Acr Pro air curtains Operation and Maintenance Documentation
5. HEAT OUTPUT RANGES
Air curtains with water heater 1500H and 2000H
Air curtains with electric heater ACR Pro 1500E and 2000E
No current on coil surface
Lower temperature on coil surface in comparison to old type of electric heaters (for
ex. electric wires), long life solution
Large space of PTC coil, enhanced energy exchange between coil and air.
No risk of system overheat, thanks to „self cooling” option (coil automatically decreas-
Very low energy consumption
ACR Pro industrial air curtians are equipped with modern and safe solution based on PTC electric heaters.
PTC are thermistors which means that along with the temperature increase the resistance of the heating element increases as well.
ACR Pro 1500H
inlet/outlet water temperature 60/40 70/50 80/60 90/70
inlet air temperature 0 5 10 15 20 0 5 10 15 20 0 5 10 15 20 0 5 10 15 20
Airow: 6500 m3/h
heat output [kW] 18,3 16,2 13,7 11,3 8,6 23,5 21,3 19,1 17,0 14,8 28,0 25,8 23,7 21,5 19,3 32,5 30,4 28,2 26,0 23,8
outlet air temperature [°C] 8,2 12,3 16,2 20,1 23,8 10,6 14,6 18,6 22,6 26,6 12,6 16,6 20,6 24,7 28,7 14,6 18,7 22,7 26,7 30,7
water ow [m3/h] 0,8 0,7 0,6 0,5 0,4 1,0 0,9 0,8 0,8 0,6 1,2 1,2 1,0 0,9 0,9 1,4 1,3 1,3 1,2 1,0
pressure drop [kPa] 2,3 1,8 1,3 0,9 0,9 3,6 3,0 2,4 2,0 1,5 4,9 4,2 3,6 3,0 2,5 6,4 5,7 4,9 4,2 3,6
ACR Pro 2000H
inlet/outlet water temperature 60/40 70/50 80/60 90/70
inlet air temperature 0 5 10 15 20 0 5 10 15 20 0 5 10 15 20 0 5 10 15 20
Airow: 9000 m3/h
heat output [kW] 26,4 23,4 20,4 17,4 14,1 33,3 30,3 27,3 24,3 21,2 39,5 36,5 33,5 30,5 27,5 45,7 42,7 39,7 36,7 33,7
outlet air temperature [°C] 8,6 12,6 16,6 20,6 24,6 10,8 14,8 18,9 22,9 26,9 12,8 16,9 20,9 24,9 28,9 14,8 18,9 22,9 26,9 30,9
water ow [m3/h] 1,2 1,0 0,9 0,8 0,6 1,4 1,3 1,2 1,0 0,9 1,7 1,6 1,5 1,3 1,2 2,0 1,9 1,8 1,6 1,5
pressure drop [kPa] 5,4 4,3 3,3 2,5 1,7 8,1 6,8 5,6 4,5 3,5 11,0 9,5 8,1 6,8 5,6 14,0 13,0 11,0 9,5 8,1