User manual | Weather Station · 7
Configuration of analogue sensors in Agrónic 4000/5500
Sensor Number
Sensor
Number
Input
Number
Format
Voltage
(Vdc)
Temperature 1 1 1
12 Vdc
Humidity 2 2 4
Anemometer 3 3 5
Wind vane 4 4 16
Solar radiation 5 5 2
Internal configuration of analogue sensors in Agrónic Bit
Sensor Number
Sensor
Number
Input
Number
Format
Time
Reading (s)
Number
Output *
Voltage
(Vdc)
Humidity 1 00001 4 1.0" 00101
12 Vdc
Temperature 2 00002 1 1.0" 00101
Solar radiation 3 00004 2 0.4" 00002
Anemometer 4 00005 5 2.0" 00003
Wind vane 5 00006 16 2.0" 00001
Analogue Sensor Formats
Setting Humidity
Temperature
Solar Anemometer Wind vane
No. of integers 3 2 4 3 3
No. of decimals 0 1 0 0 0
Sign no yes no no no
Units % ºC W/m2km/h º
Calibration Point 1
Real value 800 mV 800 mV 800 mV 800 mV 800 mV
Logical value 000% - 40ºC 0000 W/m20 km/h 0º
Calibration Point 2
Real value 4000 mV 4000 mV 4000 mV 4000 mV 4000 mV
Logical value 100% 85.0ºC 2000 W/m2120 km/h 360º
Two calibration points must be configured for the sensor calculation from the controller menu
as follows.
From the Agrónic Bit menu, go to:
• Function | Settings | Sensors | Analogue | Formats
Once in, the settings should be the same as shown in the following table.
*This digital output number is used to power the sensor for a configurable time.
IMPORTANT
In the controllers, modify the values of format number 1, since by default it is configured for
another type of temperature sensor.