MegaTec NetAgent Mini Manuale utente

NetAgent
UPS SNMPAgent
User’s Manual

User Guide for the NetAgent
Version 5.0
Firmware version 2.40
Copyright Information
Copyright © 2000-2008, Mega System Technologies, Inc.
All rights reserved.
Reproduction without permission is prohibited.
Technical Support and Contact Information
Mega System Technologies, Inc.
Tel: +886-2-87922060
Fax: +886-2-87922066
Web: www.megatec.com.tw

1
Contents
Chapter1. Introduction ________________________________________ 1
Section1. Features __________________________________________ 1
Section2. Applications _______________________________________ 2
2.1 NetAgent makes your UPS on the Internet____________________ 2
2.2 NetAgent Provides Shutdown Utilities________________________ 2
2.3 NetAgent II for Surrounding Monitoring_______________________ 2
2.4 When we need the NetAgent? _____________________________ 2
Section3. NetAgent Models ___________________________________ 4
3.1 NetAgent Models________________________________________ 4
3.2 Pictures of NetAgent_____________________________________ 5
3.3 NetAgent Package Contents_______________________________ 6
3.4 NetAgent II Out looking___________________________________ 6
3.5 NetAgent Mini Out looking ________________________________ 8
Chapter 2. NetAgent UPS Installation ____________________________ 9
Chapter 3. NetAgent, UPS and Network Connection _______________ 10
Section1. Install the NetAgent II with UPS and Network___________ 10
1.1 For External NetAgent II _________________________________ 10
1.2 For Internal NetAgent II__________________________________ 10
Section2. Install the NetAgent Mini with UPS and Network ________ 11
2.1 For External NetAgent Mini_______________________________ 11
2.2 For Internal NetAgent Mini _______________________________ 11
Chapter 4. Using Netility Setup IP.Update Firmware________________ 12
Section1. Install Netility _____________________________________ 12
Section2. Using Netility _____________________________________ 12
Chapter 5. UPS Web management by NetAgent___________________ 16
Section1. Introduction ______________________________________ 16
Section2. NetAgent UPS Web Interface ________________________ 17
2.1 Information ___________________________________________ 18
2.1.1 System Status______________________________________ 19
2.1.2 Basic Information ___________________________________ 20
2.1.3 Current Status______________________________________ 21
2.1.4 Remote Control ____________________________________ 22
2.1.5 Meter/Chart________________________________________ 23

2
2.1.6 Modem Status (For 3 Ports NetAgent II only)______________ 24
2.1.7 Environment Sensors-NetFeeler Lite ____________________ 25
2.2 Configuration__________________________________________ 26
2.2.1 UPS Configuration __________________________________ 27
2.2.2 UPS On/Off Schedule________________________________ 29
2.2.3 Network __________________________________________ 31
2.2.4 SNMP ____________________________________________ 34
2.2.5 Email_____________________________________________ 37
2.2.6 SMS _____________________________________________ 39
2.2.7 Modem (For 3 Ports NetAgent II only) ___________________ 41
2.2.8 WEB/Telnet________________________________________ 42
2.2.9 System Time_______________________________________ 43
2.2.9 NetFeeler Lite (For 3 Ports NetAgent II only)______________ 45
2.2.10 Language ________________________________________ 46
2.3 Log Information________________________________________ 47
2.3.1 Event Log _________________________________________ 47
2.3.2 SMS _____________________________________________ 49
2.3.3 Data Log__________________________________________ 50
2.3.3 Save Data Log _____________________________________ 52
2.4 Help_________________________________________________ 53
2.4.1 Help _____________________________________________ 53
2.4.2 About ____________________________________________ 53
Chapter 6. Telnet (Remote Monitoring) __________________________ 54
Section1. Introduction ______________________________________ 54
Section2. Telnet Configuration _______________________________ 54
Chapter 7. ClientMate - Windows Shutdown Utility ________________ 56
Section1. Install ClientMate __________________________________ 56
Section2. Using ClientMate __________________________________ 56
2.1 Config _______________________________________________ 57
2.2 Closed Files __________________________________________ 58
2.3 About________________________________________________ 59
2.4 Event log _____________________________________________ 59
2.5 IP address of connection_________________________________ 60
2.6 AC power status _______________________________________ 60
2.7 Battery Status _________________________________________ 60
2.8 Status History _________________________________________ 60

3
Chapter 8. SNMPView – Windows Based UPS Management System__ 61
Section1. Introduction ______________________________________ 61
Section2. System Requirements______________________________ 61
Section3. Install SNMPView__________________________________ 62
Section4. Using SNMPView __________________________________ 63
Section5. SNMPView Buttons ________________________________ 64
5.1 ENUMERATE(D)_______________________________________ 66
5.1.5 Browse Device _____________________________________ 67
5.1.6 Export Configuration_________________________________ 67
5.1.7 Import Configuration _______________________________ 68
5.1.8 Open archive Event Log______________________________ 69
5.1.9 Open archive Data Log_______________________________ 70
5.1.10 Quit_____________________________________________ 70
5.2 View(S) ______________________________________________ 71
5.2.1 Large Icons________________________________________ 71
5.2.2 Small Icons________________________________________ 71
5.2.3 Details____________________________________________ 72
5.2.4 Map Background ___________________________________ 72
5.3 Tools(P)______________________________________________ 73
5.3.1 Settings___________________________________________ 73
5.3.2 UPS Monitor _______________________________________ 76
5.3.3 UPS Management __________________________________ 79
5.4 System(S) ____________________________________________ 80
5.4.1 Event Log _________________________________________ 80
5.4.2 Data Log__________________________________________ 80
5.4.3 SNMP Option ______________________________________ 81
5.5 User(U) ______________________________________________ 82
5.5.1 Change Password __________________________________ 82
5.5.2 User Management __________________________________ 82
5.6 Help(H) ______________________________________________ 83
5.6.1 HTML Help ________________________________________ 83
5.6.2 About ____________________________________________ 83
Appendix - Update the firmware of NetAgent UPS _________________ 84

