Parameters Settings
(Default Value)
Operation Manual
This brief manual is primarily meant for quick reference to wiring connections
and parameter searching. For more details on operation and application;
please log on to www.ppiindia.net
101, Diamond Industrial Estate, Navghar,
Vasai Road (E), Dist. Palghar - 401 210.
T: 0250 - 2391722/33/37/42
M: 07498799226
09321985369
Parameters
Parameters
Temperature
Alarm Type
Temperature
Alarm Setpoint
Temperature
Alarm Hysteresis 0.1 to 25.0 °C or °F
( 0.2)Default :
Direct
Reverse
( Direct)Default :
Temperature
Alarm Logic
( Yes)Default :
Yes
No
Temperature
Alarm Inhibit
Alarm Type
0.0 to 100.0%
(Default :
For Process Low : 0.0
For Process High : 100.0)
0.1 to 25.0%
(Default : 0.2)
-25.0 to +25.0°C
(Default : 0.0)
-25.0 to +25.0%
(Default : 0.0)
Settings
(Default Value)
Settings
(Default Value)
(Default : None)
None
Process High
Process Low
ALARM PARAMETERS FOR TEMPERATURE: PAGE-10
ALARM PARAMETERS FOR RELATIVE HUMIDITY: PAGE-11
ZERO-OFFSET PARAMETERS: PAGE-12
%RH Alarm Setpoint
%RH Alarm Hysteresis
%RH Alarm Logic
%RH Alarm Inhibit
Zero Offset
for Temp. Value
Zero Offset
for %RH Value
Parameters Settings
(Default Value)
OPERATOR PAGE AND PARAMETERS : PAGE - 0
View Only
Maximum Dry Bulb
Temperature Value
Minimum Dry - Bulb
Temperature Value View Only
Maximum %RH Value
View Only
Minimum Peak of RH
View Only
Reset Command
Reset Pass - Code 0 to 250
(Default : 0)
Keys Operation
Symbol Key Function
Press to enter or exit set-up mode.
DOWN
UP
ENTER
Press to store the set parameter value and
to scroll to the next parameter on the
PAGE.
Press to increase the parameter value.
Pressing once increases the value by one
count; keeping pressed speeds up the
change.
Press to decrease the parameter value.
Pressing once decreases the value by one
count; keeping pressed speeds up the
change.
PAGE
Front Panel
-50.0 to 150.0°C or
-58.0 to 302.0°F
(Default :
For Process Low : -50.0
For Process High : 150.0)
(Default : None)
Direct
Reverse
( Direct)Default :
( Yes)Default :
Yes
No
Parameters
0 to 250
(Default : 0)
Password For
Resetting
PV High - Low
Baud Rate
(Default : 4800)
1 to 8
(Default : 1)
Settings
(Default Value)
(Default : °C)
°C
°F
(Default : No)
Yes
No
SUPERVISORY PARAMETERS: PAGE-13
Unit Selection
for Temperature
Dry-Bulb Temperature
and % RH Min / Max
Monitoring
ID Number for
RH Loop
ID Number for
Temperature Loop
1 to 8
(Default : 2)
(Default : No)
Yes
No
PV Error Indications
Message
Over-range
(Dry-Bulb Temp. above
Max. Range)
Under-range
(Dry-Bulb Temp. below
Min. Range)
Open
(Sensor open / broken)
PV Error Type
FRONT PANEL LAYOUT
None
Process High
Process Low
Lower Readout
DOWN Key
PAGE Key
Alarm -1 Indicator
Upper Readout
Alarm-2 Indicator
ENTER Key
UP Key
PPI
HumiTherm-i
AL1 AL2
°C
%RH
Version : RTD Pt100, 3-wire for Temperature
DC Linear (Voltage) for Humidity
Composite Temperature + Humidity Indicator
HumiTherm-i