- Connect power for the devices
1. A separate power line for each device is recommended.
2. Wire neutrals together at another location per local electrical codes.
3. Bring the hot wire into the Node panel and land at the IN location at the terminal. (See
figure 2)
Figure 2
- Connect device motors to Relay Board as follows:
Requires a 4-wire line sized appropriately for the length of run (minimum recommended
size as follows):
•12 AWG for up to 90 feet of run
•10 AWG for 90 feet to 140 feet of run
•8 AWG for 140 feet to 240 feet of run
•6 AWG for 240 feet to 380 feet of run
1. Connect the motor wires from the devices to the Relay Board as noted in the design form.
Land all other devices as noted in the design form.
a. Terminal blocks on relay board only accept 10 AWG wires. If wire coming into
box is too large it must be stepped down in size to connect.
b. Device wires will land on the UP and Down locations at each terminal blocks.