DAMPING
Superimposed “noise” frequently occurs when
pressure measuring from e.g. burners, fans, etc.
It is possible to set different damping (time constant)
for the pressure sensor. On delivery MRP-2000 is
set to 3.5 seconds attenuation.
1. Open the cover.
2. On the midmost circuit board is a 2-way
miniature switch (DIL-switch) in the
left-hand lower corner.
3. Set the required damping option in
seconds as set out below.
4. Refit the cover.
PROGRAMMING
Hold down the PGM key for 3 seconds and the dis-
play will switch from the actual value to the first pa-
rameter P00 in the list of parameters. The list of pa-
rameters includes eight parameters, the first, P00,
can not be changed.
Browse through the list of parameters by pressing
the ¸¹ keys and this will display P00, P01, P02,
P03, P04, P05, P06 and P07.
Pressing the PGM key for the parameter in question
shows the set value.
The set value is changed by pressing PGM after
which the left-hand digit starts to flash. Use the ¸¹
keys to change digit and when the required digit is
shown, press the PGM key. The next digit to the
right will then start to flash and can be changed.
Continue along the entire row to the right and press
the PGM key. The unit responds by flashing the re-
quired value three times to acknowledge program-
ming has been successful.
Negative values are entered by pressing the ¹-key
repeatedly when programming the left most digit
displayed until the digit turns over from positive to
negative numbers. Remaining digits are then pro-
grammed as described above until the entire pa-
rameter value is entered.
Ongoing programming can be cancelled before the
last digit is completed by pressing the ESC key.
After programming a value you can return to the list
of parameters by pressing the ESC key.
Par.
no
Description Range Factory
default
P00 Programme ver-
sion
X.XX the current
programme
version, not
re-program-
mable
P01 Set point 1 -300..300 Pa
-3000..3000 Pa
-7500..7500 Pa
0Pa
0Pa
0Pa
P02 Set point 2 -300..300 Pa
-3000..3000 Pa
-7500..7500 Pa
0Pa
0Pa
0Pa
P03 Neutral zone 2..15 Pa
2..150 Pa
2..375 Pa
2Pa
20 Pa
50 Pa
P04 Pulse zone 1..75 Pa
1..750 Pa
1..1875 Pa
10 Pa
100 Pa
250 Pa
P05 Pulse length 200..3000 ms 500 ms
P06 Pulse separation
time
200..3000 ms 1000 ms
P07 Forced operation 0 = decrease,
1= increase
0 (decrease)
Set point value
Set point value 1 is programmed in P01 and Set
point value 2 in P02. Both set point values have the
same neutral zone and pulse zone.
Neutral zone
When the actual value lies in the neutral zone, the
controller gives no increase or decrease pulses.
The neutral zone is programmed in P03 and lies
symmetrical around the active set point value.
Pulse zone
When the actual value lies outside of the neutral
zone and in the pulse zone, the controller gives in-
crease or decrease pulses.
The size of the pulse zone is programmed on P04.
The pulse length is programmed in P05 and the
pulse separation time between pulses in P06. The
pulse zones are stated in Pa and lie above and be-
low the neutral zone with equal values (P04).
When the actual value is outside the pulse zone, the
controller gives a continuous increase or decrease
output signal.
Switching set point values
Switching between set point 1 and 2 is done by con-
necting power to terminal 3.
No power on terminal 3:
Set point 1 (P01) is activated.
Power on terminal 3:
Set point 2 (P02) is activated
Note ! Power on terminal 3 must be of the same
phase as connected on terminal 1.
This method permits, e.g. a stage burner to use dif-
ferent set point values for stage 1 and stage 2.
2
© AB MICATRONE 2006-02-09 [H:\ Apps \ Typeset \ Mima \ Mi-247gb_060209.vp]
Damping selection:
0,1 sec. 1,0 sec. 3,5 sec. 4,5 sec.
damping of the pressure measurement