Minco Tel:763.571.3121 • Fax:763.571.0927 • www.minco.com 3
8. Select“ProgramPassword”,andpressEnter.
9. Enter1111forpasswordbyusingtheuparrowandrightarrow. Thiswillenable
passwordprotectionfor the“Configuration Menu”option,inthemainmenu.
10. PressBacktoexitonemenulevel.
11. Select2.“Configuration”,andthenEnter.
12. Youwillseethepromptto enterthepassword. Enter1111andpressenter. You
willthenenter the configurationmenu.
13. Select2.“ChangeProgram”,and thenEnter.
14. LeavealloutputssettoN for“ReverseActingoutputs?”,thiswillcausealloutputs
tobedirectacting. PressEnter.
15. Set“Temperature Scale” to“F”fordegreesFahrenheit,byusingtheuparrow,then
pressEnter.
16. Set“Zoneto bedisplayedduringnormaloperation”to “Any”,thenpressEnter.
ThiswillallowtheusertochoosethezonethatwillbedisplayedontheCT224.
17. Set“Minutes ofAlarmSilencewhenakeyispressed” to1minute,thenpressEnter.
Thiswillcausethe alarmtoresound1minute aftertheoutputhasbeen tripped,if
thecurrentreadingisstillabovethetripsetting.
18. Set“Ifaninputfails” to“SoundAlarm”,thenpressEnter. Thiswillcausethealarm
tosoundiftheinputfails.
19. Set“Zone1Chooseinputtype:” tothe inputtype thathas beenconnected to
Zone1onthecontroller,thenpressEnter.
20. Set“Zone1Trip1:” to 85ºF, thenpressEnter.
21. Set“Zone1Trip1:Trip Over or Under”to“Over”,then press Enter.
22. Set“Zone1Trip1:Sound Alarmon trip” to“Yes”, thenpressEnter.
23. Set“Zone1Trip1:Outputs to trip:”to“Output1:Y”andtheotheroutputsleaveas
N,thenpressEnter.
24. Set“Zone1Trip1: UntripOutputsby”to“UsingHysteresis”,thenpressEnter.
25. Set“Zone1Trip1:SetHysteresis:” to “5”,thenpressEnter.