OBO Bettermann isCon Series Guida utente

01/2018 EN
isCon®
System instructions
Building Connections

© 2018 OBO Bettermann GmbH & Co. KG
Reprinting, even of extracts, as well as photographic or electronic reproduction are prohibited!
isCon® is a registered brand of OBO Bettermann GmbH & Co. KG
OBO isCon
®
System instructions

System instructions OBO isCon®EN | 3
Table of contents
Table of contents
1 About these instructions . . . . . . . . . . . . . . . . . . . . .5
1.1 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Using these instructions . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Types of safety information . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 Declaration of conformity . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.6 Basic standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 General safety information . . . . . . . . . . . . . . . . . . . .7
3 Product description . . . . . . . . . . . . . . . . . . . . . . . .8
3.1 Basic principles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 isCon® conductor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Insulated air-termination rods . . . . . . . . . . . . . . . . . . . . . . 12
3.4 System accessories for fastening . . . . . . . . . . . . . . . . . . . . 14
3.4.1 Air-termination rod stand . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4.2 Air-termination rod support for isFang mounting . . . . . . . . . . . . . . . . . 17
3.4.3 Holder for the isCon® conductor . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.5 System accessories for connection . . . . . . . . . . . . . . . . . . . 19
4 Planning an installation. . . . . . . . . . . . . . . . . . . . . 20
4.1 Schematic diagram of the isCon® system using the example of the
isCon® ProPl 75 SW . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2 Calculating, checking and maintaining the separation distance . . . . 23
4.3 Cable lengths and lightning protection classes . . . . . . . . . . . . . 23
4.4 Installation in potentially explosive areas . . . . . . . . . . . . . . . . 25
4.5 Soft-covered roofs . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5 Installing the isCon® system . . . . . . . . . . . . . . . . . . 28
5.1 Cutting and removing the insulation of the isCon® conductor . . . . . . 28
5.1.1 Removing the light grey protective jacket (isCon® ProPI 75 LGR) . . . . . . . . 28
5.1.2 Revealing the copper core for connection . . . . . . . . . . . . . . . . . . . . 29
5.2 Mounting the isCon® connect connection elements . . . . . . . . . . 30
5.2.1 Air-termination rod with internal isCon® conductor . . . . . . . . . . . . . . . . 32
5.2.2 Air-termination rod with external isCon® conductor . . . . . . . . . . . . . . . . 38
5.3 Fastening the air-termination rod in the air-termination rod stand . . . 42
5.3.1 Mounting the concrete plinth . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.3.2 Erecting the air-termination rod stand . . . . . . . . . . . . . . . . . . . . . . 42
5.3.3 Fastening the air-termination rod in the air-termination rod stand . . . . . . . . 45
5.4 Fastening the air-termination rod to pipes, a wall or T support . . . . . 47
5.5 Routing the isCon® conductor. . . . . . . . . . . . . . . . . . . . . . 48
5.6 Attaching the potential connection . . . . . . . . . . . . . . . . . . . 49
5.6.1 Installing the potential connection on an insulated air-termination rod . . . . . . 49
5.6.2 Installing the potential connection on the end of the isCon® conductor . . . . . 52
5.6.3 Including the air-termination rod stand in the functional equipotential bonding . 54
5.6.4 Installing additional potential connections . . . . . . . . . . . . . . . . . . . . 55
5.6.5 Creating additional equipotential bonding for isCon® ProPlus in potentially
explosive areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

OBO Bettermann
4 | EN
Table of contents
6 Mounting variants . . . . . . . . . . . . . . . . . . . . . . . . 58
6.1 Separate lightning protection ring conductor . . . . . . . . . . . . . . 58
6.2 Metallic roof parapet . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6.3 Internal and external isCon® conductor . . . . . . . . . . . . . . . . . 61
6.4 Lightning protection class I . . . . . . . . . . . . . . . . . . . . . . . 62
6.5 isCon® conductor included in the ring conductor . . . . . . . . . . . . 63
7 Checking the lightning protection system . . . . . . . . . . 64
8 Testing report for the OBO isCon® system . . . . . . . . . . 65

System instructions OBO isCon®EN | 5
About these instructions
1 About these instructions
1.1 Target group
These mounting instructions are intended for specialists, who are quali-
fied to erect lightning protection systems, e.g. lightning protection spe-
cialists. These specialists must know the lightning protection standards
applicable at the mounting location, as well as the generally recognised
rules of technology.
1.2 Using these instructions
• These instructions are based on the standards valid at the time of
compilation (January 2018).
• Before commencing work, read these instructions through once com-
pletely. In particular, please observe the safety instructions.
• Keep all the documents supplied with the isCon® system safe, so that
the information is available should you need it.
• We will not accept any warranty claims for damage caused through
non-observance of these instructions.
• Regional and seasonal factors were not taken into account.
• To find out more about planning and installation using the OBO isCon®
system, we recommend a comprehensive training course.
1.3 Types of safety information
WARNING
Type of risk!
Shows a possibly risky situation. If the situation is not avoided, then death
or serious injury may result.
CAUTION
Type of risk!
Shows a possibly risky situation. If the situation is not avoided, then light
or minor injury or damage to property may result.
ATTENTION
Type of risk!
Shows a possibly hazardous situation. If the situation is not avoided, then
damage to the product or the surroundings may occur.
Note! Indicates important information or assistance!

