1. INSTALLING LOGS50
Make sure the working temperature it is within the boundaries of – 30ºC to
+85ºC. It is a wall mounting device with no need of additional accessories.
Device ingress protection: IP67 - IP68 depending on model. IP68 protection
for LOGS50 equipment is established in accordance with the following
criterion: depth in water up to 1 meter for a up to 2 hours.
If it is necessary to open the box, this must be always done in a dry
environment, so that when the device is closed there is no moisture inside.
Humidity in conjunction with abrupt thermal changes might cause damage in
the electronics.
Equipment performance might be altered during the installation process and
when manipulating. Next are shown critical aspects that must be kept under
controlled:
a. Concerning the enclosure: Ensure the enclosure is tightly closed.
The box is closed by making pressure on the lower part of the lid.
b. Regarding the antennas: Screw tightly the antenna to the RF
connector by using the proper wrenches.
c. Regarding signal connectors: Signal cables must go perfectly
screwed to the circular connector and where no cable be connected,
in its place, a cap must be firmly screwed on the connector.
QUICK GUIDE FOR INSTALLATION

2 | 50
Installation Manual LOGS50 EN_MI_090221
2. POWER SUPPLY
LOGS50 unit has its own internal power supply (lithium battery cells) for its
own operation in autonomous mode through whether lithium primary cells or
via rechargeable accumulators always depending of the model acquired.
Figure 1: LOGS50 models. Solar panel rechargeable and with primary battery cells
For these type of autonomous power, 2 3.6 VDC cells in series are required.
To do so, just insert the cells or the rechargeable accumulators in their
battery holders.
LOGS50 models with rechargeable accumulators has available an electronic
circuit for battery cell recharging connected to a solar panel.
Total capacity supported by the system is completed with the use of up to 4
cells paired in group of 2.
Single capacity: 2 cells on clip-holders 1 and 2.
1 + 2, place the batteries in the holders 1 and 2.
Double capacity: 4 cells on clip-holders 1 and 2, and 3 and 4.
1 + 2, place the batteries in the holders 1 and 2.
3 + 4, place the batteries in the holders 3 and 4.
Note: Always place either 2 or 4 cells with the distribution REMARKED.

3 | 50
Installation Manual LOGS50 EN_MI_090221
Figure 2: Equipment open showing the clip-holders and the lithium battery cells.

4 | 50
Installation Manual LOGS50 EN_MI_090221
IMPORTANT: Mind the polarity inscribed in the PCB when inserting the
batteries. It is advisable to protect with a piece of film the terminals and
retrieve it once the battery is placed.
Alternatively, to the batteries or rechargeable accumulators- Through the
COM-POW, it is available an external power input; Maximum supported
voltage: 15 VDC. Do not exceed that value! The user must employ a
regulated and stabilized power supply. Please pay attention to the wires of
the LOGSCP cable for proper wiring.
3. SIM CARD INSERTION AND NETWORK COVERAGE
Insert the µSIM card into the SIM holder provided for this purpose in a similar
way as done in cell phones.
The SIM holder consists of a spring retentor to facilitate the insertion and
releasing of the µSIM card.
Figure 3: GPRS-3G module and SIM holder.

5 | 50
Installation Manual LOGS50 EN_MI_090221
4. HARDWARE CONFIGURATION OF ANALOG INPUTS
The microswitches SW1, SW2, SW3, SW4 (AI0, AI1, AI2, AI3) allows the user
to make a hardware configuration enabling the input to work either 4-20 mA or
0-10 VDC.
Figure 4: Microswitches.
Figure 5: Microswitches SW1 & SW2 for AI0 & AI1.
Figure 6: Microswitches SW3 & SW4 for AI2 & AI3.

6 | 50
Installation Manual LOGS50 EN_MI_090221
5. VOLTAGE OUTPUT HARWARE CONFIGURATION
Microswitch SW5 allows the user to select between 24 VDC and 12 VDC output
mainly for analog sensor powering.
Figure 7: Microswitch SW5 for voltage output selection.
6. ANTENNA CONNECTION
Figure 8: SMA antenna connector.

7 | 50
Installation Manual LOGS50 EN_MI_090221
7. BLUETOOTH ACTIVATION
Placing a magnet near the location pinpointed for 1-2 seconds automatically
activates the BT communication (buzzer sounds).
Placing a magnet near the location pinpointed for over 6 seconds causes a
hardware reset within LOGS50 (buzzer sounds).
Figure 9: Magnet for BT activations & LOGS50 reset.
8. LOGS50 INSTALLATION POINT
Bear in mind the characteristics of the installation point and materials
surrounding it. I. e, whether it is or not a subterranean location, whether the
enclosing surrounding is metallic or not, etc. All these aspects may have
important influence in communication quality due to signal attenuations. For
cases such those, use external antennas outside the metallic surrounding
(metallic cabinets) and when subterranean locations place the antenna nearest
possible to ground level.
Figure 10: Equipment Locations to pay attention to.

8 | 50
Installation Manual LOGS50 EN_MI_090221
In order to achieve good reception conditions, avoid placing the unit inside
metallic enclosures and near to interference sources. Consider the usage of
cable extensions an external antenna when the reception or communications
proves to be weak or poor.
9. CONFIGURE LOGS50 UNIT WITH YOUR COMPUTER USING
THE APPLICATION “CONFIGURATOR PROGRAM CONF50”
Once LOGS50 is powered, approach a magnet to the REED switch
indicated on the enclosure with the symbol shown. A buzzer will sound in
the presence of the magnet. Keep the magnet close for 2-3 seconds. This
action will awake the BT module.
Figure 11: location to near the magnet.
Here are the steps to set a peripheral up on Windows 10. In this link, the
user will also find a way to manage the Bluetooth device
https://www.windowscentral.com/how-manage-bluetooth-devices-windows-
10.
The device will appear as “ILOGS-XXXX” (If password or PIN asked, enter
“1234”).
Figure 12: Add BT device.

9 | 50
Installation Manual LOGS50 EN_MI_090221
Figure 13: LOGS50 unit and PC paired.
Figure 14: LOGS50 and PC paired. BT ID: ilOGS-ED31.