Luxaire LX Series Guida rapida

Johnson Controls Ducted Systems
Luxaire Technical Guide: LX Series TCD2B
Models - 13.4 SEER2 Split-System Air
Conditioner - Single-Phase
R-410A - 1.5 to 5 Nominal Ton
York International Corporation, 5005 York
Drive, Norman, OK 73069
2022-11-04
6268887-LTG-A-1122
Supersedes: nothing

2 Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems

Contents
ContentsDescription........................................................................................................................................................ 7
Certification.......................................................................................................................................................7
Warranty summary.......................................................................................................................................... 7
Features.............................................................................................................................................................8
Nomenclature...................................................................................................................................................9
Physical and electrical data.............................................................................................................................9
Physical and electrical data notes......................................................................................................10
Illustration of dimensions............................................................................................................................. 11
Dimensions..................................................................................................................................................... 11
Dimensions data notes....................................................................................................................... 11
System charge table.......................................................................................................................................12
System charge A-coil data notes........................................................................................................12
Charging..........................................................................................................................................................13
Air handler capacity....................................................................................................................................... 13
Air handler capacity data notes......................................................................................................... 17
Coil only capacity............................................................................................................................................17
Coil only capacity data notes..............................................................................................................18
Furnace capacity - 1.5 ton..............................................................................................................................19
Furnace capacity - 2 ton.................................................................................................................................22
Furnace capacity - 2.5 ton..............................................................................................................................27
Furnace capacity - 3 ton.................................................................................................................................34
Furnace capacity - 3.5 ton..............................................................................................................................41
Furnace capacity - 4 ton.................................................................................................................................50
Furnace capacity - 5 ton.................................................................................................................................58
Furnace capacity data notes......................................................................................................................... 62
Applications and accessories........................................................................................................................63
Sound power rating....................................................................................................................................... 64
Mechanical specifications..............................................................................................................................64
Typical installation..........................................................................................................................................65
Typical field wiring......................................................................................................................................... 67
Alternative installation clearances............................................................................................................... 68
Performance data - 1.5 ton........................................................................................................................... 68
Condenser only performance data - 1.5 ton.................................................................................... 68
Condenser only performance data notes............................................................................................... 68
Cooling performance data - 1.5 ton.................................................................................................. 69
Cooling performance data notes............................................................................................................. 69
Multipliers for determining the performance with other indoor sections...................................69
Cool multiplier air handler - 1.5 ton.................................................................................................. 69
Cool multiplier furnace - 1.5 ton........................................................................................................ 70
Johnson Controls Ducted Systems
Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase 3

Performance data - 2 ton.............................................................................................................................. 74
Condenser only performance data - 2 ton....................................................................................... 74
Condenser only performance data notes............................................................................................... 74
Cooling performance data - 2 ton..................................................................................................... 75
Cooling performance data notes............................................................................................................. 75
Multipliers for determining the performance with other indoor sections...................................75
Cool multiplier air handler - 2 ton......................................................................................................75
Cool multiplier furnace - 2 ton........................................................................................................... 77
Performance data - 2.5 ton........................................................................................................................... 82
Condenser only performance data - 2.5 ton.................................................................................... 83
Condenser only performance data notes............................................................................................... 83
Cooling performance data - 2.5 ton.................................................................................................. 83
Cooling performance data notes............................................................................................................. 84
Multipliers for determining the performance with other indoor sections...................................84
Cool multiplier air handler - 2.5 ton.................................................................................................. 84
Cool multiplier furnace - 2.5 ton........................................................................................................ 85
Performance data - 3 ton.............................................................................................................................. 92
Condenser only performance data - 3 ton....................................................................................... 92
Condenser only performance data notes............................................................................................... 92
Cooling performance data - 3 ton..................................................................................................... 93
Cooling performance data notes............................................................................................................. 93
Multipliers for determining the performance with other indoor sections...................................93
Cool multiplier air handler - 3 ton......................................................................................................93
Cool multiplier furnace - 3 ton........................................................................................................... 95
Performance data - 3.5 ton......................................................................................................................... 103
Condenser only performance data - 3.5 ton.................................................................................. 103
Condenser only performance data notes............................................................................................. 103
Cooling performance data - 3.5 ton................................................................................................ 104
Cooling performance data notes........................................................................................................... 104
Multipliers for determining the performance with other indoor sections.................................104
Cool multiplier air handler - 3.5 ton................................................................................................ 104
Cool multiplier furnace - 3.5 ton...................................................................................................... 106
Performance data - 4 ton............................................................................................................................ 115
Condenser only performance data - 4 ton..................................................................................... 115
Condenser only performance data notes............................................................................................. 115
Cooling performance data - 4 ton................................................................................................... 116
Cooling performance data notes........................................................................................................... 116
Multipliers for determining the performance with other indoor sections.................................116
Cool multiplier air handler - 4 ton................................................................................................... 116
Cool multiplier furnace - 4 ton......................................................................................................... 118
Performance data - 5 ton............................................................................................................................ 126
Condenser only performance data - 5 ton..................................................................................... 126
Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase4
Johnson Controls Ducted Systems