OBO Bettermann
6 | EN
About these instructions
1.4 Correct use
The OBO isCon® system is a lightning protection system for the external
lightning protection of buildings and systems, which, in the case of direct
lightning strikes, can arrest the lightning surge currents into the earth,
thus protecting the building, the system and people against the impacts of
the lightning strike, e.g. fires, mechanical building damage and possibly
lethal voltages and current pulses.
The system is not designed for any other purpose than the one described
here. If the system is installed and used for another purpose, any liability,
warranty or damage claims shall be rendered null and void.
If you require information on the use of the OBO isCon® system for some-
thing other than under the conditions of use described here, please speak
to your OBO contact.
1.5 Declaration of conformity
Lightning protection components are not subject to an EU directive.
Instead, OBO makes the manufacturer's declarations of conformity avail-
able for the appropriate components of the lightning protection systems.
These declarations of conformity certify the agreement with the named
standards and stored documents, but do not, however, contain any guar-
antee of properties.
You can find individual proofs for lightning protection components on the
OBO web pages (www.obo-bettermann.com).
1.6 Basic standards
Comply with the following standards*, amongst others, during the plan-
ning, mounting, maintenance and repair of lightning protection systems:
• DIN EN 62305-1 (IEC 62305-1, VDE 0185-305-1), Protection against
lightning Part 1: General principles
• DIN EN 62305-2 (IEC 62305-2, VDE 0185-305-2), Protection against
lightning Part 2: Risk management
• DIN EN 62305-3 (IEC 62305-3, VDE 0185-305-3), Protection against
lightning ‒ Part 3: Protection of structural facilities and persons
• DIN EN 62305-4 (IEC 62305-4, VDE 0185-305-4), Protection against
lightning ‒ Part 4: Electrical and electronic systems within structures
• DIN EN 62561-1 (IEC 62561-1, VDE 0185-561-1), Lightning protection
system components – Part 1: Requirements for connection compo-
nents
• DIN EN 62561-2 (IEC 62561-2, VDE 0185-561-2), Lightning protection
system components – Part 2: Requirements for conductors and earth
electrodes
• DIN EN 62561-4 (IEC 62561-4, VDE 0185-561-4), Lightning protection
system components – Part 4: Requirements for conductor fasteners
• DIN 18014, Foundation earthers
• IEC TS 62561-8 (draft)
* Date of standards: January 2018

System instructions OBO isCon®EN | 7
General safety information
2 General safety information
Observe the following general safety information on handling the OBO
isCon® system:
• The work may only be carried out by lightning protection specialists,
who have been trained for the installation of standard-conformant
lightning protection systems.
• If there is a lightning strike, lethal currents can flow through the light-
ning protection system. Never work on the elements of the lightning
protection system during a thunderstorm or if there is a risk of one.
• Lethal voltages can occur during the handling of electrical resources.
Therefore, never work on parts through which power is flowing. Wear
suitable protective clothing and comply with all the required safety
guidelines!
• To install the OBO isCon® system, use only components of the OBO
product range, as otherwise there is no guarantee that safe installation
is possible.
• Only the jacketing of the grey OBO isCon® conductor may be painted a
different colour, as it does not possess any electrical properties which
could be at risk from paint.
• The production method means that metallic objects may have areas
with sharp edges. Wear suitable protective gloves to avoid cutting
injuries.
• When erecting function maintenance systems, take the necessary fire
protection regulations into account. These instructions do not mention
any fire protection standards which are to be complied with. Read the
OBO fire protection guide (article number: 9134859) for more informa-
tion.