1
Chapter1. Introduction
Section1. Features
NetAgent is a new generation SNMP (Simple Network Management Protocol)
monitoring product. Not only could remote control the UPS and get the current
status of it, the NetAgent II –3Ports also could provide other functions, ex.
connect to Modem could make the monitoring possible when there is no
permanent connection to Internet. The NetAgent II – 3Ports could also been
used to connect to ‘NetFeeler Lite’, to get the temperature, humidity and water
conditions. To get the condition of Smoke detector, Gas detector, door and
window detector will also be possible.
This product is for “Contact Closure” and “RS232” interface UPS. The
communication protocol includes the Contact Closure, RS232[MegaTec],
RS232[Phoenixtec], SEC 2400, SEC 9600, Three Phase, Powerware, Smart
APC, EMERSON. And user could also provide their own protocol to build in.
NetAgent provides a simple and easy installation procedure. User only needs
to install the software of NetAgent CD on a Windows environment to configure
the IP address. All the other configurations could be accomplished in a Web
browser.
NetAgent also provides shutdown utility for different operating systems. It
could send out the shutdown command in different conditions. These
conditions include the AC power failure, Battery Low, Over Loading, Over
Temperature and scheduled shutdown. User could configure these conditions
to initiate a system shutdown event, and to avoid the abnormal power
disconnection of the system.
Features:
nProvide SNMP MIB to monitor & control UPS
oAuto-sense 10M/100M Fast Ethernet
pManage and configure via Telnet, Web Browser or NMS
qSupport TCP/IP, UDP, SNMP, Telnet, SNTP, PPP, HTTP, SMTP Protocol
rProviding easy setup and upgrade tools via MS-Windows, just a few
seconds to finish IP setting, about 1.5 minutes to upgrade firmware.
sSending both of SNMP TRAP and E-mail for events notification.
tAuto email daily UPS history report
uSend SMS for events notification
vMatches with shutdown software to protect computer’s file saving and shut
down safely
wNetAgent II – 3Ports : Environment Measurement (Optional Kits), External
modem dial in/out via PPP protocol.

2
Section2. Applications
2.1 NetAgent makes your UPS on the Internet
When the UPS install the NetAgent, the system manager could check each
and every UPS condition by a computer with Browser installed. The manager
could monitor and control the UPS by simply input the IP address of the
NetAgent which connects to the UPS. When there is a power abnormal
condition happeneds, the NetAgent could also send the trap information to the
system manager to take proper action.
2.2 NetAgent Provides Shutdown Utilities
When a computer on the network with the NetAgent utility installed, it could
locate all the NetAgent on the network. When the UPS of this NetAgent is in
AC failure condition or Battery Low condition, the operating system could close
all the files on the system, and perform a gracefully shutdown. This could avoid
system corrupt when a power disconnection happened.
2.3 NetAgent II for Surrounding Monitoring
3Port NetAgent II could be used to connect the surrounding monitoring utility,
NetFeeler Lite, to get the temperature/humidity/smoke/fire signals. These
informations could also be revealed on the NetAgent Web page. When there is
an abnormal condition happened, it could also be sent as a trap to the system
manager.
2.4 When we need the NetAgent?
nWhen we need to remote monitoring and controls the UPS conditions. For
example, the system manager could use the Internet to control all the UPS
conditions all over the country. When the shutdown utility is installed, the
shutdown utility could close all the files and shutdown the system when a
power abnormal condition happened.
oWhen we need to monitor surrounding conditions of the machine room,
warehouse, office, …etc. For example, the system manager could know the
temperature, humidity, smoke and water condition by using the NetAgent II-
3Ports version and NetFeeler Lite. The system manager could always know
these surrounding conditions by using a Web browser.

3
Fig.1 NetAgent connection Software
Fig.2 3 Port NetAgent II Diagram

4
Section3. NetAgent Models
3.1 NetAgent Models
NetAgent II Model
P/N Package Contents Internal/External 1/3 Ports 1/3 phases
CK504
CP504
1. 1Port Internal card
2. NetAgent Utility CD
3. User Manual Internal 1 Port 1 phase
BK505
BP505
1. 3 Port External Agent
2. NetAgent Utility CD
3. User Manual
4.M2501 Cable (for Contact
Closure UPS)
5.M2502 or M2505 Cable. (for
RS232 UPS)
6. M2506 Cable (for Modem)
7. 9V DC adapter
External
BK506
BP505
1. 3 Port Internal card
2. NetAgent Utility CD
3. User Manual
3. M2506 Cable (for Modem)
Internal
3 Ports 1/3 phases
NetAgent Mini Model
P/N Package Contents Internal/External 1/3 Ports 1/3 phases
DK520
DP520
1. Internal NetAgent Mini
2. NetAgent Utility CD
3. User Manual Internal
DK522
DP522
1. Enternal NetAgent Mini
2. NetAgent Utility CD
3. User Manual
4. 5.3V DC adapter
External
DK532
DP532
1.Enternal NetAgent Mini with LCD
Display
2. NetAgent Utility CD
3. User Manual
4. 5.3V DC adapter
External
1 Port 1/3 phases
Fig.3 NetAgent Models

5
3.2 Pictures of NetAgent
NetAgent II(BK,CK Series)
CK504
CP504
BK506
BP506
BK505
BP505
NetAgent Mini (DK,DP Series)
DK520, DP520 DK522, DP522 DK532, DP532
Fig.4 Pictures of NetAgent
Questo manuale è adatto per i seguenti modelli
12