Media Converters
Installation
Guide

(Revised 2010-11-15)
2
Industrial Ethernet Switch Installation Guide
202MC-SC
202MC-ST
202MCE-SC-YY
202MCE-ST-YY
Where: YY = -15, -40, or -80

(Revised 2010-11-15)
3
Copyright, © N-TRON Corp., 2008
820 S. University Blvd., Suite 4E
Mobile, AL 36609, USA
All rights reserved. Reproduction, adaptation, or translation without prior written permission from N-TRON
Corp. is prohibited, except as allowed under copyright laws.
Ethernet is a registered trademark of Xerox Corporation. All other product names, company names, logos
or other designations mentioned herein are trademarks of their respective owners.
The information contained in this document is subject to change without notice. N-TRON Corp. makes no
warranty of any kind with regard to this material, including, but not limited to, the implied warranties of
merchantability or fitness for a particular purpose. In no event shall N-TRON Corp. be liable for any
incidental, special, indirect or consequential damages whatsoever included but not limited to lost profits
arising out of errors or omissions in this manual or the information contained herein.
Warning
Do not perform any services on the unit unless qualified to do so. Do not substitute unauthorized parts or
make unauthorized modifications to the unit.
Do not operate the unit with the top cover removed, as this could create a shock or fire hazard.
Do not block the air vents on the sides or the top of the unit.
Do not operate the equipment in the presence of flammable gasses or fumes. Operating electrical equipment
in such an environment constitutes a definite safety hazard.

(Revised 2010-11-15)
4
Safety Warnings
ELECTRICAL SAFETY
WARNING: Explosion hazardous, do not disconnect while circuit is live, unless area is known to be non-
hazardous.
WARNING: Disconnect the power cable before removing the enclosure top.
WARNING: Do not operate the unit with the top cover removed.
WARNING: Properly ground the unit before connecting anything else to the unit. Units not properly
grounded may result in a safety risk and could be hazardous and may void the warranty. See the
grounding technique section of this user manual for proper ways to ground the unit.
WARNING: Do not work on equipment or cables during periods of lightning activity.
WARNING: Do not perform any services on the unit unless qualified to do so.
WARNING: Do not block the air vents.
WARNING: Observe proper DC Voltage polarity when installing power input cables. Reversing
voltage polarity can cause permanent damage to the unit and void the warranty.
Power must be supplied by an isolating source, and a 0.5 A max rated UL recognized fuse must be installed
immediately before the unit.
LASER SAFETY (202MCE -40 and -80)
CAUTION: CLASS 1 LASER PRODUCT. Do not stare into the laser!)

(Revised 2010-11-15)
5
202MC & 202MCE Industrial Ethernet Media Converters
The 202MC and 202MCE Unmanaged Industrial Ethernet Media Converters support high speed layer 2
switching between ports.
The 202MC is a 2 port unmanaged media converter switch that has 1 RJ45 port and a multimode fiber optic
up-link port, capable of 2 Kilometers of 100 Mb communications without the use of repeaters.
The 202MCE is a 2 port unmanaged media converter that is similar to the 202MC, but with extended range.
The N-TRON 202MCE utilizes a singlemode fiber transceiver that is capable of up to 80 Kilometers of 100
Mb communications.
Both the 202MC and 202MCE utilize the IEEE compliant SC or ST duplex connector for fiber optic
communications. The 10/100Base-TX port utilizes an RJ45 shielded connector.
All N-TRON switches and media converters come housed in a steel ruggedized Din-Rail enclosure,
designed to withstand the most demanding industrial applications, and have been fully tested and certified at
industrial environmental extremes. All 200 Series units operate on 10-30VDC @ 0.2A.
Key Features
Full IEEE 802.3 & 100BASE-FX Compliance
Extended Environmental Specifications
Support for Full/Half Duplex Operation
LED Link/Activity Status Indication
Autonegotiation and Autosensing Speed and Flow Control
Up to 1.0 Gb/s Maximum Throughput
Industry Standard DIN-Rail Enclosure

(Revised 2010-11-15)
6
PACKAGE CONTENTS
Please make sure the Ethernet Switch package contains the following items:
1. 202MC/202MCE Ethernet Media Converter
2. N-TRON Product CD
Contact your carrier if any items are damaged.
INSTALLATION
Read the following warning before beginning the installation:
WARNING
The 202MCE unit contains a class 1 laser. Do not stare into the laser beam (fiber optic connector) when
installing or operating the product.
Never install or work on electrical equipment or cabling during periods of lightning activity.
Disconnect the power cable before removing the enclosure top.
Do not operate the unit with the top cover removed
UNPACKING
Remove all the equipment from the packaging, and store the packaging in a safe place.
File any damage claims with the carrier.

