SPECIFICATIONS
Power Supply 12-30VDC/24VAC(1), 100mA max.
Analog Outputs
Temperature 0-5/10V standard; Scaling 50°F to 95°F (10°C to 35°C)
Thermistor/RTD values optional
CO2 and RH 0-5/10V
Update Rate Continuous
Programmable Relay Solid-state output, 1A @ 30VAC/DC, N.O.
Analog LCD Menu
Parameters (2)
Spt, Set point, Hi (On) Sets relay turn-on threshold (800ppm default)
SPh, Set point, hysteresis (O) Sets the relay turn-o hysteresis (100ppm default)
SCL, Scaling 0-2000ppm or 0-5000ppm (2000ppm default)
AJ, Adjustment CO2 Oset adjustment +/-250ppm (0 default)
CAL, Auto Calibration Period O, 7 days, 14 days, 30 days, 60 days (14 days default)
C, Displayed Temp Unit degrees fahrenheit (default), C degrees celsius
LvL Analog Output Scale 5v 5.0V full scale, 10v 10.0V full scale (default)
UN, Run Mode Displays temp and optional CO2 and RH
CO2
Type Non-dispersive Infrared (NDIR)
Accuracy ±40ppm, ±3% of reading (400-2000ppm)
Range 0-2000/5000ppm (2000ppm default); Programmable up to 10,000ppm
Response time 60 seconds to 90% reading
Sample rate 3 seconds
Relative Humidity
Type Digital CMOS
Accuracy 2% models, +/-2% over 10 to 90%RH range
Resolution 0.05%RH
Hysteresis +/-1%RH
Temperature coecient Compensated on-board
Response time (3) 30s
Sample rate 3s
Operating range/Output Scale 0 to 100%RH (non-condensing)
Long term drift <0.5%RH per year
Operating conditions (4) -20° C to 60° C @ RH>90%
-20° C to 80° C @ RH=50%
Type Silicon Bandgap
Temperature
(with RH element)
Nominal Accuracy +/-0.3° C (operating range)
Maximal Accuracy +/-0.5° C (at 25° C), +/-1.0° C (operating range)
Resolution 0.01° C
Repeatability +/-0.1° C
Response time (3) 30s
Sample rate 3s
Type NTC Thermistor
Nominal Accuracy +/-0.5° C (operating range)
Temperature
(without RH element) Maximal Accuracy +/-1.0° C (at 25° C), +/-2.0° C (operating range)
Resolution 0.05° C
Repeatability +/-0.2° C
Sample Rate 100 milliseconds
Operating Environment Temperature 32 to 122F (0 to 50C)
Humidity 0-95% non-condensing
Enclosure Material ABS Plastic
Dimensions 4.85”h x 3.25”w x 1.19”d
(1) One side of transformer, secondary is connected to signal common. Dedicated transformer is recommended.
(2) Quick Start Menu parameters shown, for additional capabilities see ‘AQ Series User’s Guide’.
(3) Time for reaching 63% of reading at 25° C and 1 m/s airow
(4) Long term exposures to conditions outside normal range at high humidity may temporarily oset the RH reading (+3%RH after 60 hours.)
Revised 10/7/2014 Document #152-0161-0B