- 3 -
3. Name of each section
(Indication /Operation)
(Terminal)
① Mode SW (mode switch)
At normal monitoring time: set to [Normal] (assigned) side.
At address setting time: set to [AD Set] (address setting) side.
② Up (increment switch)
③ Down (decrement switch)
When 2 or more alarms sound, digital indication can be scrolled.
④ Sensor Address/Err. Code (detector address/error code)
To indicate digitally smoke detector address or error code.
⑤ Silence (audible sound stop switch)
To stop alarm sound of the Smoke Detector Control Panel.
⑥ Fault (trouble light: yellow)
To turn on at smoke detector line (L+, C-) fault/short circuit, at
smoke detector detachment and at smoke detector trouble time.
Fault is not latched at automatic reset.
⑦ Fire Alarm (fire light: red)
To turn on when 2 or more smoke detectors operate.
It remains ON until pressing Reset.
⑧ Detector Operated (1 detector operation light: red)
To turn on when 1 or more smoke detector operates.
It remains ON until pressing Reset.
⑨ Reset (reset switch)
To reset fire indication of operated smoke detector and the
Control Panel.
⑩ Power Indication (power supply light: green)
To turn on when [Power SW] (power supply switch) is
switched on at power supply time.
⑪ Power SW (power supply switch)
⑫ Earth Terminal
⑬ Detector Operated (1 detector operation signal transfer
terminal: no-voltage c contact).
⑭ Fire Alarm (fire signal transfer terminal: no-voltage c contact).
⑮ L+, C- (detector line connecting terminal).
⑯ DC24V or AC24V PowerLine (Power input terminal).
⑰ Fault (trouble signal transfer terminal: no voltage c contact).
⑱ R+, R- (reset input terminal).
Terminal to input reset signal when reset operation is carried
out externally.
* Please use round crimp terminal with insulation coating
(RAV1.25-3) when connecting wire to terminal block.