MARK COLDSTREAM
0665020_R02
Livret technique FR
Technisch boek NL

2

3
EN
Read this document before
installing the appliance
1.0 General
1.1 All rights reserved
The manufacturer has a policy of continuous product improvement and reserves the right to make
changes to the specications without prior notice. The technical details are considered correct but
do not form the basis for a contract or warranty. All orders are accepted subject to the standard
terms and conditions of sale and delivery (which will be sent to you at your request).
1.2 General warnings
Installation must comply with the relevant local and/or national regulations. You must therefore
have the ColdStream installed by a professionally qualied installer in accordance with all applicable
national and international regulations. Faulty installation, adjustment, alteration, maintenance activity
or repair shall render the warranty void.
The machine is conforming to the following European Community Directives:
2006/42/EEC Machinery Directive
2006/95/EEC Low Voltage Directive
2004/108/EEC Electromagnetic Compatibility Directive
1.3 Presentation of the ColdStream Evaporative Cooler
To improve the summer microclimate inside a production unit, sales or other area, it is necessary
to ventilate the environment with frequent changes of fresh, ltered and possibly cool air. For large
areas such as industrial buildings, an air conditioning plant is frequently not adaptable due to the
great volume of air to be cooled and the thermal loads of processes to be neutralized, the necessary
amount of energy is very high and the cooling effect is reduced by the exhaust air extraction plant
and by frequent opening of the doors during normal activity.
Evaporative cooling plants that cool the air using a natural principle represent an optimal solution:
the air passes through special wet water lters, loosing part of its heat during the evaporation
process of the water and hence lowering the air temperature. The absence of refrigeration plants
reduces energy consumption to a minimum and enables great volumes of air to be treated for the
many air changes necessary.
Warning
Incorrect installation, adjustment, alteration, repair or maintenance work may lead to material
damage or injury. All work must be carried out by certied, qualied professionals. If the
appliance is not positioned in accordance with the instructions, the warranty shall be rendered
void. This appliance is not intended for use by children or persons with a physical, sensory or
mental handicap, or who lack the required experience or expertise, unless they are supervised
or have been instructed in the use of the appliance by somebody who is responsible for their
safety.Children must be supervised to ensure that they do not play with the appliance.

4
1.4 Foreseen use
The ColdStream evaporative cooler can be installed in all environments where it is necessary to
improve the microclimate, where the environment must be ventilated with frequent changes of
fresh, ltered and possibly cool air, such as:
• production buildings and units;
• sales areas and warehouses;
• sport areas such as gymnasiums.
It is absolutely forbidden to make modications to the machine and its destination of use.
The supplier declines all responsibility for any damages which may be, directly or indirectly, caused
to exposed persons or property, due to improper use or use of the machine for different purposes
other than the design purposes, incorrect installation, inappropriate power supply, different or
changes to the installation environment from the one declared during order conrmation, grave
deciency of maintenance, unauthorized alterations and modications, use of non-original spare
parts, removal of the protection guards, inobservance of the instructions for use, negligence, etc..
The machine must NOT be used for a different use than its designed use for any reason
whatsoever or used in a different way than stated in this manual.
DO NOT install the machine in closed areas; the machine must be installed outside the area to be
treated, except by specic approval of the manufacturer.
Do NOT start-up the machine if it is not connected to the relative plant (duct) of air distribution.
When the plant is operating, do not touch the fan – Mechanical danger.
It is forbidden to work on moving parts.
It is absolutely forbidden to install ColdStream evaporative cooling plants in potentially explosive
environments.
1.5 Machineidenticationdata
Machine identication data is shown on the warranty sheet supplied to the customer and is
enclosed in the documentation and on the machine identication plate.
If Technical Assistance or spare parts are required, always supply the machine model and serial
number.
1.6 Electrical boards
Any electrical boards supplied by Mark Climate Technology. are manufactured according to EN
60204/1 regulations.
It is absolutely forbidden to make modications to the electrical board.
!
!

5
EN
2.0 Transportation, handling, unpacking, storage
2.1 Delivery of the unit
When the unit is delivered, the customer MUST check the state of the goods.
Check the packaging and its contents, if damage due to transportation is found, make a reserve
for the damage on the shipping documents to be signed by the shipping agent and send a copy to
the supplier.
2.2 Transportation, handling and lifting
Take care when handling Evaporative Cooling units during unloading from the transportation
means, handle and position to avoid damages to the equipment.
Avoid contact with elements, which may damage the equipment.
The supplier declines any responsibility for damage caused during transportation, loading and
unloading of the evaporative cooling units.
2.2.1 Lifting with fork lift
Widen the forks as much as possible to balance the load. Dip the ends of the forks to avoid
damaging the bottom of the machine.
2.2.1 Lifting with cables
We suggest to attach the cables as shown, inserting spacers of an adequate length to prevent the
cables from damaging the casing when tightened.
Because of the heavy weight, TC models, when unpacked, are provided with punched brackets to
allow to lift them by using appropriate metal tubes.
!
!

6
Place the goods down with care, avoiding sudden movements or, worse, dropping the goods.
IT IS ABSOLUTELY FORBIDDEN to station under suspended loads and inside the movement area
of the lifting equipment.
When handling the units, use suitable means according the weights involved, as envisaged by EC
Directive 89/391 and subsequent amendments.
Lifting must only be carried out by qualied personnel.
2.3 Unpacking the equipment
Free items from the packaging material and collect the packaging to avoid potential danger of re and
suffocation of persons or animals.
Leave the machine on its packaging base until the installation to avoid damages.
Disposal of packaging materials must be conform to the regulations in force in the country of
destination where the evaporative cooling unit is installed.
2.4 Storage
During transportation and storage, make sure that the environmental temperature is between -10
and 50 °C. If the ColdStream evaporative cooling unit must be stored, make sure that the relative
humidity in the warehouse is between 5% and 90%.
3.0 Positioning and installation
3.1 General warnings
Before proceeding to install, make sure that each evaporative cooling unit has been unpacked and
checked for damage.
Positioning and installation of the evaporative cooling units must be carried out by qualied
personnel and by observing the laws in force in the country of destination.
3.2 Roof installation
Prepare and x an air inlet anged duct. The ange has to be of the
same dimension of the unit’s trunk duct ange.
The unit is equipped with a trunk of anged duct that will be xed to the
ange of the inlet duct prepared before.
3.2.1 TA Evaporative coolers
Position the evaporative cooler base to the inlet duct and x the two
anges (base duct ange-inlet duct ange) together by using provided
bolts.
It is recommended to insert some silicon paste between the two
anges to guarantee perfect insulation from external agents.
!
!
!
!

7
EN
Position and x the 4 coloumns at the cooling unit base by using provided
screws.
Check the tightness of the pump exible hose clamp.
Positioning and applying cooling pads. Maintain the groove (made on one
side of the pad) in the upper position and towards the external part of the
machine.
Insert the water distribution stripes into the pad grooves.
Check that stripes are well pressed down to the bottom of their seat.
Insert the water distributor into the pad grooves and make sure that the
water distributor rests in a uniform manner over the distribution stripes.
Maintain the hose-end tting on the side of the water pump. Make a hole
through the pads to allow the passage of the hose-end tting.
Connect the distributor
hose-end tting to the
exible hose coming from
the pump and x them with
an hose clamp.
Insert the grates on the sides and rear of the unit and x them by using
the clips provided. Do not assemble the front unit grate (connections/
components side). At rst insert the clips till to their rst “click” on
the two upper corners of the grate. Finally force the clips until they are
completely inserted so that they do not protrude from the cooling pads.
Position the cap without xing it to allow the front unit grate insertioning.
The cap must be lifted so the grate slots into its seat. Do not use clips to
x the front unit grate to facilitate any necessary maintenance operation.
Once the protection grates have been positioned, x the cup by using
supplied screws.

8
3.2.2 TC Evaporative coolers
Prepare and x an air inlet anged duct and a frame to hold
up the unit. The ange has to be of the same dimension of the
unit’s trunk duct ange.
The unit is equipped with a trunk of anged duct that will be
xed to the ange of the inlet duct prepared before and with
two side girders bars that will be xed to the prepared frame.
Verify that the frame is designed to well support the weight of
the machine, doesn’t cause vibrations and it must be perfectly
horizontal. If necessary to insert antivibration dumpers
between frame and the bars, this needs to be planned before
manufacturing the frame and consider to insert exible
couplings in the hydric connections.
Position the evaporative cooler on the inlet duct.
Fix the two anges (base duct ange-inlet duct ange)
together and the bars at the frame by using provided bolts.
We suggest to insert an outlet exible connection between
the two anges to avoid vibrations transmitted through the
ducts.
We suggest to insert silicone sealant between anges to
guarantee perfect insulation from external agents.
3.3 Notes
Inside the building, prepare the anchor points for the support chains of the air inlet duct. These must
be placed in a position to avoid excessive stress to the air inlet duct and make sure they are on the
same axis as the machine.
To anchor the unit to the ceiling or to the wall, use chains and accessories having the necessary
test certicates, made from zinc-plated steel or stainless steel and having a wire diameter of no less
than 3 mm or dimensioned for the weight to be supported, bear in mind safety margins imposed by
regulations.
Do not use aluminium alloy or similar components.
The ducts must be sized according to the ratings of the system and the characteristics of the fan.
Incorrect calculation of the size of the ducting may lead to a drop or an increase in output, causing
the activation of any safety devices in the system.
3.4 Connection to the power supply
Each unit must be connected to the power supply using an Omnipolar switch. The isolator must
have a distance between its contacts of at least 3 mm for each pole and must be placed in a position
that can be easily reached by the user. The electrical plant must be constructed according to the
regulations in force in the country where the machine is installed.
Connection to the power supply MUST be carried out by qualied personnel.
All components used to connect the power supply must be certied.
Before working on the power supply cables, make sure that power has cutted-off.
!
!
!

