NetPing 886A02 Manuale utente

[Docs] NetPing Converter 0-20mA, 886A02

[Docs] NetPing Converter 0-20mA, 886A02 -
2
Содержание
[ENG] [886A02] Introduction....................................................................................... 4
[ENG] [886A02] Limitation of Liability and Copyright ............................................... 5
[ENG] [886A02] Overview and Main Features ............................................................ 6
The External View of The Sensor ....................................................................................................... 6
Main features...................................................................................................................................... 6
[ENG] [886A02] Connectors and Indications Elements ............................................. 8
Front Panel ......................................................................................................................................... 8
Back Panel.......................................................................................................................................... 9
[ENG] [886A02] Installation and Connection ........................................................... 10
[ENG] [886A02] Loop/Sensor Connection to the Converter.................................... 12
Functions of the converter`s connectors....................................................................................... 12
General information......................................................................................................................... 12
The example of connection ............................................................................................................. 13
Equivalent circuit scheme of a meter input.................................................................................... 14
[ENG] [886A01] Delivery Package ............................................................................. 15
[ENG] [886A02] Warranty .......................................................................................... 16
[ENG] [886A02] Operating and storage conditions ................................................. 17
[ENG] [886A02] Additional Documents and Weblinks............................................. 18

[Docs] NetPing Converter 0-20mA, 886A02 -
–

[Docs] NetPing Converter 0-20mA, 886A02 -[ENG] [886A02] Introduction
[ENG] [886A02] Introduction
–
•
•
•
[ENG] [886A02] Introduction
This manualwill help you get acquainted with the specialities and features of theNetPing Converter 0-20mA,
886A02 model, get an idea of its functionality and technical characteristics and prepare the sensor for operation.
A User Guide is designed for network administrators and users, who set up or operate a device. To work with a
device properly, a user must have an idea about the principles of building and functioning of local networks as well
as possess the next knowledge and skills:
Basic knowledge in the area of local and global networks;
Basicknowledgeintheareaofarchitectureandprinciples of work of TCP/IP networks;
Basic knowledge in the area of architecture and principles of work of Ethernet networks.

[Docs] NetPing Converter 0-20mA, 886A02 -[ENG] [886A02] Limitation of Liability and Copyright
[ENG] [886A02] Limitation of Liability and Copyright
–
[ENG] [886A02] Limitation of Liability and Copyright
The information, contained in this document, can be changed by a manufacturer without a prior notice.Although
every effort was made to make the information in this document accurate and without errors, a manufacturer is not
liable for their possible presence and for the consequences that may result from the errors herein. A manufacturer is
not liable if supplied equipment, software and this user guide does not correspond to expectations of a user and
his/her opinion about where and how to use all the above.All copyrights on supplied devices, described in this User
Guide, as well as firmware and software of devices and this User Guide belong to NetPing global Ltd. Сopying,
replication and translation of this user guide to other languagesare not allowed without a prior written permission
of a rightholder. Copying, replication, changing, disassembling of provided software are not allowed without a prior
written permission of a rightholder. For the part of software that is provided in source codes, there is a separate
license agreement, which defines an order of its use and modification. Other trademarks used in this description
belong to corresponding rightholders.
Developer and manufacturer:
NetPing east Co Ltd.

[Docs] NetPing Converter 0-20mA, 886A02 -[ENG] [886A02] Overview and Main Features
[ENG] [886A02] Overview and Main Features
–
[ENG] [886A02] Overview and Main Features
The External View of The Sensor
Main features
Sensor Specifications Values
Сurrent measurement range -30...30 mA ±3%
Мoltage measurement range 0…30 VDC ±3%
Resistance measurement range 0…29999 Ohm ±3%
Current sensor connection type High side (positive polarity), Low side (negative polarity) drop on
the intrumental shunt up to 1V
Loop power supply Built-in 12V with short circuit current 100mA + 24V with output
current up to 30 mA
Power supply From the host device. "Hot" connection to the host is not
provided - it is allowed to reboot the host during the "hot"
connection
Operating Temperature Range -30 °С...+50 °С(without moisture condensation, at normal air
humidity)
Sensor dimentions 95 x 28 x 25

[Docs] NetPing Converter 0-20mA, 886A02 -[ENG] [886A02] Overview and Main Features
[ENG] [886A02] Overview and Main Features
–
Sensor Specifications Values
Sensor weight 70 g

[Docs] NetPing Converter 0-20mA, 886A02 -[ENG] [886A02] Connectors and Indications Elements
[ENG] [886A02] Connectors and Indications Elements
–
[ENG] [886A02] Connectors and Indications Elements
Front Panel
Element Function
GND Common connector
RS- / RS+ Current loop connectors
+12V Power connector +12V
+24V Power connector +24V

[Docs] NetPing Converter 0-20mA, 886A02 -[ENG] [886A02] Connectors and Indications Elements
[ENG] [886A02] Connectors and Indications Elements
–
Back Panel
Element Function
LP Loop power indicator
PWR Sensor power indicator
1W Host connector

[Docs] NetPing Converter 0-20mA, 886A02 -[ENG] [886A02] Installation and Connection
[ENG] [886A02] Installation and Connection
–
•
•
•
•
[ENG] [886A02] Installation and Connection
The converter can be mounted on a horizontal or vertical surface. There are mounting holes.
When you install the converter pay attention to the next restrictions:
Do not expose the converter to direct sunlight.
Do not install the converter near heat sources.
Do not open the converter case.
Avoid getting liquid on the converter particularly on the connectors.
The sequence of connection:
Step 1.
Remove the converter 886A02 from its packaging. Put it onto the place you need.
Step 2.
Connect the converter to the 1-wire port of the device (or through an extension-splitter) to which you are
connecting it. The host device must be disconnected at the time of connection, otherwise it can be rebooted.
Step 3.
Connect the sensor to the converter.