Nortech NanoQuest Lite Manuale utente

NanoQuest Lite Installation Guide
DOC0085_Issue1.0
Scope
This document explains the installation of the NanoQuest Lite product. This information is not
relevant to the standard NanoQuest product.
Before Installation
Check that the box contains the following items:
1 x NanoQuest Lite (2-part) unit
2 x mounting screws (No.6 x 1.25”)
1 x cover securing screw
2 x Master proximity cards
1 x varistor
1 x Mounting Template
You will also need unassigned proximity cards or card packs purchased separately.
The NanoQuest Lite requires a power supply of between 9 and 16V DC. We recommend that an
appropriate 12V DC power supply unit or mains adaptor is made available to supply power to the
NanoQuest Lite. The NanoQuest Lite requires less than 70mA at 12V.
Mounting the NanoQuest Lite
1) Identify a suitable location for the unit. It should
be located at a convenient height near to the
door that it controls. The unit is waterproof and
suitable for exterior use but it must not be used
for an exterior door without another means of
securing the door. (For example, a dead lock
secures the door at night with NanoQuest Lite
controlling access by staff during the day).
2) Use the supplied template to mark out the
positions of the holes for screw fixings and cable
access, and drill appropriate sized holes.
3) Remove the cover from the unit by inserting the
tip of a terminal screwdriver into the small slot
next to the screw hole at the bottom of the unit,
and pressing lightly to release the securing catch
while you separate the cover from the body at
the base.
4) Feed the cable through the wall and terminate it
either inside the PSU enclosure or in a suitable
tamperproof terminal box.
5) Secure the NanoQuest Lite to the wall.
6) Fit the cover and secure with the supplied
securing screw once the NanoQuest Lite has
been fully installed.
Wiring the NanoQuest Lite
Connect the unit as shown on the next page (always fit the varistor as close to the locking device
as possible). If a door strike is used and a door handle is left in use on the inside of the door,
connection to the free exit button may not be required.

NanoQuest Lite Installation Guide
DOC0085_Issue1.0
Connecting the NanoQuest Lite Using Normally Closed Contacts
Connecting the NanoQuest Lite Using Normally Open Contacts
Power Up and Confidence Check
Apply power to the unit and check that the LED’s glows red.
Present a Master Card once to the face of the unit and check that the buzzer gives two short beeps
and the LED’s blink green and then continue to flash red. Wait 30 seconds. The buzzer should give
two short beeps and the LED’s return to a steady Red.
Press the Free Exit Button, if fitted. The NanoQuest Lite will give a short beep, the lock will release
for 3 seconds and the LED’s change to green during this period. This indicates that the unit is
functioning correctly.

NanoQuest Lite Installation Guide
DOC0085_Issue1.0
Programming the NanoQuest Lite
Adding User Cards Individually
1) Present a Master Card, 2 short beeps will
sound and the LED will blink green and
then start to flash red slowly to show that
the unit is in programming mode.
2) Present each User Card to the unit in turn.
A short beep will sound when the card is
detected.
3) One you have presented all required
cards, present the Master Card again. The
unit gives 2 short beeps and the LED
returns to a steady red glow indicating that
it is in operating mode.
Adding a Batch of User Cards
1) Present a Master Card, 2 short beeps will
sound and the LED will blink green and
then start to flash red slowly to show that
the unit is in programming mode.
2) Present the Batch Card to the unit. A short
beep will sound when all cards have been
set (this may take several seconds).
3) Present the Master Card again. The unit
gives 2 short beeps and the LED returns
to a steady red glow indicating that it is in
operating mode.
All related user cards are now valid and will now release the lock when presented to the
NanoQuest Lite. Keep the Master Cards in a secure place.
Additional Settings
The Master Card can be used to set further functions. Each time you present the Master Card, the
unit steps to the next function (see the table below). Once you have adjusted the setting by
presenting the appropriate user cards, you can exit programming mode by presenting the Master
Card again.
Note: When in programming mode, the LED provides an indication of the mode/option that has
been selected by blinking red the number of times that correspond with the selection made.
For example, when in mode 8 (Silent Mode), the LED blinks 8 times followed by a pause.
The sequence is repeated the while the unit is in mode 8.
Programming
Function
Present
Master
Programming Options/Actions
Default
Value
1
Add user card(s)
Once
Present each card to make it a valid User card
2
Not Used
Twice
Feature not available
3
Delete card(s)
3 times
Present each card to delete it
4
Add 2nd Master
4 times
Present an unregistered card to make it a Master
5
Not Used
5 times
Feature not available
6
Not Used
6 times
Feature not available
7
Not Used
7 times
Feature not available
8
Silent mode
8 times
Off - present a User card once
On - present a User card twice
Off
9
Set relay strike
time
9 times
Present a User card once per second of strike time.
For 0.5 seconds present User card 11 times.
To select ‘latching’ mode present User card 12 times.
3 sec’s

NanoQuest Lite Installation Guide
DOC0085_Issue1.0
Operating the NanoQuest Lite
When a valid user card is presented to the reader in operating mode, the buzzer beeps once and
the strike relay operates. The LED glows green while the strike relay is active.
Wiring Information
Colour
Function
Red
+ve (9 to 16V DC, 100mA)
Black
Ground
White
Request to Exit button
Blue
Normally closed contact
Yellow
Relay common
Green
Normally open contact
Specifications
Number of users:
500
Door Open time:
0.5 to 10 seconds, plus Latch mode (e.g. for secure control of equipment)
Silent Mode:
Card detection is silent (does not affect programming and audible alarm).
Power requirements:
9-16V DC, 70mA (unit only)
Relay rating:
1A @30Vdc
Operating Temp:.
-20C to +55C
IP Rating:
IP65 - suitable for internal and external use
Read Range:
Up to 80mm, depending on Token used
Dimensions:
111 x 49 x 19 (H x W x D)
If you can’t find the information you require in this document, then please feel free to contact us on: