WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
USING AS REPLACEMENT
CONTROLLER
Conrm software version on existing controllers
See Parameter 80
If Parameter 80 is 18 or lower change Parameter 54 to 1
224-EN
WIRELESS CONTROLLER
INSTALLATION &
INTERFACE GUIDE


FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
Contents
1.0 SAFETY WARNING 1
2.0 LANDING DOOR CONTROLLER INSTALLATION 2
2.1 LANDING DOOR CONTROLLER MOUNTING 2
2.2 LANDING DOOR WIRING LAYOUT - STANDARD OPERATORS 3
2.3 LANDING DOOR WIRING LAYOUT - EXTRA HIGH TORQUE OPERATORS 4
2.4 LANDING DOOR POWER CONNECTIONS 5
2.5 LANDING DOOR ENCODER 6
2.6 LANDING DOOR OPERATORS - STANDARD OPERATORS 7
2.7 LANDING DOOR OPERATORS - EXTRA HIGH TORQUE 8
2.8 LANDING DOOR EMERGENCY UNLOCKING DEVICE (EUD) 9
2.9 LANDING DOOR ZONE SWITCH (ZNS) 10
2.10 LANDING DOOR HALL PUSHBUTTONS 11
2.11 LANDING DOOR LIGHT CURTAIN (OPTIONAL) 12
3.0 CAR DOOR (GATE) CONTROLLER INSTALLATION 13
3.1 CAR DOOR LOCATION AND WIRING LAYOUT 13
3.2 CAR DOOR POWER CONNECTIONS 14
3.3 CAR DOOR ENCODER 15
3.4 CAR DOOR (GATE) OPERATOR 16
3.5 RETIRING CAM MOTOR 17
3.6 CAR DOOR REVERSING EDGE (OPTIONAL) 18
3.7 WARNING BUZZER 19
4.0 COMMISSIONING 20
4.1 CAR DOOR 20
4.2 LANDING DOOR 21
4.3 LANDING AND CAR DOOR OPERATION AND TESTING 22
4.4 SEQUENCE OF OPERATION 22
4.5 POWER UP MODE / LOSS OF POWER 22
5.0 ELEVATOR CONTROLLER INTERFACE 23
5.1 ELEVATOR TO DOOR CONTROLLER INPUT CONNECTIONS 23
5.2 ELEVATOR TO DOOR CONTROLLER OUTPUT CONNECTIONS 24
5.3 LANDING AND CAR DOOR INTERLOCKING CIRCUITS 25

FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
6.0 CONTROLLER SETTINGS 26
6.1 DOOR MOTION PROFILES AND PARAMETERS 26
7.0 TROUBLESHOOTING 29
7.1 INDEPENDENT MODE 29
7.2 AUTOMATIC MODE 30
7.3 ELEVATOR INTERFACE OPERATION 31
7.4 ERROR CODES 32
7.5 LANDING DOOR LCD 33
7.6 CAR DOOR LCD 34
8.0 TECHNICAL SPECIFICATIONS 35
9.0 FCC/ISED DECLARATION 36
10.0 EC DECLARATION OF CONFORMITY 37

