P6
6.4 WARNINGSETTINGSRAN1
TheWarningresponsehasthreeusersettableparameters,
notingthattheTripValuemustbehigherthantheAlarm
value.IfyouwishtosettheTripValuelowerthanthecurrent
AlarmTripValue,reducetheAlarmvaluefirst.
RecommendedSetting(IEC60364‐5‐53)
SettheWarningvaluetoabout100/V(Bus).For
example,iftheBusVoltageis600V,initiallysetthe
Warningto100x600=60000=60k
Parameter Options/Comments SamplePages
Activate
Warning
Settings
SETTINGS>Warnings>Warning>CHANGE
EnterPasswordifrequested
Thescreendisplaysallcurrentsettings
Parametersbecomeselectable.
Warning
TripValue,
Ran1
Range:001–999k
MustbegreaterthantheAlarmTripValue
Setindividualdigits
Usetocyclethroughindividualdigits.
Usetoselectthenextdigit.
Forreference,thecurrentAlarmTripValue
appearsontheWARNINGTRIPpage
Iftheoperatorattemptstosaveaninvalid
value,thedevicewillofferthechoicetoTry
Again.
Warning
TripDelay
Range:0‐20seconds
TheTripDelayisthecontinuouslengthoftime
thattheIRmustremainbelowtheWarning
TripValue,priortoRelayandLEDactivation.
Tochangethesetting,press
tocycle
throughtheavailablevalues.
Warning
Activated
Relay
Options:Relay1orRelay2
Thedevicecontainstworelays:1&2.
ThedefaultWarningRelayisRelay1.
TheRelayactivateswhentheIRremains
continuouslybelowtheWarningTripValuefor
greaterthantheWarningTripDelayperiod.
PresstotoggletheRelaychoice.
TheWarningmayactivatethesamerelayas
theAlarm.
6.5 ALARMSETTINGSRAN2
TheAlarmresponsehasthreeusersettableparameters,
similartoWarning,notingthattheAlarmTripValuemustbe
lowerthantheWarningvalue.IfyouwishtosettheTrip
ValuehigherthanthecurrentWarningTripValue,increase
theWarningvaluefirst.Thesetupisasimilarprocessto
Warningsetup.
RecommendedSetting(IEC60364‐5‐53)
SettheAlarmvaluetoabout50/V(Bus).For
example,iftheBusVoltageis600V,initiallysetthe
Warningto50x600=30000=30k