Installation Guide
Flammable & Toxic Gas Detectors
Smart Alarm Controllers
Fire & Gas System Engineering
Technical Service & Support
Warning: Read & understand contents of this manual prior to
operaon. Failure to do so could result in serious injury or death.

Gas Detector Installation and Power-up
1
2
www.rcsystemsco.com
GETTING STARTED
Finalize Installation
What you need (not included)
1. Small Flathead Screwdriver
2. Phillips Screwdriver (for poly enclosure)
3. Wire
(RC Systems recommends: Belden 3124A
Multi-Conductor wire or equivalent.)
Installation of Gas Detector
Remove windowed lid from unit.
1. AL Enclosure -
a. Loosen lid set screw
b. Rotate lid clockwise and remove
c. Loosen thumb screws on display to remove
display and access terminals
2. PY Enclosure -
a. Unscrew lid screws (4) to access terminals.

Figure 1 - SenSmart 5000 wiring
3
Remote Sensor
What you need (not included)
1. Small Flathead Screwdriver
2. Phillips Screwdriver (for poly enclosure)
3. Wire
(RC Systems recommends: Belden 3124A
Multi-Conductor wire or equivalent.)
1. Connect 10-30VDC power lead to TB2.1
(See Figure 1)
2. Connect Common lead to TB2.3 (See Figure 1)
3. Connect signal lead to TB2.5. (4-20mA Out)
(if required)(See Figure 1)
Installation of Gas Detector
Remove windowed lid from unit.
1. AL Enclosure -
a. Loosen lid set screw
b. Rotate lid clockwise and remove
c. Loosen thumb screws on display to remove
display and access terminals
2. PY Enclosure -
a. Unscrew lid screws (4) to access terminals.

SenSmart 5000 Wiring Instructions
4
www.rcsystemsco.com
Follow the steps below to first connect the SenSmart 5000
I/O Board to the Remote Sensor:
1. Verify SenSmart 5000 is powered off.
2. Remove lid from SenSmart 5000 and remote sensor
3. Connect (24V) TB.1.1on the Remote sensor board to
the10-30VDC power supply on SenSmart 5000 I/O
board (TB2.1). (Either double up wires on TB2.1 or
connect to the shared power supply (TB2.1). (Figure 2)
4. Connect 10-30VDC Ground (GND) (TB1.2) wires to
power terminal COM (TB2.2). (Figure 2)
5. Connect 10-30VDC Ground (GND) (TB1.2) wires to
power terminal COM (TB2.3). (Figure 2)
6. Connect Modbus Terminal A (TB1.3) from the remote
sensor board to terminal A1 on the Relay Board
(TB1.1). (Figure 2)
7. Connect Modbus Terminal B (TB1.4) from the remote
sensor board to terminal B1 on the Relay Board
(TB1.2). (Figure 2)
REMOTE SENSOR INSTALLATION

Remote Sensor
Connecting to the Remote Sensor
5Follow the steps below to connect the RS485 Modbus/Relay
Option board to the Remote Sensor:
1. Locate the 10-0532 relay/Modbus board or 10-0531
Modbus board.
(This board is
“piggybacked” behind the 10-0387 SenSmart 5000
CPU/Display Board.”
2. Connect Modbus Terminal A (TB1.3) from the remote
sensor board to terminal A on Modbus Board (TB1.1).
(Figure 2)
3. Connect Modbus Terminal B (TB1.4) from the remote
sensor board to terminal B on Modbus Board (TB1.B).
(Figure 2)
Terminating Resistors:
The terminating resistor (J2) jumper should be placed in
position A on the remote sensor.
REMOTE SENSOR INSTALLATION

.
Figure 2 - Remote Sensor Power Up
www.rcsystemsco.com

Configuration Instructions
6
www.rcsystemsco.com
CONFIGURATION
Transmitter (SenSmart 5000):
1. Swipe Edit on the transmitter using a magnet.
2. Swipe Down until Comm Settings is highlighted.
3. Swipe Edit to enter the Comm Settings menu.
4. Swipe Edit to enter the Comm 1 Settings menu.
5. Swipe Edit until display shows Remote Sensor.
6. Swipe Down to highlight Board Setup.
7. Swipe Edit to enter Search mode.
Remote Sensor:
Hold Edit Button on 10-2080 Remote Sensor Option Board
until the Board Setup Menu is displayed on the transmitter
LED will fade in and out on the remote board. (Figure 2)
Remote Option Board Configuration: (Figure 2)
Transmitter (SenSmart 5000):
1. Highlight Set Remote ID on transmitter.
2. Swipe Edit to Set Remote ID
3. Swipe Edit to save Remote ID settings.
4. Highlight Exit Program Mode.
5. Swipe Edit to exit program mode.
Entering Configuration Mode:
Important:
When configuring your remote sensor ensure both the sensor
transmitter and the10-2080 Remote Sensor Option are readily
accessible, as some steps require actions to be performed in a
timely manner.
7

Transmitter (SenSmart 5000):
1. Swipe Edit on the transmitter using a magnet.
2. Swipe Down until Comm Settings is highlighted.
3. Swipe Edit to enter the Comm Settings menu.
4. Swipe Edit to enter the Comm 1 Settings menu.
5. Swipe Edit until display shows Remote Sensor.
6. Swipe Down to highlight Board Setup.
7. Swipe Edit to enter Search mode.
Remote Sensor:
Hold Edit Button on 10-2080 Remote Sensor Option Board
until the Board Setup Menu is displayed on the transmitter
LED will fade in and out on the remote board. (Figure 2)
Remote Option Board Configuration: (Figure 2)
Transmitter (SenSmart 5000):
1. Highlight Set Remote ID on transmitter.
2. Swipe Edit to Set Remote ID
3. Swipe Edit to save Remote ID settings.
4. Highlight Exit Program Mode.
5. Swipe Edit to exit program mode.
Figure 3- Configuration

.
COMPLETE SETUP
Finalize Installation
1. Replace display and tighten screws.
2. Replace enclsoure lid.
3. Apply power to unit and observe power up screen.
4. After the warm up period, observe gas type and gas
concentration on screen.
5. Using the magnet wand, swipe Down Key on the display.
Follow on-screen prompts to perform calibration.
www.rcsystemsco.com
1

8621 Highway 6
Hitchcock, TX 77563
Tel: (409)986-9800
Fax: (409) 986-9880
www.rcsystemsco.com
R.C. Systems provides 24/7 superior technical support from experts right
here in our local facility.
If you are in need of any assistance during the setup of this product, you
may contact our main office and your call will be directed appropriately.
At R.C. Systems we are proud to supply quality products and are happy to
help if you have any questions or concerns.