Primex SP6R-LSC Manuale utente

DUPLEX LIFT STATION CONTROL
BAR GRAPH
4-20 mA INPUT
AUTOMATIC ALTERNATION
MOTOR STATUS LEDs
User Manual
SP6R-LSC
CONTROLLER
Ashland, OH 800-363-5842
Clearwater, FL 800-349-1905
Detroit Lakes, MN 888-342-5753
Milford, OH 513-831-9959
WWW.PRIMEXCONTROLS.COM

TABLE OF CONTENTS
Specifications
Specifications
....................................................................................................
....................................................................................................
2
Introduction
Introduction
.......................................................................................................
.......................................................................................................
3
3
Warnings
Warnings
...........................................................................................................
...........................................................................................................
4
4
Installation & Dimension Data
Installation & Dimension Data
........................................................................
........................................................................
5-7
5-7
Electrical Connections
Electrical Connections
.................................................................................
.................................................................................
8-10
8-10
Function Keys / Displays
Function Keys / Displays
................................................................................
................................................................................
11
11
Setting Up Levels and Simulation
Setting Up Levels and Simulation
..............................................................
..............................................................
11-12
11-12
Configuration
Configuration
..............................................................................................
..............................................................................................
13-15
13-15
Configuration Mode Parameters
Configuration Mode Parameters
.....................................................................
.....................................................................
16
16
Run Mode Parameters
Run Mode Parameters
....................................................................................
....................................................................................
17
17
PRIMEX™ SP6R-LSC Level Controller User Manual
WWW.PRIMEXCONTROLS.COM

SPECIFICATIONS
INPUT TYPE
4-20 mA signal.
INPUT IMPEDANCE
100 ohms.
INPUT RESOLUTION
12 - bits, 0.1% of full scale.
SAMPLING CYCLE TIME
100 mS.
AVERAGING
8 consecutive samples.
ACCURACY
0.5% of full scale.
EXCITATION VOLTAGE
24 VDC, 30 mA available for loop powered transducers.
RELAY OUTPUTS
Four programmable relay outputs with LED indication. “Form C” (SPDT)
contacts: rated at 10A at 240 VAC.
LEVEL DISPLAY
Eight character alpha-numeric LED for process value and program parameters.
POWER
24 VDC (+/- 10%). 200 mA nominal, 400 mA max.
OPERATING TEMPERATURE
-15oC to 70oC (0oF to 150oF) at up to 0-90% RH non-condensing.
ENCLOSURE RATING
Front Panel: IEC Standard IP54 (with additional gasket) for indoor use.
Rear Case: IEC Standard IP20.
BAR GRAPH
20 segment bar graph display for process value. Each bar represents 5% of full scale.
PRIMEX™ 2 SP6R-LSC Level Controller User Manual

The SP6R-LSC Duplex Lift Station Controller monitors the level in the wet well and controls the
operation of one or two pumps.
In addition, it also monitors the pump run, pump seal failure and pump over temperature status. The con-
troller has a built in alternator, run time meters, cycle counters and a level simulator. Level can be moni-
tored via a submersible transducer or any other 4-20 mA device. The controller can be configured for
pump down or pump up applications.
SP6R-LSC LEVEL CONTROLLER INTRODUCTION
The standard SP6R-LSC lift station controller kit contains (see Figure 2 on page 5 of this manual):
• one SP6R-LSC lift station controller
• two mounting brackets for panel mounting
• a two pin power supply connector block
• a five pin transducer connector block
• two 6 pin relay output connector blocks
• a 12 pin pump status input connector block
The SP6R-LSC-N4X version includes a controller mounted in a NEMA 4X enclosure. These units are
ideal for replacing float switch or “bubbler” control systems.
PRIMEX™ 3 SP6R-LSC Level Controller User Manual

WARNINGS
Failure to read and understand the information provided in this manual may result in personal injury or
death, damage to the product or product failure. Please read each section in its entirety and be sure you
understand the information provided in the section and related sections before attempting any of the proce-
dures or operations given.
Failure to follow these precautions could result in serious injury or death. Keep these instructions with
warranty after installation. This product must be installed in accordance with National Electrical Code,
ANSI/NFPA 70 so as to prevent moisture from entering or accumulating within the controller housing.
See additional specifications on page 14 of this manual.
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this product.
A qualified service person must install and service this product according to applicable
electrical codes.
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable liquids. Do not install in hazardous locations
as defined by National Electrical Code,
ANSI/NFPA 70.
• Do not install in area with: excessive or conductive dust, corrosive or flammable gas, moisture or
rain, excessive heat, regular impact shocks or excessive vibration.
• Do not place in water or let water leak onto the controller.
• Do not allow debris to fall inside the unit during installation.
• Double-check all the wiring before turning on the power supply.
• Do not touch live wires.
• Stay as far as possible from high-voltage cables and power equipment.
• Leave a minimum of 10 mm space for ventilation between the top and bottom edges of the control-
ler and enclosure walls.
PRIMEX™ 4 SP6R-LSC Level Controller User Manual

RESET
1 2
Run
Seal Fail
Pump
Over Temp.
High Level
Lag Pump
Lead Pump
Low Level
FIGURE 1 Dimensions and panel cut-out. Dimensions are indicative and may be subject to change without notification.
INSTALLATION & DIMENSIONAL DATA
PRIMEX™ 5 SP6R-LSC Level Controller User Manual

PRIMEX™ 6 SP6R-LSC Level Controller User Manual
PANEL CUT OUT TEMPLATE
FOR SP6R-LSC LIFT STATION CONTROLLER
8.6” (218 mm)
4 7/16”
(112 mm)
cut along dotted line

FIGURE 2 Standard SP6R-LSC duplex lift station controller kit.
INSTALLATION & DIMENSIONAL DATA
PRIMEX™ 7 SP6R-LSC Level Controller User Manual

ELECTRICAL CONNECTION
FIGURE 3 Wiring diagram, back view -
with a submersible pressure transducer.
1. POWER
Connect power to terminal 1 and 2: the unit requires 24 VDC (+/- 10%).
2. SENSOR
LOOP POWERED TRANSDUCER
For loop powered transducers (2 wire) connect power conductor to terminal 1 and 2. If the cable is pro-
tected with an overall shield, connect the shield to terminal (3). Terminal 4 and 5 must be connected if
an output follower is not required. If no valid input is present, the controller will flash “SENSOR” and all
outputs will be de-energized, except the high level alarm.
SELF POWERED SIGNAL TRANSDUCER
Connect to terminal 2 and 4 and shield to terminal 3.
NOTE: To avoid ground loops, the shield of the signal cable must only be grounded at one end.
PRIMEX™ 8 SP6R-LSC Level Controller User Manual

FIGURE 6 Loop Powered Transducer
Connection. FIGURE 7 Self Powered Signal Connection.
PRIMEX
™9 SP6R-LSC Level Controller User Manual