Lumisys MX08 Manuale utente

Installation Guide
1025 Cobb Place Blvd Suite 100 Kennesaw, GA 30144 • 800-241-9173 • www.anybas.com
Lumisys MX Series

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 2
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
This section serves as a notice of the immediate or potential dangers involved when working with
the equipment described throughout this manual. Any person involved in installation, maintenance,
or service of the equipment should first carefully examine the equipment and read the instructions
contained in this manual to ensure that personal and/or equipment injury is avoided.
The following safety messages are used throughout this manual to alert of immediate or potential
danger to life or property:
In addition, this symbol may appear in the margin of specific portions of text as a safety reminder.
Applicable instruction steps will be listed beneath the symbol.
This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC Rules. These limits are designated to provide reasonable
protection against harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause harmful interference
to radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference, in which case the user will be required to correct the interference at his own
expense.
Instructions contained in this user’s guide should be performed only by qualified persons in
accordance with local and national codes. Lumisys® Lighting and its affiliates assume no
responsibility for any consequences related to the improper use of this manual.
CAUTION: Used without the safety alert symbol, indicates a potentially haz-
ardous situation which, if not avoided, can result in personal or
property damage. Failure to comply with proper handling of the Lumisys
products may void your warranty
ATTENTION
DANGER! Indicates an immediately hazardous situation which,
if not avoided, will result in death or serious injury.
!
WARNING! Indicates a potentially hazardous situation which, if
not avoided, can result in death or serious injury.
!
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, can result in minor or moderate injury.
!
Disclaimer
Hint Indicates a tip or trick to help you.
Note Indicates an important note.

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 3
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
Table of Contents
Overview ..............................................................................................................
Inspection ............................................................................................................
Installation ............................................................................................................
Connecting the Power Supply .............................................................................
Connecting the Power Supply con’t .....................................................................
Connecting Branch Circuit Wires .........................................................................
Connecting Branch Circuit Wires con’t ................................................................
Connecting Switch Inputs ....................................................................................
Connecting Switch Inputs con’t ............................................................................
Connecting the RS-485 Network .........................................................................
Connecting Lumisys LS5 Photocell Inputs ...........................................................
Adding and Removing LTR Relays ......................................................................
Connecting to Digi-Touch Addressable Switch Network ......................................
Terms and Conditions of Sale ..............................................................................
3
4
5
6
7
8
9
10
11
12
13
14
15
16

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 4
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
Product Family Comparison
MX08 MX16 MX32 MX48 MX60
Panel
Dimensions (Width x Height x Depth) 13” x 16” x 4” 18” x 25” x 5 3/4” 18” x 33 3/4” x
5 3/4”
18” x 45 1/2” x
5 3/4”
18” x 45 1/2” x
5 3/4”
Contactor Mounting Space N/A 8.0” x 8.0” x 5.0” 8.0” x 8.0” x 5.0” 8.0” x 8.0” x 5.0” N/A
Trim Style Screw on Tru-lock Tru-lock Tru-lock Tru-lock
Controller Lx5 Lx5 Lx5 Lx5 Lx5
Flash Upgrade Yes Yes Yes Yes Yes
Inputs
Digital Subnet for Switches and Occupancy
Sensors
Digi-Touch Native Digi-Touch Native Digi-Touch Native Digi-Touch Native Digi-Touch Na-
tive
Binary inputs available without option card 24 24 56 88 120
Analog Inputs available without option card 6 6 6 6 6
Optional Telephone Override Card No Yes Yes Yes Yes
Outputs
Relay Panel Capacity 8 16 32 48 60
Latching Relay with manual override on relay Yes,
Lumisys True
Relay (LTR)
Yes,
Lumisys True
Relay (LTR)
Yes,
Lumisys True
Relay (LTR)
Yes,
Lumisys True
Relay (LTR)
Yes,
Lumisys True
Relay (LTR)
Warranty 24 months from date of shipment.
Refer to Lumisys Terms and Conditions of Sale for additional details.
This document provides instructions on how to physically install the Lumisys MX Series Lighting Relay Panel. For panel
conguration and programming refer to Maxiom User’s Guide- Hardware and Maxiom User’s Guide - Software. For network
point descriptions and integrations to a building automation system refer to the appropriate Maxiom Integration Guide.
Overview

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 5
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
The MX Series comes in ve basic units based upon relay capacities: MX08, MX16, MX32, MX48, and the MX60. Each unit may
contain up to the number of relays indicated. Enclosure sizes for each of the ve units will vary
Pictures of the MX08 and MX32 appear below showing the main components. Check each unit for shipping damage or missing
parts
Inspection
1) Power Supply and fuse
2) LTR Relays
3) High Voltage Sections
4) Low voltage section
5) Contactor space
6) LX5 main processor electronics
7) RIB relay interface board electronics (not
visible on MX08)
8) Surface mounted cover (MX08)
9) LEXP input expansion electronics
10) True lock screw
11) Ground nut
12) Surface mounted cover w/ hinged door
13) Removable, one-piece interior frame
MX32 cover
!
!
High Voltage
Section
High Voltage
Section 3
3
Low Voltage Section
4
12
13
2
1
6
MX08 Cover
MX32
MX08
13
1
!
High Voltage
Section 3
Low Voltage Section
4
2
67
10
11
5
9
8
11
11

