressure it is required that
pressure sensor is zero-callibrated. The 0-50Pa
and 0-500Pa models are zero-calibrated from
factory.
Communication Protocol: ModBus
Communication Interface: RS485
Page 6 of 17
Size and Measures
Front Side

Possible Display
Push button 1
Push button 2
SW2
ES 1088
NTC 1
NTC 2
GND
GND
Out 0-10V / 4-20mA
GND
DI 1
DI 2
GND
+24V
B
A
Green LED
SW1
Pressure
Sensor 1
Pressure
Sensor 2
Jumpers
www.lscontrol.dk
Connection Diagram
Jumper Choices
Jumper
2 pins at right (marked red)
connected
2 pins at left (marked
green) connected
1: ModBus termination
Termination OFF
Termination ON
2: NTC/PT1000
PT1000
NTC
3: NTC/PT1000
PT1000
NTC
4: V/mA output
0-10V Out
4-20mA out
Page 7 of 17
Jumpers
Jumper 1
ModBus
termination
Termination Off
Termination On
Jumper 2
NTC / PT1000
Use the jumpers to choose ModBus termination, type of
temperature sensor and output V/mA.
See below for selections.
PT1000
NTC
Jumper 3
NTC / PT1000
PT1000
NTC
Jumper 4
0-10V / 4-20mA
Output
0-10V out
4-20mA out

www.lscontrol.dk
Connecting Pressure Tubes
Page 8 of 17
Below photos show how to connect the pressure tube to PressureBox without display. Pressure tubes
are connected the exact same way on PressureBox with display.
Connecting the pressure tubes on PressureBox with
one pressure transducer only.
Pressure +
Suction -
Connecting the pressure tubes on PressureBox with 2
pressure transducers.
Pressure +
Suction -
Pressure transducer 1
Pressure transducer 2
Mounting
PressureBox must be mounted on a firm non-vibrating surface by use of screws through the holes in the
mounting base on each side of the PressureBox.
Please also pay attention to the paragraph with safety precautions and preconditions for mounting and
using the product.

Push button 1
Push button 2
SW2 Green LED
SW1
Push button 1
Push button 2
SW2 Green LED
SW1
www.lscontrol.dk
Setting Pressure Area in PressureBox without Display
To use PressureBox as a pressure transducer in installations using 0-10V or 4-20mA signal it is possible
to set most models of PressureBox to 1 of 4 different pressure areas. Please refer to table of
PressureBox models to select the right model to the required pressure area.
Below instruction shows how to change the pressure area.
Turn screws and remove lid from PressureBox. Now you
have access to the push buttons and the connection
clamps.
Connect supply voltage.
Hold button 1 down until the green LED is constantly lit.
Let go of button 1.
Push button 1 the number of times required for the
desired pressure area. E.g. for PressureBox E 500; 1
time for 0-50Pa, twice for 0-125Pa, 3 times for 0-250Pa
and 4 time for getting back to factory setting 0-500Pa.
When no buttons have been pushed for 25 sec. the
PressureBox saves the selected pressure area and is
ready to be used as pressure transducer, where pressure
is read as 0-10V or 4-20mA signal through the analogue
output.
The green LED flashes the number of times you have
pushed button 1 and thereby indicate the setting. 3
flashes followed by pause, then again 3 flashes indicates
a setting of 0-250Pa.
If you want to read the pressure though ModBus you must also set the Pressure Area using ModBus
Protocol.
Please see the paragraph on setting up PressureBox using ModBus Protocol.
Green LED
Green LED
Page 9 of 17
Hold down
lit
Push X times Flashes
according to
nbr of pushes

Push button 1
Push button 2
SW2 Green LED
SW1
Push button 1
Push button 2
SW2 Green LED
SW1
Push button 1
Push button 2
SW2 Green LED
SW1
www.lscontrol.dk
Further Settings of PressureBox Without Display
If PressureBox without display is to be used in installations where K-factor, setpoints to PID-regulator
etc. are to be used, it must be set using the ModBus protocol.
Please refer to the tables starting at page 12 with ModBus Protocol settings for PressureBox.
Setting PressureBox With Display
To use PressureBox as a pressure transducer in installations using 0-10V or 4-20mA signal it is possible
to set most models of PressureBox to 1 of 4 different pressure areas. See table of PressureBox models
for the different models possible pressure areas.
Below instruction shows how to change the pressure area.
Turn screws and remove lid from PressureBox. Now you
have access to the push buttons and the connection
clamps.
Connect supply voltage.
Hold down button 1 for approx. 15 sec. until display
changes to show 'SCALEMAX' and the current pressure
scale setting is shown.
Let go of button 1
Push button 1, with each push the scale value changes
in display. Stop when required scale is shown.
Page 10 of 17
When the required scale value is shown in display, push
button 2 to save the setting.
PressureBox is now ready to be used as pressure
transducer, where pressure can be read as 0-10V or 4-
20mA signal through the analogue output.
Hold down
Push to modify
Push to save
Indice
Altri manuali LS Control Controllori