GAS LINE (A)
The gas train is to be connected on the right of
the burner, by flange 1) (A).
If it is necessary to connect it on the left of the
burner, loosen nuts and screws 3) and 4),
remove blind flange 2) together with its gasket
and fit them to flange 1) tightening the nuts and
screws.
Note
Once assembled the gas train, check for leaks.
GAS TRAIN (B)
It must be type-approved according to Stand-
ards and is supplied separately from the burner.
KEY TO LAYOUT (B)
1 - Gas input pipe for main burner
2 - Manual valve
3 - Low gas pressure switch
4 - Safety shut-off valve with SKP10
5 - NO vent valve
6 - Regulating shut off valve with SKP20
7 - Gas input pipe for pilot
8 - Gas adjustment butterfly valve
9 - Burner
10- High gas pressure switch
11- Manual valve (for seal control)
12- Pilot regulator
IMPORTANT
The pressure at the head of the burner from
table (C) - refers to zero in the combustion
chamber; to obtain true pressure, measured by
a U-type manometer, (see fig. (A) page 10) add
the counter-pressure of the boiler.
Note
See the accompanying instructions for the
adjustment of the gas train.
(A)
(B)
Main
gas supply
10
2
3
45
6
11
Vent
Pilot
gas supply
212
5
4
7
Vent
9
8
1
4
NCV
kW
Combustion
Head
mbar
Gas
butterfly +
Adaptor
mbar
GCV
MBtu/hr
Combustion
Head
“WC
Gas
butterfly +
Adaptor
“WC
RS 300/E BLU
1350 8.4 1.6 5112 3.3 0.63
1500 9.4 2.0 5680 3.7 0.79
2000 12.4 3.5 7574 4.9 1.38
2500 13.7 5.4 9467 5.4 2.13
3000 15.0 7.8 11361 5.9 3
3500 20.2 10.6 13254 7.9 4.2
3800 23.0 13.0 14390 9 5.1
RS 400/E BLU
1800 5.8 2.8 6816 2.3 1.1
2000 7.6 3.5 7574 3 1.38
2500 11.9 5.4 9467 4.7 2.13
3000 16.3 7.8 11361 6.4 3
3250 18.5 9.2 12307 7.3 3.62
3500 21.1 10.6 13254 8.3 5.17
4000 27.6 13.9 15148 10.8 5.47
4500 33.0 18.0 17042 13 7
RS 500/E BLU
2500 11.2 4.6 9467 4.4 1.81
3000 15.4 6.7 11361 62.64
3500 19.5 9.1 13254 7.7 3
4000 24.7 11.8 15148 9.7 3.82
4500 30.0 15.0 17042 11.8 4.64
5000 35.9 18.5 18935 14.1 5.55
5200 38.0 20.0 19692 15 5.9