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 6
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
Installation
Mounting the MX Series Enclosure
1. Knockout Holes for high and low voltage conduit connections. Below illustrates areas in the MX Series
enclosure where conduit holes for high and low voltage wiring can be made.
a. Remove the interior. If the panel was shipped with electronics installed, remove the interior with electronics until all holes for
conduit are punched and all metal shavings are removed. Metal shavings from drilling could lodge in the electronic components
and cause damage.
The interior is held to the enclosure by ange nuts. See picture below.
Remove the interior and place it away from any work area before drilling holes for conduit.
Interior
ange nuts
(May vary
with panel
size)
Mounting
Holes
(four total)
2. Mount the enclosure with anchors and screws according to picture above .
The picture on the right illustrates the location of the panel mounting holes. The top two mounting holes of the panel enclosure
are keyhole shaped so you can slide the unit over mounting screws, avoiding the need to hold the unit while trying to secure the
mounting screws. Use wall anchors capable of supporting 6lbs for MX08, 16lbs for MX32 and 25lbs for MX60.
If ush mounting, secure the enclosure between the wall studs. Be sure to allow for the thickness of the drywall and 7/8” for the
overhang of the cover so that the panel’s cover will mount ush on the nished wall and away from adjacent panels.

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 7
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
Connecting the Power Supply
The MX Series can be powered by either 120 or 277VAC. A fuse and dual primary transformer are utilized to offer maximum
exibility during installation. This factory mounted transformer powers the MX Series controller and associated low voltage
coils on the contactors (relays).
1. If connected, remove the power harness from the MX Series controller.See Figure 4 for location of the
harness on the controller. Remove the harness by lifting on the terminal block of the harness.
2. Connect main power to the transformer and fuse assembly. Locate the Common (white) wire and the hot
(black) wire for connection to main power. Figure 4 shows the connectors on the white and black wires.
Figure 4
Connectors for
power supply
Power harness
from transformer
(24VAC)

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 8
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
Connecting the Power Supply
Replace with 1.0A
Slow Blow Fuse Only!
Blue
Yellow
White - Common
Black - 120V
Brown - 277V
Transformer
Fuse
24V
Black - HOT
Select either 120 or 277V to HOT
Figure 5
3. Locate wire with correct voltage and connect to fuse. Refer to Figure 5. Power is connected by
choosing the proper voltage wire stemming from the transformer and connecting that wire to the fuse holder.
Each wire is labeled either 120V or 277V. The 120V wire should be black and the 277V wire should be brown.
If this is not the case contact the factory immediately. Each wire is terminated with a spade connector that inserts
over a contact on the fuse holder.

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 9
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
Fuse or Breaker
Figure 7
Lighting Load
Neutral
Fuse or Breaker
Hot
(size per
N.E.C.)
Maxiom Series
LTR Relay
Lighting Load
Maxiom Series
LTR Relay
Lighting Load
Maxiom Series
LTR Relay
Connecting Branch Circuit Wires
The MX Series panel is equipped with relay capable of switching up to 20 amperes at 277 VAC (Canadian versions, 347VAC). Each
relay can be easily assigned to any of the unit’s zones.
The following gure is a typical wiring diagram. Be sure not to exceed 20 amperes per relay. If the high voltage wiring requires both
120V and 277V on the same high voltage of the panel, a Lumisys MXDIV will be required.
WARNING! Disconnect high voltage power to all circuits before connecting them to the
MX Series. Failure to do so could result in serious injury.
!
Steps 1-2

www.anybas.com
Due to continuous product improvement, Lumisys reserves the right to change product specications without notice.
Page 10
Installation Guide
Mx Series
Lighting Relay Panel
0726070122
Lumisys is a Registered Trademark
1. Pull branch circuit wires through high voltage conduit. Note: All wiring should be in accordance with local
regulations and the National Electric Code. Control signal wiring to the low voltage side of the unit should not be run in the
same conduit as line voltage wiring or other conductors that supply highly inductive loads such as generators, motors, or
high voltage circuits located on the high voltage side of the unit.
If 120V and 277V branch wires must be connected to relays on the same side of the panel do not run these wire through the
same conduit. See Overview for high (load) and low (24V) voltage areas of the panel.
2. Install each branch circuit in one relay as shown in Figure 6. Each branch circuit can be installed in a
relay as shown in Figure 6 below.
Figure 6
Terminal opening to Circuit Breaker
Terminal opening to Lighting Load
Terminal opening to Circuit Breaker
Terminal opening to Lighting Load
Lumisys LTR Relay
The Lumisys LTR Relay
features manual override and
large gauge terminal block
capable of accommodating
#14-8 AWG or two 10 AWG
wires in each terminal opening.