Condenser only performance data notes............................................................................................. 126
Cooling performance data - 5 ton................................................................................................... 127
Cooling performance data notes........................................................................................................... 127
Multipliers for determining the performance with other indoor sections.................................127
Cool multiplier air handler - 5 ton................................................................................................... 127
Cool multiplier furnace - 5 ton......................................................................................................... 128
5Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems

6 Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems

Description
The TCD2B models are part of our successful 13.4 SEER2 Regional Minimum Efficiency in the
northern United States and Canada. These outdoor units are specifically designed to be matched
with our residential indoor coils, furnaces, and air handlers to provide a complete system solution.
Figure 1: Installation map
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.simplygettingthejobdone.com andwww.luxaire.com.Additional rating
information can be found at www.ahridirectory.org.
This document is only for distribution use - it is not to be used at point of retail sale.
Certification
Warranty summary
Standard 5-year limited parts warranty.
Standard 10-year limited compressor warranty.
Extended 10-year limited parts warranty when product is registered online within 90 days of
purchase for replacement or closing for new home construction.
Warranty does not apply to R-22 models, three-phase models, or Internet sales.
See the limited warranty certificate in the User's Information Manual for details.
7Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems

Features
•Small footprint - Minimum footprint for easier handling, transportation, and installation.
•Easier installation - Independent panels provide quick access for unit setup. Installation
time is reduced by easy power and control wiring access. Select indoor matches with factory-
mounted TXVs are available for quicker system installation. The filter-drier is shipped loose for
installation in the field. The unit is factory-charged for 15 ft refrigeration piping. The small base
dimension and reduced unit clearances make for easier retrofits.
•Accessible information - QR code on unit provides quick access to technical documents and
warranty information.
•Durable finish - The coated steel wire fan guard, coated external fasteners, and pre-
treated G90-equivalent galvanized steel chassis components resist corrosion and rust creep.
Champagne colored powdercoat paint further protects external panels.
•Quality coils - The high efficiency microchannel aluminum coil is manufactured using an
improved material system, providing reliable performance and small unit size.
•Rugged coil protection - Coils are protected from mechanical damage by a proven stamped
steel coil guard design.
•Protected compressor - Compressors are protected internally by a high-pressure relief valve
and a temperature sensor, and externally by the system high-pressure switch.
•Reliable operation - Ball bearing fan motors provide superior performance in extreme
temperatures.
•Environmentally friendly - CFC-free R-410A refrigerant delivers environmentally friendly
performance with zero ozone depletion.
•Top discharge - Warm air is blown up, away from the structure and any landscaping, allowing
compact location on multi-unit applications.
•Low operating sound levels - Developed using CFD and FEA tools, the sturdy cabinet and top
design provides sound performance of 76 dBA or lower. Compatible accessories for further
sound reduction are also available.
•Better service access - Diagonal base valves with open access for low-loss fittings, single
panel access to the electrical controls, swing out control box for full corner access, and
removable fan guard allow easy access for unit maintenance.
•Agency listed - Safety certified by CSA to UL 1995/CSA 22.2. Performance certified to ANSI/
AHRI Standard 210/240 in accordance with the Unitary Small Equipment certification program.
Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase8
Johnson Controls Ducted Systems

