Scarlet Tech WL-410 Manuale utente

WL-410/XB
User Guide
Wireless
Wind Alarm System

WL-410/XB Wireless Wind Alarm System consists of a wind speed sensor and a receiver. The sensor
measures wind speed and transmits data to the receiver. The 3.5-inch LCD display of receiver shows
readings on the main page and the history graphs are shown in dierent pages. According to the preset
values, the receiver can trigger local alarms such as LED lights and buzzer, or trigger external indication via
3 built-in relays when measured wind speeds exceeding the thresholds.
A 868 MHz radio frequency module is installed in the receiver of model WL-410 and WL-410XB. In mode
WL-410XB, an additional Bluetooth Low Energy chip is installed in the receiver to enable smartphone
communication functionality. WL-410XB sensor output power is stronger (+14 dBm) than WL-410, allowing a
longer transmission distance. An optional 4-20 mA current loop module is available to both WL-410 and
WL-410XB to make long distance cable transmission possible.
Overview
Instrument at a Glance
SensorReceiver
3 programmable alarm relay outputs
433/868/915 MHz
1,300 meter
Bluetooth
30 meter
4-20 mA outputRelays
Smartphone App
iOS/Android
External
indicators
Control room
/ Equipment

Wind cup
(replaceable)
Battery cap
(O-ring sealed)
Aluminum
sensor body
Wind cup
(replaceable)
Aluminum
sensor body
Power
When the “Lo battery” appears on the display, replace the sensor battery. Take off the battery cover (on the
bottom) by turning it counterclockwise. Pull out the battery holder and insert new battery (Lithium 3.6 V AA).
Range
The connection between sensor and receiver goes through free 868 MHz band (optionally 908MHz).
Transmission range is up to 500 meters (1300 meters at models XB) - at 10 m sensor mounting height and
when there is no obstacle between the sensor and the display unit. The range is much shorter inside
buildings. Normally the signal can be received through two to three walls.
Address
The correspondent sensor address has been present at the factory. Always set the address to correspond to
the address of the sensor from which the receiver will receive data. Address of the sensor is indicated on the
sensor label and in the interior of the sensor battery compartment.
Sensor unit switches ON automatically when the anemometer cups revolve. It switches OFF 6 hours after
the anemometer cups stop revolving. In ON state, the sensor updates wind speed data every two seconds.
Sensor
wind vane
Sensor & Receiver

Port 1 Port 2 Port 3
Buzzer
Yellow LED for Pre Alarm 2
Up/Mute button
Down/History button
Set menu button
Pre Alarm 2 indicator
Pre Alarm 1 indicator
Max Alarm indicator
Red LED for Max AlarmLCD display
Antenna (SMA connector)
The indication light on the top of the LCD display blinks when the receiver receives signals from the sensor
(every 2 seconds if the reception is good). Signal strength is numerically shown in dB.
When the sensor stop sending data (in OFF state) or the signal is lost for more than 30 seconds, the “No
data” appears on the display, indicating that the receiver doesn’t receive data from the sensor (sensor OFF
or out of range).
The threshold wind speed of Pre Alarm 1, Pre Alarm 2 and Max Alarm can be configured via setting menus.
Please see the section “Settings” for more details.
• Pre Alarm 1 triggers one LED indicator sit beside the LCD screen.
• Pre Alarm 2 triggers two LED indicators sit beside the LCD screen and the yellow LED on the top of LCD
display. It sounds the buzzer interleaved.
• Max Alarm triggers all three LED indicators sit beside the LCD screen and the red LED on the top of LCD
display. It sounds the buzzer continuously.
Receiver

12 to 24 V DC source
Working voltage of receiver is 12 to 24 V DC. Please plug the DC power source to the corresponding jack on
the circuit board after opening the front panel.
Relay 3 When wind speed exceeds the set on pre alarm 1, the relay 3 will activate. Please see section
“Settings” for more details.
Relay 2 When wind speed exceeds the value set on pre alarm 2, the relay 2 will activate and yellow light will
start blinking and buzzer will sound with interruptions. When the sound alarm is activated you can mute it by
pressing upper key for 3 seconds. Please see section “Settings” for more details.
Relay 1 When set value exceeds the relay 1 will activate, red light will flash and buzzer will continuously
sound. When sound alarm is activated you can mute it by pressing upper key for 3 seconds. Please see
section “Settings” for more details.
The relay jacks are by the side of DC power.
NOTE: Please make sure the polarity is correct otherwise the receiver will be damaged.
DC Power
Relays & External Indicators

