Pts PTS90423 Series Manuale utente

1
All Rights Reserved, 2018
888-820-3508
Scan the QR code above to link to current document or click the link below:
PTS90423 Series
120V AC Power Distribution Panel
60A Main Breaker,
with External Rotary Disconnect Switch
Suitable for Use as Service Equipment
Small Cell, Pico, Micro, CRAN or Macro
INSTALLATION GUIDE
Compact 120V AC Power Distribution Load Center
60AMP Main Breaker with External Rotary Disconnect Switch
Single SPD (L-G) per Leg or Dual SPD (L-N) per Leg, (N-PE)
PTS90423 - Maximum 6 UL489 Breaker Positions with Single SPD
PTS90423 - Maximum 5 UL489 Breaker Positions with Dual SPD
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
2
All Rights Reserved, 2018
888-820-3508
Table of Contents
1.0 Model Overview ........................................................................................................................... 3
Figure 2: Dimensional Drawings. .............................................................................................. 4
1.1 Specifications .............................................................................................................................. 5
1.2 Breaker Specifications……..……….…………………………………………………….……………..6
1.3 Wiring Diagrams .......................................................................................................................... 7
1.4 Application………………………………………………………………………………………..……….8
2.0 Features ......................................................................................................................................... 8
2.1 Main Breakers ............................................................................................................................ 8
2.2 Distribution Breakers .................................................................................................................. 8
2.3 Optional Surge Protection Device…………………………………………………………….............8
2.4 Suitable for Use as Service Equipment....................................................................... .…….…....8
3.0 Inspecting and Unpacking of PTS90423 Series Panels ................................................................ 9
3.1 Steps to Inspect and Remove……………………………………………………………………….…9
4.0 Mounting. ...................................................................................................................................... 9
4.1 Mounting Bracket................................................................................................................................. 9
4.2 Mounting to Pole, Stanchion or Round Surfaces ........................................................................10
Figure 3: Mounting Example ..................................................................................................... 11
4.3 Mounting to flat surfaces ........................................................................................................... 11
Figure 4: Mounting Example. .................................................................................................... 11
5.0 Accessing Dead Front Plate and Breakers .................................................................................. 12
5.1 Removing Dead Front Access Plate ......................................................................................... 12
5.2 Wiring Ground Connections……………………………………………………………………………12
5.3 Wiring Load Connections………………………………………………………………………………13
Figure 6: Standard Wiring Example ............................................................................................ 14
5.4 Re-Installing Dead Front Access Plate...................................................................................... 15
Figure 7: Dead Front Access Plate Re-installed .......................................................................... 15
6.0 Installation Review ....................................................................................................................... 17
7.0 Document and Revision Control…………………………………………………………………..…….18
5.5 Labeling the Breakers............................................................................................................... 16
Figure 1: PTS90423.................................................................................................................... 3
Figure 5: Enclosure Grounding.................................................................................................. 12
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
3
All Rights Reserved, 2018
888-820-3508
1.0 Model Overview
The PTS90423 Series of Small Cell AC Power Distribution Load Centers
provides a custom factory fully assembled load center for Small Cell and CRAN
deployments.
PTS90423 – Small Cell AC Power Distribution Load Center
Figure 1: PTS90423
The PTS90423 Series products are:
Suitable for Use as Service Equipment.
Conforms to UL Standard 67
Certified to: CSA Standard C22.2 #29
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
4
All Rights Reserved, 2018
888-820-3508
PTS90423 Outline Drawing
Caution: Installation shall be completed per all NEC and Local Codes. Do not install
PTS90423 Systems before reading and understanding all specifications and
installation guides provided. Installation should be performed by a qualified installer.