Nomenclature
Table 1: Nomenclature
Brand T T = as manufactured
Product type C C = air conditioner
Nominal series efficiency and staging D2 D2 = 13.4 (SEER2 - US northern region)
Refrigerant B B = R-410A
18 = 1.5 ton
24 = 2 ton
30 = 2.5 ton
36 = 3 ton
42 = 3.5 ton
48 = 4 ton
Nominal unit capacity (MBH) 18
60 = 5 ton
Staging S S = single-stage
T = two-stage
M = modulating
V = variable capacity
Refrigerant B B = R-410A
Voltage (voltage-phase-hertz) 2 2 = 208/230-1-60
1 = first generationGeneration (major revision) 1
2 = second generation
Factory option S S = standard (no options)
A = style AStyle letter (minor revision)
not used for ordering
A
B = style B
Physical and electrical data
Table 2: Physical and electrical data
Outdoor unit model TCD2B18S21S TCD2B24S21S TCD2B30S21S TCD2B36S21S TCD2B42S21S TCD2B48S21S TCD2B60S21S
Unit supply voltage 208/230 V, 1 phase, 60 Hz
Normal voltage
range (V)1
187 to 252
Minimum circuit
ampacity (A)
8.9 11.3 15.3 19.6 21.1 25.7 29.1
Maximum
overcurrent device
(A)2
15 15 25 30 35 45 50
Minimum
overcurrent device
(A)3
15 15 20 20 25 30 30
Compressor type4Rotary Rotary Scroll Scroll Scroll Scroll Scroll
Compressor rated
load
6.5 8.4 11.7 14.7 15.9 19.5 22.2
Compressor locked
rotor
33.0 53.0 71.3 75.0 112.3 130.0 128.0
Crankcase heater No No No No No No No
9Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase
Johnson Controls Ducted Systems

Table 2: Physical and electrical data
Outdoor unit model TCD2B18S21S TCD2B24S21S TCD2B30S21S TCD2B36S21S TCD2B42S21S TCD2B48S21S TCD2B60S21S
Factory external
discharge muffler
No No No No No No No
HS kit required with
TXV
No No No No No No No
HS Kit Part Number
(S1-2SA067*****)5
22006 22006 10106 10106 10106 10106 10106
Fan diameter (in.) 18 18 18 22 22 24 26
Fan motor type PSC PSC PSC PSC PSC PSC PSC
Fan motor rated HP 1/8 1/8 1/8 1/4 1/4 1/4 1/4
Fan motor rated load
(A)
0.7 0.7 0.7 1.3 1.3 1.3 1.3
Fan motor nominal
RPM
1075 1075 1075 850 850 850 850
Fan motor nominal
CFM
2150 2575 2575 2875 3350 3550 4300
Coil face area (sq. ft) 11.07 12.45 12.45 13.83 17.37 18.74 23.40
Coil rows deep 1 1 1 1 1 1 1
Coil fins per inch 23 23 23 23 23 23 23
Liquid refrigeration
piping outdoor unit
(field-installed)
3/8 3/8 3/8 3/8 3/8 3/8 3/8
Vapor refrigeration
piping outdoor unit
(field-installed)6
3/4 3/4 3/4 3/4 7/8 7/8 1 1/8‡
Unit charge (lb-oz)73-3 3-4 3-4 4-3 4-15 4-11 5-9
Charge (oz/ft) 0.62 0.62 0.62 0.62 0.67 0.67 0.75
Operating weight (lb) 120 135 130 150 195 200 230
Physical and electrical data notes
1. Rated in accordance with AHRI Standard 110-2012, utilization range A.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. Rotary compressor models are limited to an equivalent length of refrigeration piping of 100 ft
with no exceptions.
5. Refer to the Hard Start Kit Accessory Installation Manual for the hard start kit part number for
each model. The hard start kit is a field installed accessory.
6. For applications with non-standard vapor line sizes, refer to the Applications and accessories
section.
7. The unit charge is correct for the outdoor unit, smallest matched indoor unit, and 15 ft
of refrigerant tubing. For tubing lengths other than 15 ft, add or subtract the amount of
refrigerant, using the difference in actual refrigeration piping length (not the equivalent
length) multiplied by the per foot value.
‡ The adapter fitting must be field installed for the required 1 1/8 in. refrigeration piping.
Luxaire Technical Guide: LX Series TCD2B Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase10
Johnson Controls Ducted Systems
Altri manuali per LX Series
5
Questo manuale è adatto per i seguenti modelli
8
Indice
Altri manuali Luxaire Condizionatore d'aria

Luxaire
Luxaire LX Series Guida rapida

Luxaire
Luxaire R-410A Guida rapida

Luxaire
Luxaire ACCLIMATE AL6B024F3 Guida rapida

Luxaire
Luxaire K*BU060A Series Manuale utente

Luxaire
Luxaire ACCLIMATE AL21B2421S Guida rapida

Luxaire
Luxaire LX SERIES TW4B18 Guida rapida

Luxaire
Luxaire TC4B18 THRU 60 Guida rapida

Luxaire
Luxaire TCJD30 THRU 76 Guida rapida

Luxaire
Luxaire TC17B2421S Guida rapida

Luxaire
Luxaire Climasure PAC030 Guida rapida