(Revised 2010-11-15)
7
202MC/202MCE HALF DUPLEX SETUP
While all RJ45 port uses Autonegotiation and Autosensing, the 202MC/202MCE Fiber Optic Port is
factory configured for full duplex operation. In the event half duplex operation is desired, follow these
steps:
1. Remove the Voltage Input Power Plugs.
2. Remove the top cover (8 screws).
3. Remove the jumper plug (JP1) from pins 1 and 2.
4. Replace the top cover.
5. Proceed with the installation.
Full Duplex = Pins 1 and 2 shorted.
Half Duplex = Remove jumper.
In order to verify the jumper settings have been set correctly, for units which have the N-View option turned
on, you should install N-ViewOPC Server software on a PC connected to the LAN. The software is freely
distributed on the ProductCD and our web site (http://www.n-tron.com/html/opc.html). Once N-ViewOPC is
installed, you should view the Ports Counter page to remotely monitor each connected port. You may find it
helpful to Copy [Alt]+[PrintScreen] the Port Counter information for each port and Paste [Control]+[V] into a
Windows document for further review. Please consult your N-View OPC Server Manual for additional
information.

(Revised 2010-11-15)
8
DIN-Rail Mounting
Install the unit in a standard DIN-Rail. Recess the unit to allow at least 5” of horizontal clearance for fiber optic
cable bend radius. Note: This unit may be mounted horizontally or vertically.
To install the unit to 35 mm industrial DIN-Rail - Place the top edge of the included mounting bracket on
the back of the unit against the top flange of the DIN-Rail at a 15° angle. Rotate the bottom of the unit to the
back (away from you) until it snaps into place.
To remove the unit from the 35 mm industrial DIN-Rail - Apply downward force to the unit until it
disengages from the bottom of the unit from the DIN-Rail. Then, rotate the unit approximately 15° upward
and towards you to completely remove the unit.
Optional Mounting
With the exception of the 524TX and 526FX2, all N-Tron™ products are designed to be mounted on
industry standard 35mm DIN-Rail. However, DIN-Rail mounting may not be suitable for all applications.
We offer two alternative mounting solutions.
Our 900 Panel Mount Assembly (P/N: 900-PM) may be used to securely mount our 100, 200, 300, 400,
500, or 900 Series products to a panel or other flat surface.
Our Universal Rack Mount Kit (P/N: URMK) may be used to mount our products to standard 19" racks.

(Revised 2010-11-15)
9
FRONT PANEL
From Left to Right:
LNK Link LED for Fiber Optic Port
TX Fiber Optic Transmit Port
RX Fiber Optic Receive Port
ACT Activity LED for Fiber Optic Port
RJ45 PortAuto sensing 10/100BaseT Connections
! Red LED indicates controller error
Green LED lights when Power is connected
NOTE: The RJ45 data port has two LED’s located at the top of the connector. The left LED indicates
LINK status, and the right LED indicates ACTIVITY.
LED’s: The table below describes the operating modes:
LED
Color
Description
GREEN
Power is Applied
OFF
Power is OFF
!
RED
Controller HW Error
OFF
No Errors. Normal Operation.
LNK
GREEN
Link between ports established
OFF
No Link between ports
ACT
GREEN
Data is active between ports
OFF
Data is inactive between ports

(Revised 2010-11-15)
10
APPLYING POWER (Side View)
Unscrew & Remove the DC Voltage Input Plug(s) from the side header
Install the DC Power Cables into the Plug(s) (observing polarity).
Plug the Voltage Input Plug(s) back into the side header.
Tightening torque for the terminal block power plug is 0.22 Nm/0.162 Pound Foot.
All LED’s will flash ON Momentarily (including the Error LED)
Verify the Power LED stays ON (GREEN).
Verify the Error LED is OFF (after a few seconds).
Note: Only 1 plug is required to be connected to power input for minimal operation. For redundant
power operation, V1and V2plugs must be connected to separate DC Voltage sources. Use wire sizes
16-28 gauge.
Recommended 24V DC Power Supplies, similar to
100VAC/240VAC:
N-Tron’s NTPS-24-1.3, DC 24V/1.3A
Questo manuale è adatto per i seguenti modelli
10
Indice
Altri manuali Ntron Convertitore multimediale

Ntron
Ntron 1002MC-LX-YY Istruzioni per l'installazione e il funzionamento

Ntron
Ntron 102MC Istruzioni per l'installazione e il funzionamento

Ntron
Ntron SER-485-1C Manuale utente

Ntron
Ntron 102PC-SE Istruzioni per l'installazione e il funzionamento

Ntron
Ntron 202MC Manuale utente

Ntron
Ntron 302MC-SC Manuale utente

Ntron
Ntron SER-485-FXC Manuale utente