Figure 2: Dimensional Drawings
Example with Dual SPD
and 5 Load Positions
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
5
All Rights Reserved, 2018
888-820-3508
1.1 Specifications
Electrical
Operating Voltage
120VAC
Main Breaker
60Amp MAX
Distribution Breakers
Max of (6) UL489 Breakers 0-20Amp
Power Input Wire Size
#14 - #4 awg Cu - Al
Power Output Wire Size
#14 - #4 awg Cu - Al
Neutral and Ground Contacts
#14 - #4 awg Cu - Al
Rated Conditional Short
10kAIC
SPD, Dual MOV (L-N) & (N-G)
20Ka 8/20us Nominal
External Ground Connection
2-hole ¼-20 w/ 5/8” spacing
Physical
Housing Material
Powder Coated Aluminum
Breaker Access
Thumb knob and lockable hasp
Wire Access, Internal
¼” hex head or #2 Phillip
Housing Dimensions (H x W x D)
(Excludes hasp and bracket)
PTS90423 16.15" x 6.68" x 6.285"
Unit Weight / Shippping Weight
PTS90423 11lbs / 13lbs
Mounting
Supplied Bracket
Environmental
Operating Temperature
(-40°C) to (60°C)
Relative Humidity
95% Non-Condensing
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
6
All Rights Reserved, 2018
888-820-3508
1.2 Breaker Specifications
Breaker Specifications
PTS P/N
Description
PT-KM1N-07A
UL489A DIN rail Breaker, 07 AMP
PT-KM1N-10A
UL489A DIN rail Breaker, 10 AMP
PT-KM1N-12A
UL489A DIN rail Breaker, 12 AMP
PT-KM1N-16A
UL489A DIN rail Breaker, 16 AMP
Torque Recommendations
Main QOU Breaker
42-47 in-lbs
Load Breaker
17-22 in-lbs
Surge Protection
17-22 in-lbs
Neutral Block and Bar
24-27 in-lbs
Ground Bar
24-27 in-lbs
Caution: Installation shall be completed per all NEC and Local Codes. Do not install
PTS90423 Systems before reading and understanding all specifications and
installation guides provided. Installation should be performed by a qualified installer.
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
7
All Rights Reserved, 2018
888-820-3508
1.3 Wiring Diagrams
PTS90423 Wiring Diagram
Caution: Installation shall be completed per all NEC and Local Codes. Do not install
PTS90423 Systems before reading and understanding all specifications and
installation guides provided. Installation should be performed by a qualified installer.
Drawing above shows equipped with Neutral to Ground
Bond Required when Using for Service Equipment.
Suitable for Use as Service Equipment
NEUTRAL to GROUND
BOND Require when using for
SERVICE EQUIPMENT
Drawing above shows equipped with Single SPD,
supporting up to 6 load breaker positions.
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
9
All Rights Reserved, 2018
888-820-3508
1.4 Application
The PTS90423 is a compact AC Load Centers designed for Small Cell and CRAN Deployments
where distribution of AC power is required.
The PTS90423 Series of compact AC Load Centers can also be used for AC Power Distribution
applications where limited space exists, excluding the ability to use a larger load center.
The PTS90423 Series of compact AC Load Centers is Suitable for Use as Service Equipment, or
as a sub-tending branch panel when modernizing or expanding existing sites.
2.0 Features
The PTS90423 Series of Small Cell AC Load Centers packaged as a custom
configuration, ready for install in new and expansion environments.
2.1 Main Breaker
The PTS90423 Systems can support main breaker ampacity up to 60Amps.
2.2 Distribution Breakers
The PTS90423 Systems support upto (6) UL489 Breakers rated from 0-20 Amps.
2.3 Optional Single-SPD or Dual–SPD Protection
The PTS90423 Systems can support either Single SPD (L-G) or Dual SPD (L-N) & (N-G) modules.
2.4 Suitable for Use as Service Equipment
The PTS90423 is Suitable for Use as Service Equipment when bonding the
Neutral and Ground and following code requirements.
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
10
All Rights Reserved, 2018
888-820-3508
3.0 Inspecting and Unpacking of PTS90423 Series Load Centers
3.0.1 Inspect the packaging for obvious signs of rough handling and/or external damage.
3.0.2 Review Installation Guide.
3.0.3 Remove from plastic packaging.
Caution: Installation shall be completed per all NEC and Local Codes. Do not install
PTS90423 Systems before reading and understanding all specifications and
installation guides provided. Installation should be performed by a qualified installer.
4.0 Mounting
The PTS90423 Systems are certified for outdoor installations This section
provides installations guidelines to insure the appropriate requirements are met.
4.1 Mounting Bracket
4.1.1 A mounting bracket is included and pre-installed with the enclosure and can be used
as a template, or the mounting bracket detail on page 4 can be used, if preferred.
4.1.2 If mounting bracket is removed, a lock-tite like adhesive should be applied to the
screws when replacing.
www.pactechsol.comwww.pactechsol.com

PTS 90423 Series Small Cell
AC Power Distribution Load Centers
Installation Guide
11
All Rights Reserved, 2018
888-820-3508
4.2 Mounting enclosure to Pole, Stanchion or Round Surfaces
4.2.1 Customer is responsible to identify suitable location for mounting
4.2.2 Install Pole Straps and tighten per specifications -or -
4.2.3 Mark and drill anchors locations using template provided.
4.2.4 Wood Poles should be Lag Bolted or Through Bolted
4.2.5 Fiberglass or Metal pole shall be strap mounted.
4.2.6 Torque to mounting hardware specifications.
Figure 3: Mounting Configuration for enclosure on a
Pole, Stanchion or Round Surface
www.pactechsol.comwww.pactechsol.com