1
FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
Electrical Hazard Warning Symbol – Failure to observe this warning could result in electrical shock
or electrocution.
Operational Hazard Warning Symbol – Failure to observe this warning could result in dangerous or
unsafe conditions.
Installation Note: This product should be installed and serviced by a qualied elevator technician
familiar with its operation and hazards involved. Proper safety procedures must be followed when
working with this controller during installation and with control under power. Proper shielding and
grounding of this product is necessary to reduce the emissions of radio frequency interference (RFI)
which may adversely aect sensitive electronic equipment.
Electrical Wiring: Wire controller in accordance with the National Electrical Code, Canadian Electrical
Code, European Norms and/or any other local codes that apply.
General Contractor Note: A separate fuse disconnect switch is required for the door controllers. See
job specic wiring diagrams for disconnect and fuse requirements.
1.0 SAFETY WARNING
Enclosure Conduit Connections
TYPE 1, 4 & 4X
(Indoor Use Only)
CAUTION
Non-metallic enclosure does not provide grounding
between conduit connections. Use grounding bushing
and jumping wires.
WARNING
Do not mount controller on or above a combustible
surface.
The conduit hubs are to be connected to the conduit
before being connected to the enclosure.
To maintain the environmental rating of this enclosure,
install in any openings only listed or recognized conduit
hubs with the same environmental ratings as required,
in compliance with the installation instructions of the
device.
53
T&B Conduit Fittings
Rigid and Intermediate Metal Conduit Fittings
Methods of Bonding and Grounding (continued) —
Typical Installations Using Thomas & Betts Bonding and Grounding Wedge
T&B Series 3651
Bonding & Grounding Wedge
(1) T&B Series 142 Locknut
(2) T&B Series 122 Metallic Bushing
(3) T&B Series 3651 Bonding &
Grounding Wedge
(4)T&B Pressure (crimp type)
Terminal Lug.
Grounding electrode
Conductor enclosure
(Rigid Metal Conduit or
Intermediate Metal Conduit)
Service Enclosure
Service Equipment
Bonding Jumper
Equipment Bonding Jumper
Phase Conductors
Grounding electrode
conductor
Threaded Rigid Metal Conduit
or intermediate Rigid Metal Conduit
Sheet Metal Box or
Enclosure with unpunched
concentric or eccentric
rings remaining around
knockout opening.
Ground Bus
Acceptable Method for Bonding
Following
(i) Service Equipment
CEC Rule 10-614
(ii) Bonding for Circuits over 250 volts
CEC Rule 10-614
(iii) Bonding in Hazardous Locations
CEC Rule 18-074
When installed with a bonding jumper,
acceptable method of bonding where
unpunched rings remain around
concentric or eccentric knockouts in
sheet metal boxes or enclosures.
[CEC Rule 10-614].
Suggested Specifications
Bonding and Grounding Wedge
(Series 3650)
Bonding and Grounding Wedges
installed to effectively bond terminating
fitting or metal conduit to a cabinet, box,
enclosure or an auxiliary gutter or to
install bonding jumper around
concentric or eccentric knockouts shall
be of the type as manufactured by
Thomas & Betts—Series 3650.
Bonding and Grounding Wedge
shall be of rugged bronze/tin plated or
steel/electro-zinc plated.
CONFITMRO_1a_fr.pdf 53 9/21/2011 10:15:19 AM
!

2
FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
Mount the Landing door Controller
to the hoistway wall.
Use 1/4” inch hardware.
2.0 LANDING DOOR CONTROLLER INSTALLATION
2.1 LANDING DOOR CONTROLLER MOUNTING
Alternate Location
Lowest Landing
Recommended
location 4 Feet
Operator
Encoder
Floors above
lowest landing
Recommended
locations
Alternate Location
Interlock
SLA
Controller
locations
(where
provided)

3
FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
2.2 LANDING DOOR WIRING LAYOUT - STANDARD OPERATORS
Operator
Encoder
Interlock
Operator
Landing
Door
Junction
Box or
Trough
EUD
Hall Pushbuttons
HOISTWAY TROUGH
Door lock contact (DI) and
Door Close Contact (DC)
connect to elevator controller
Landing
Door
Controller
Power
DI & ZONE
DC

4
FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
2.3 LANDING DOOR WIRING LAYOUT - EXTRA HIGH TORQUE OPERATORS
Operator
Encoder
Interlock
Operator
Landing
Door
Junction
Box or
Trough
EUD
Hall Pushbuttons
HOISTWAY TROUGH
Door lock contact (DI) and
Door Close Contact (DC)
connect to elevator controller
Power
SLA
Controller
Landing
Door
Controller
DI & ZONE
DC

5
FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
2.4 LANDING DOOR POWER CONNECTIONS
Connect controllers in accordance with local electrical codes.
Power branch circuit should come from machine room disconnect
10 amp circuit for each line of doors. Use #14AWG [2mm]
copper wire for power connection.
• ON/OFF switch disconnects both lines
• If neutral is not used, main disconnect must break both lines.
WARNING
HIGH VOLTAGES
Read Safety Warning before
attempting to use this controller
CONDUIT AND SHIELD
GROUNDING LUG
!
The enclosure supplied is non-
metallic and does not provide
grounding between conduit
connections. Use grounding
bushings or jumper wires.
Power
GND L1 L2 / N
1 Ø Power
208-240V AC
5.5A, 50/60 Hz
Landing
Door
Controller

6
FREIGHT DOORS ICAR GATES ICAR ENCLOSURES
TECHNICAL SUPPORT 1-800-787-5020 ext 275
THE PEELLE COMPANY
®
Guide No.
Date:
224-EN
WIRELESS CONTROLLER
INSTALLATION & INTERFACE GUIDE
May 13 / 2021
D
E
T
A
I
L
A
GND COMM B A 12V
2.5 LANDING DOOR ENCODER
Install and wire encoder same side as the controller. Do not extend the encoder wire.
Shield
White
Ye l l o w
Green
Brown
Landing Door
Encoder
Landing Door
Encoder
ENCODER
Landing
Door
Controller
Indice