STATION CONTROLLER SC2000
Analog Output Option:
•Up to four Isolated 4-20mA Analog Outputs may
e ordered and used for VFD speed control or fo
telemetry.
Auxiliary Input Option:
•Up to four Isolated 4-20mA Auxiliary Analog
Inputs may be ordered and used for telemetry.
•Data may be read through the Serial Port.
Specifications:
•Input Power: 120 VAC ±10%, 13 VA max
•External Dimensions: 6.9” x 8.5” x 4.9”
•Agency Approvals: UL 508, CAN/CSA
•Ambient Operating Temperature:
Without Analog Outputs:
–20°C to +65°C (–4°F to +149°F)
With Analog Outputs:
–20°C to +50°C (–4°F to +122°F)
•Level Display: 3 Digit, 7 Segment LED
•Level Display Range: 0 – 255 feet
(Decimal Point Position is Selectable)
•Indicators: LED
•Color: White with Blue Lettering
•Relays: 6A @ 250VAC
•Level Analog Input: 4 – 20mA, 250ΩLoad,
Transient Protected
•Discrete Inputs: 24VDC, Transient Protected
•Power for Discrete Inputs: Unregulated 24VDC,
Transient Protected
•Power for Analog Input: Regulated 20VDC ±1V,
Transient Protected
•Analog Outputs: Isolated 4 – 20mA
Maximum Load Resistance: 600Ω
Each Output may be configured as the Speed
Reference for any of the Pumps, or set to follow
the Wet Well Level input
•Auxiliary Analog Inputs: Isolated 4 – 20mA,
250ΩLoad, Transient Protected
Ordering Information:
Part Number: SC2000 – X X
umber of Optional Analog Outputs:
0 = Zero Analog Outputs
1 = One Analog Output
2 = Two Analog Outputs
3 = Three Analog Outputs
4 = Four Analog Outputs
umber of Optional Auxiliary Analog Inputs:
0 = Zero Auxiliary Analog Inputs
1 = One Auxiliary Analog Input
2 = Two Auxiliary Analog Inputs
3 = Three Auxiliary Analog Inputs
4 = Four Auxiliary Analog Inputs
Applications:
•Simplex, Duplex, Triplex, or Quadraplex
•Fixed or Variable Speed Control
•Pump Down (Empty a Tank) or Pump Up (Fill a Tank)
Standard Features:
•All Setup Parameters Values may be viewed or changed from the
front of the unit
•Phoenix style connectors used
•Analog Level Input [4-20mA], Transient Protected
•20VDC power for analog Level Input Loop
•6 Amp Pump Call Relay outputs
•RS-232 Serial Port, Modbus RTU Protocol
•Wet Well Level Analog Input Zero and Span Adjustments
•High and Low Level Alarm Relays and Alarm Indication
•Adjustable Lag Pump(s) Delay
•Alternation Schemes – Menu Selectable:
-Standard Alternation
-Pump 1 Always Lead – Stays On with other Pumps
-Pump 1 Always Lead – Turns Off with other Pumps On
-Split Alternation – Pumps 1&2, and Pumps 3&4
-Fixed Sequence – Pump 1 Always Lead
-Stepped On/Off – Only One Pump Runs at a Time
Alternator Logic Skips Disabled Pumps
Remembers Lead Pump Position during Power Outage
•First On - First Off or First On - Last Off Alternation
•Timed [1 minute] Level Simulation
•Security Code Protected Parameter Setup
•18 Discrete Inputs that can be programmed for the following
functions:
-Pump disable with HOA in OFF, or pump fault
-External Alternator Selector Switch
-All pump disable – for connection to Phase Monitor
-Limit number of pumps called while on emergency power
-Alternation by External Time Clock
-Freeze wet well level during a bubbler tube purge
-Call pump last
-Float switch backup
-Low Level Pump Cutoff
-Bubbler System fault
-A variety of telemetry functions
•Status of Discrete Inputs may be viewed from front of controller
Variable Frequency Drive Control:
•VFD Speed Reference – The Controller must be ordered with a
Analog Output for speed control of each pump that will be on a VFD.
•Three setup parameters are provided to establish a Linear Wet Well
Level versus Pump Speed Curve.
•Pump Speed Clamp Logic – Will Not allow the VFD Speed
Reference to drop below the “VFD Minimum Speed” setup paramete
value.
•Pump Start Speed Boost Logic – If enabled, will temporally ramp the
Pump Speed Reference to 100%, to give the Check Valve a chance to
open.
•Call Pump Last Logic – The Controller will call pumps in the Bypass
Mode Last. (External circuitry must be connected to Discrete Inputs
on the Controller, to signal when a pump is in the Bypass Mode.)