9
EN
Provide an efcient earth connection.
The unit is supplied with an electrical switch box for the connections, this is placed on the external
part of the unit. It contains a main power inlet switch and a domino for the remote control module
connection. The unit is supplied also with a remote control module to be installed inside the building.
For connection to the power supply, use a multipolar cable + T (earth) according to directives in
force.
Comfort line: For connection to the remote control device use shielded cable type 20 AWG - 5
poles with a minimum section of 0,50 sq. mm – Maximum length of 25 meters.
Basic line: For connection to the remote control device use multipolar cables according to directives
in force. Perform connections as shown on the wiring diagram enclosed in this manual or inside the
on-board electrical box.
It is absolutely necessary to maintain the polarity of the electrical phases and the numbers on the
wires/terminals.
3.5 Connection to the water supply
The ColdStream cooling unit is connected to the water supply by a 3/8” sleeve attachment found on
the lower part of the equipment, it is advisable to provide a water tap at the water inlet to run dry
the plant before winter.
Insert a sand lter in the water supply plant.
The water piping must guarantee a minimum capacity of 5 -10 Lt/minute at a pressure of 1.5 - 3 bars.
(maximum pressure allowed: 6 bars).
It is advisable to install the water piping inside the building, to protect it from freezing during winter,
otherwise, insulate it adequately.
It is advisable to use potable water, hardness not more than 27°f and not less than 7°f. If hardness is
more than 30°f, insert a water softener system into the water supply plant. Don’t use demineralized
water.
Proceed to connect the 3/8” connection to the main water supply.
DO NOT use excessive force on the sleeve during its connection to
the water supply.
The unit is also equipped with a Ø60 mm sleeve to discharge water.
Connect the supplied exible hose (on request for Basic line)
according to the situation found at the installation site as mentioned
further on, x the hose by using a hose clamp.
1st Situation: If a discharge system is present, connect the tube to the
dis-charge according to the regulations in force regarding hygiene in
the country where the unit is installed.
2nd Situation: If no discharge system is present, place the hose in the
best way avoiding any bends.
When connecting the discharge hose, DO NOT use excessive force
on the sleeve and make sure that the sleeve does not rotate.

4.0 Protection devices
4.1 Protection devices
To comply with the instructions of the European Community Directives, applicable to the unit
referred to in this use and maintenance manual, Mark Climate Technology has designed the safety
systems on the unit foreseen by the regulations in force.
4.2 Caution signs applied on the unit
DANGER: Risk of electric shock
MOVING MACHINERY
4.3 Clothing
The equipment is destined for installation in positions which cannot be directly reached by users
during normal operations and therefore particular prescriptions regarding clothing are not necessary.
4.4 Residual risks
It is forbidden to use water to clean electro-mechanical components
Electrocution danger
Pay attention to fan movement. Do not introduce arms or limbs.
Mechanical danger
4.5 Emergency situations
In case of emergency immediately turn the machine off and cut off the electrical circuit through the
omnipolar isolator switch, identify and solve the problem, contact Mark Climate Technology.
It is absolutely forbidden to use water to put out res, use exclusively powder or CO2 extinguishers.
5.0 Functioning notes
The functioning of the evaporative cooler is based on an important principle: It introduces big
quantities of fresh air into the building and removes hot exhausted air through doors, windows and
other openings. If the system is not able to expel the air volume introduced into the building, the
efciency would be compromised. INLET FRESH AIR = OUTLET HOT AIR: a very simple principle.
If the system is able to expel all the air introduced into the building, the system operates at the
highest efciency. The ideal condition is when, into the building, the air diffusers are positioned away
(better on the opposite side) from the openings (windows, doors, etc.) so the air passes through
the building while cooling it. Maximum efciency can be reached by adjusting the dimensions of
the window and door openings. Never close the openings: if they are closed, no changes of air will
occur, consequently reducing the cooling effect and increasing the relative humidity level inside the
building.