Scarlet provides free iOS and Android Apps. Users can download directly via QR link below:
Before pairing, please turn on the Bluetooth function on
your mobile device. Make sure the mobile device with
Android 4.3 or newer with Bluetooth Low Energy (BLE).
For iPhone, the
device should be at least iPhone 4s or newer.
In Application setting menu always set the address
corresponding to the address of the sensor from which you
wish to receive data. Address of the sensor is indicated on
the label and in the interior of the battery compartment.
For example, enter the sensor address showed on the
label, e.g. 78. Once it’s paired, the data will be automatically
transmitted to the mobile device.
iOS Wind Smart Android Wind Smart
Smart Phone Applications
Sensor Pairing
Bluetooth
(WL-410XB and WL-410XB 4-20mA model)

Current wind speed
Signal strength
Temperature Pre alarm 2 threshold
Max alarm threshold
Peak wind bar graph
Current wind
bar graph
Wind speed unit
Scarlet WindPro display consists of 3 pages including: 1) readings of wind speed; 2) alarm settings and 3)
graphs to provide users information for project management.
By pressing HIST key user can navigate to page 2 and 3 to see the wind speed and max. alarm history. To
switch back to the first-page user can long pressing HIST key for 3 seconds or leave the device alone for 1
minute.
The contents of the display are shown above. Note: in both bar graphs, the max alarm value set by user is
always on the 3/4 bar height. One icon not shown in the photo is data packet receiving indicator and it
flashes by the side the signal strength.
8 hours peak wind speed history graph with 5 minutes resolution, each
row presents the peak wind speed during 5 minutes
First Page
Second Page
.
With upper button pressed at power ON – RESET is performed (all settings except “Sensor Address”and “WS
Cal. Factor” goes to default values).
8 hours Maximum alarm history graph with 5 minutes resolution.
Third Ppage
Restore Receiver to Default
Display

Factory default Settable range Description
Wind speed 72 km/h 1…50 m/s Max alarm limit
On delay 0 sec 0…600 sec Minimum time of exceed wind
speed to activate the max alarm
Off delay 0 min 0…60 min
Delay of alarm switch OFF after
wind speed drop below preset
level
Relay Normal Normal/interleaved Inverted operation of relay
Setting of Parameters
Max Alarm
Settings
1. Hold pressed SET key to enter the setting menu. If the password protection is active, enter correct pass-
word. The options of settings are shown on display.
2. Select the option by using up and down keys and press SET key to enter into selected option.
3. By up and down keys select the parameter you wish to adjust and press SET key to enter into selected
parameter. The adjustable parameter blinks.
4. By up and down key adjust the parameter value. Press SET to enter new value and move to next parame
ter.
5. Exiting setting menu: hold pressed SET key to move back for one level. Anemometer also returns to
normal operation after 2 minutes of inactivity.

Factory default Settable range Description
Wind speed 52 km/h 1…50 m/s Pre alarm 2 limit
On delay 0 sec 0…600 sec Minimum time of exceed wind
speed to activate the pre alarm 2
Off delay 0 min 0…60 min
Delay of alarm switch OFF after
wind speed drop below preset
level
Relay Normal Normal/interleaved Inverted operation of relay
Factory default Settable range Description
Wind speed 42 km/h 1…50 m/s Pre alarm 1 limit
On delay 0 sec 0…600 sec Minimum time of exceed wind
speed to activate the pre alarm 1
Off delay 0 min 0…60 min
Delay of alarm switch OFF after
wind speed drop below preset
level
Relay Normal Normal/interleaved Inverted operation of relay
Pre Alarm 2
Pre Alarm 1

Factory default Settable range Description
Sensor address Enclosed sensor 1…255 Set the sensor address of your
Wind speed sensor
Averaging period 2 sec 2/10/30 sec Averaging period for showed
wind speed
Wind speed unit km/h m/s, km/h, mph,
knots Unit of displaying wind speed
Temperature unit ° C ° C or ° F Unit of displaying Temperature
20 mA output 180 km/h 10…50 m/s
Wind speed at 20 mA output
4mA = 0 km/h
20 mA = seted value wind speed
* applicable only at model with
additional 4-20 mA output
Password No No
Yes:0000…9999
Activation of password
protection and setting of
password
Sound alarm On On/Off Switching sound alarm ON and
OFF
Language English English/French Language selection
Wind speed
calibration factor +0.0% Calibration factor for wind speed
(-15,0 ...+15,0% in 0,5% steps)
Bluetooth On On/Off
Power ON/OFF Bluetooth
transmitter
* applicable only at WSM
W410XB model
General Settings
Altri manuali per WL-410
1
Questo manuale è adatto per i seguenti modelli
2
Indice
Manuali Sistema di sicurezza popolari di altre marche

EDM
EDM Solution 6+6 Wireless-AE Manuale utente

Highway Safety Group
Highway Safety Group EA401 Manuale utente

Siren
Siren LED GSM Manuale utente

Detection Systems
Detection Systems 7090i Istruzioni per il montaggio

Se-Kure Controls
Se-Kure Controls MicroMini SK-4841 Manuale utente

Siemens
Siemens FDM273 Manuale utente