OBO Bettermann
8 | EN
Product description
3 Product description
3.1 Basic principles
Without any additional countermeasures, the high-voltage pulses which
occur when there is a direct lightning strike will cause arcing to insula-
tion surfaces. This effect is termed a creep flashover. When the so-called
creep discharge inception voltage has been exceeded, surface discharge
is initiated, which can bridge a gap of several metres. To avoid dangerous
arcing between conductive parts (electrical systems, pipelines, etc.), the
maintenance of the separation distance is a key requirement when plan-
ning and implementing a lightning protection system.
These days, the roof level of building complexes is used as an installation
area for air-conditioning, ventilation, transmission and energy collection
systems, meaning that the structural features may be in the way of the
required spacing between the air-termination systems and the electrical
installations.
The isCon® insulated lightning protection system is used to maintain the
required separation distance. Depending on the design, after the first
potential connection behind the connection element on the air-termination
rod, the isCon® conductor reflects an equivalent separation distance of
up to 0.45‒0.9 metres in the air or double that in solid matter. This means
that installation is possible directly on metallic and electrical structures. If
there is a direct lightning strike, the incoming energy is arrested through
the isCon® conductor to the building's earthing system. There is no direct
arcing between the down-conductor and the building to be protected.
The isCon® system has a tested arresting capacity of 150‒200 kA light-
ning surge current (10/350 μs). It primarily consists of the following com-
ponents:
– isCon® conductor
– Insulated air-termination rods
– System accessories for fastening (air-termination rod stand, support
and holder)
– System accessories for connection
3.2 isCon® conductor
According to DIN EN 62305-3/VDE 0185-305-3/IEC 62305-3, the insu-
lated isCon® conductor implements a separation distance of 0.45‒0.9
metres in the air and 0.9‒1.8 metres in the case of solid mater-
ials, depending on the product design. The isCon® conductor is equipped
with an external semi-conductive jacket, allowing it to limit high lightning
voltage pulses against a reference potential, by creating a connection be-
tween the external semi-conductive jacket and the building's equipotential
bonding, which is not energised with lightning current, in the area of the
connection element.
The isCon® conductor is flame-resistant according to DIN EN 60332-1-2,
weather-resistant and halogen-free. It is suitable for routing in external
areas and can be routed on roofs, in walls, in concrete, in facade installa-
tions or in buildings.

System instructions OBO isCon®EN | 9
Product description
The isCon® conductor is sold by the metre and in five variants:
Conductor type Characteristic Item number
isCon® PR 90 SW (Premium) Black 5408 018
isCon® Pro 75 SW Black 5408 008
isCon® ProPl 75 SW Black 5408 002, 5408 004,
5408 006
isCon® ProPl 75 LGR Light grey 5407 995, 5407 997
isCon® BA 45 SW (Basic) Black 5408 014
Table 1: Product variants, isCon® conductor
The light grey isCon® conductor is also suitable for routing in the earth. It
can also be painted, e.g. with the paint of the facade. As the external light
grey protective jacket is non-conductive, it must be removed in the contact
areas.
35 mm²
Ø 23 mm
Ø 26 mm
1
2
3
6
5
4
Figure 1: Schematic diagram of the isCon® conductors ProPl 75 SW and
ProPl 75 LGR
35 mm²
x
x = Ø 20 mm
(Pro 75 SW/BA 45 SW)
x = Ø 23 mm
(PR 90 SW)
1
2
3
4
Figure 2: Schematic diagram of the isCon® conductors Pro 75 SW, BA 45 SW
and PR 90 SW
Legend:
1
Round conductor, multi-wire, 35 mm2, Cu
2 Inner conductive layer
3
Insulation
4 Outer conductive layer
5
External jacket
6
External jacket, light grey

OBO Bettermann
10 | EN
Product description
The isCon® conductor may only be connected to air-termination rods or
forwarding systems using system-tested connection elements (see also
“„5.2 Mounting the isCon® connect connection elements“ on page 30).
Type isCon® BA 45
SW
isCon® Pro 75
SW
isCon® ProPl 75
SW
isCon® ProPl 75
LGR
isCon® PR 90
SW
Colour Black Black Black Light grey Black
Equivalent separation distance,
air (cm)
≤ 45 ≤ 75 ≤ 75 ≤ 75 ≤ 90
Equivalent separation distance,
solid materials (cm)
≤ 90 ≤ 150 ≤ 150 ≤ 150 ≤ 180
Equivalent separation distance,
mixed materials See EN 62305-3
External diameter ~ 20 mm ~ 20 mm ~ 23 mm ~ 26 mm ~ 23 mm
Round conductor, multi-wire, Cu 35 mm2
Conductor weight ~ 0.570 kg/m ~ 0.570 kg/m ~ 0.694 kg/m ~ 0.868 kg/m ~ 0.666 kg/m
Temperature range for routing min. -5 °C, max. 40 °C
Operating temperature min. -30 °C, max. 70 °C
Bend radius min. 200 mm min. 200 mm min. 230 mm min. 260 mm min. 230 mm
Maximum tensile load 1 750 N
Routing in the earth No No No Yes No
Can be painted No No No Yes No
Weathering resistance (UV-
stabilised)
Ozone resistant according to DIN EN 60811-2-1 Section 8
Sunlight resistance test according to UL 1581 Section 1200
Coldness impact resistance according to DIN EN 60811-1-4 Section 8.5
Fire load (kWh/m) 3.3 4.3 5.1 4.2
Lightning current carrying
capacity (class/Iimp (kA)
H1/150 H1/150 H1/150 H2/200
Testing certificate according to
IEC TS 62561-8 Yes
Halogen-free Yes
Softener None
Table 2: Technical data of the isCon® conductors