Published: 28.08.2019 7 (15)
Parameter Available values Description
Offset CO2ppm -200...200 CO2 measurement tuning. The value can be adjusted by 10 ppm
steps.
ABC-Logic On / Off Automatic calibration function (On/Off).
Offset °C -3,0...3,0 Temperature measurement tuning. The value can be adjusted by
0,1 °C steps.
Offset %RH -5...5 Humidity measurement tuning, RH models. The value can be
adjusted by 1 % steps.
ML-SER tool display shows how much the current value is tuned. The measured value is shown in
brackets after the tuning value.
1.4.2.3 Output menu
You can change the output scaling of all outputs and the controller output direction through the output
menu. Also, the fixed controller output value and duration can be selected through the menu.
M
OK OK
Modbus ID
0-10V
Y1-Y4 range
OK
Direct
Output mode
OK
OFF
Fixed output
OK
100%
Fixed output
+/-
OK
12h
Deactivation
OUTPUT
Parameter Available values Description
Y1-Y4 range 0-10V / 2-10V / 0-5V Output scaling.
Output mode Direct / Reversed Controller output direction.
Fixed output OFF / 100% / 75% /
50% / 25% / 0%
Fixed output.
Deactivation 6h / 12h / 24h /
MANUAL
Fixed output deactivation timer.
1.4.2.4 Controller menu
The control output can be controlled either according to a one measurement value or according to the
maximum selection of all values.